AIRCON
AIRCON
Hvac System Design: Refining The Air Conditioning Of Drift Motor Speedway
ME 519
Air Conditioning and Ventilation
Systems
Presented to:
Engr. Ricardo Bote, PME
PREFACE
This research focuses on designing an HVAC (Heating, Ventilation,
and Air Conditioning) system for Drift Motor Speedway, a themed park in
Valley Fair Town Center, Taytay, Rizal, Philippines. With the growing need
loads, assessing ventilation needs, and choosing the right equipment, the
design aims to maintain a steady indoor temperature and good air quality
while using less energy.
well as the industry experts for their valuable insights and help. The
knowledge and skills gained from this project not only help create a better
HVAC system for Drift Motor Speedway but also lay the groundwork for
TABLE OF CONTENT
CHAPTER 1: INTRODUCTION
have been increasing. The area has reached up to 47°C in some areas,
and experts claim that this will continue in the succeeding months.
market, which has been increasing steadily but is expected to slow down
The most critical problem facing the institution was indoor heat and
humidity that was above the normal level. It made both customers and
60%, and indoor temperatures should range between 72°F and 80°F. The
testing occurred during an event, where the few people present caused
only minor heat buildup. However, the situation could worsen with more
activity, especially if the go-kart track was in use. The use of floor-
standing fans and exhaust fans by the establishment was not enough to
dissipate the heat that had been gathered, thus causing discomfort
among customers and employees. Such discomfort led to a reduction in
the success of the business if the issue was not addressed appropriately.
• Definition of Terms
construction environment.
evaporator.
security systems.
optimization.
used.
conditioning equipment.
• Purposes of the Hvac
heat and the furnace is responsible for providing warmth. Air flows
through ducts across rooms, and the thermostat controls the temperature.
Fans, filters, air inlets and outlets, and heat exchangers are all key
They also consider all sun-generated heat, generated within the building
the system ensure that it would run effectively, avoid energy waste, and
Cooling load is the total heat that has to be controlled to maintain the
sources like occupants, equipment, and lighting. Heat that originates from
design, and even purpose of the building. This balance decides the overall
The amount of cooling needed may also differ from building type.
weather condition. However, buildings with all their heating coming from
the interior, like people and equipment, typically don't have much
variation in their cooling loads. In reality, an efficient HVAC design will
In air conditioning, there are four types of heat flow rates that change over
time:
• Cooling load: The total amount of heat the cooling system removes,
including heat from inside the building and external sources like air
• Heating: Low activity areas should be kept at 68°F (20°C) and high
activity areas at 55°F (13°C).
pressure is required.
Supply and Return Fans: These are the largest noise producers.
between 31.5 to 250 Hz, mainly in lower frequencies. Fans make the
fins help to distribute air but can create noise. The more the air is
• Introduction
from the same building. Over time, it evolved into a vibrant entertainment
• Vicinity Map
• Layouts
𝑄 = 𝐴 • 𝑈 • ∆𝑇
𝑤𝑎𝑙𝑙
Where:
(m2 )
∆𝑇
𝑈 = 1
𝑇
Where:
= Temperature Difference
1 𝑥
𝑥 𝑥 1
𝑅 =
+ 1 + 2 + 𝑛 +
ℎ 𝑘
𝑖 1
𝑘 𝑘 ℎ
2 𝑛 0
DESCRIPTION SURFACE AREA OF THE WALL & ROOF
ROOF 943.8615 m2
NORTH WALL
𝑄 = 8528. 6228 𝑊
EAST WALL:
𝑄 = 3707. 3817 𝑊
𝑄 = 4785. 2645 𝑊
𝑄 = 1526. 5569 𝑊
WEST WALL:
𝑄 = 4504. 6293 𝑊
ROOF:
𝑄 = 25958. 9695 𝑊
𝑈 = 1
)+( (0.01 𝑚)
)+(0.12 (𝑚^2−𝐾)
)
𝑄 = 25958. 9695 𝑊
load.
• Calculation for Internal Load
𝑄 =𝑄 +𝑄
𝑝𝑒𝑜𝑝𝑙𝑒 𝑝𝑠 𝑝𝑙
Where:
𝑄 = 𝑞 ×𝑁
𝑝𝑠 𝑠 𝑝
𝑄 = 𝑞 ×𝑁
𝑝𝑙 𝑙 𝑝
Total
Heat, Sensib Laten
Degree Location W le t Heat,
of Heat, W
Activity W
Adul Adjusted, Low V High V
t
Mal
e
Walking, Drug 160 145 75 70 - -
standin store,
g bank
Heavy Factory 440 425 170 255 54 19
Work
𝑄𝑝𝑠 = 7125 𝑊
𝑄 = (170 𝑊)×5
𝑝𝑠
𝑄 = 850 𝑊
𝑝𝑠
𝑄 = (255 𝑊)×5
𝑝𝑙
𝑄 = 1275 𝑊
𝑝𝑙
𝑄 = 82×10𝑊×1. 2
𝑙𝑖𝑔ℎ𝑡
𝑄 = 984 𝑊
𝑙𝑖𝑔ℎ𝑡
𝑄 = 𝑞 ×𝑁
𝑒𝑞𝑢𝑖𝑝𝑚𝑒𝑛𝑡 𝑅 𝐸
𝑄 = 𝑞 ×𝑁
𝐸𝑞𝑢𝑖𝑝𝑚𝑒𝑛𝑡 𝑒𝑚 𝑒
Where:
𝑞 (1−𝐸 )
)𝐹 𝐹
= 𝑃(
𝑀
𝑒𝑚
𝐸 𝑈𝑀
𝐿𝑀
FOR COMPUTERS:
FOR MONITOR:
𝑄 = 25 𝑊 ×4 = 100 𝑊
𝑒𝑞𝑢𝑖𝑝𝑚𝑒𝑛𝑡
𝑄 = 100 𝑊
𝑒𝑞𝑢𝑖𝑝𝑚𝑒𝑛𝑡
FOR GO-KART:
𝑞𝑒𝑚 = 375 𝑊
7125 W
SENSIBLE HEAT
850 W
PEOPLE
6650 W
LATENT HEAT
1275 W
LIGHTING 984 W
COMPUTER 166 W
EQUIPMENT LAPTOP 100 W
GO-KART 375 W
TOTAL 17525 W
• Introduction
Outdoor air is often considered pure and fresh with the right
hydrogen, argon, carbon dioxide, and water vapor (1%). Humans and
animals need oxygen to survive, and since nitrogen and other gases are
inert, they do not harm living things. Humans inhale oxygen and exhale
oxygen levels in closed spaces. However, before it enters, the outdoor air
contaminate the air. To maintain oxygen levels and purify the air, outside
air must be supplied. The amount of outdoor air needed in a typical office
contaminants, for example, 20 cubic feet per minute (CFM) per person. In
Ventilation
room and circulating it throughout the space. The main goal of ventilation
Just like lungs, buildings need proper ventilation to ensure fresh air
flows in and polluted air flows out. Indoor air can contain moisture, odors,
gases, dust, and other pollutants. To keep the air safe inside, fresh
outdoor air is necessary to dilute these indoor pollutants. Air enters and
• Spot ventilation such as fans that remove air from areas like
bathrooms.
Infiltration
building's exterior and due to pressure differences between the inside and
outside. When outdoor air enters through open doors or windows, it is
outdoor air is colder and denser than the indoor air. It is influenced by
wind speed, direction, and how airtight the building is. In tall buildings,
Exfiltration
to be airtight, which means windows are not meant to be opened, and they
are pressurized. During the summer, the indoor air is cooler and denser
than the warmer outside air. As a result, the natural flow of air is from the
inside to the outside. Because these buildings are pressurized, air leakage
happens from the interior to the exterior. Exfiltration is usually minimal and
𝑄 =𝐶 𝐴
𝐼 𝐷 𝑂
𝐶𝐷 = 0. 40 + 0. 0045|𝑇𝑖 − 𝑇𝑜 |
𝑄𝑆 = ρ𝑎𝑖𝑟 • 𝐶𝑝𝑎𝑖𝑟 • 𝑄𝐼 • Δ𝑇
Description Values
𝑄 = 0. 40495(2. 4𝑚×1. 2𝑚 )
𝐼
FOR SENSIBLE HEAT:
3
𝐾𝑔 𝐾𝐽 𝐽
𝑄 = 1. 2 ×1. 0062 ×1000 ×0. 34000878292 ×(30. 5 − 20)𝐾
𝑆 𝑚^3
(𝐾𝑔−𝐾)
1𝑘𝐽 𝑠
𝑄 = 4310. 6721 𝑊
𝑆
Using a steam table to get the value of partial pressure of indoor dry air
𝑃 = 4. 6538 𝑘𝑃𝑎
𝑑
𝑊 ( 𝑘𝑔
= 0. 622
𝑣
2.8760 𝑘𝑃𝑎
101.325 𝑘𝑃𝑎 − 2.8760 𝑘𝑃𝑎
𝑃 = 4. 375 𝑘𝑃𝑎
𝑑
2.5920 𝑘𝑃𝑎
101.325 𝑘𝑃𝑎 − 2.5920 𝑘𝑃𝑎
𝑘𝐽−𝑘𝑔
𝑚^3
𝑘𝑔
𝑘𝑔
𝑄 𝑎 ×0. 34000878292 ×(0. 01817085988
− 0.=01632914947
3010 𝑣 )
𝑣
𝐿 𝑚 −𝑘𝑔 𝑠
𝑣
𝑄 = 1. 8849 𝑘𝐽
( 1000𝐽 )
𝑘𝑔
𝑎
𝑘𝑔
𝑎
𝐿 𝑠
1𝑘𝐽
𝑄 = 1884. 8551 𝑊
𝐿
𝑉
𝑟𝑜𝑜𝑚
3
= 6130. 265 𝑚
For the air change per hour, Based on ASHRAE 16.15 and 16.29 for
ℎ𝑜𝑢𝑟
𝑞 = 3. 405702778
3
𝑚
3
𝑘𝑔 𝑘𝐽 1000𝐽
𝑄 = 1. 2 ×1. 0062 × ×3. 405702778 ×(30. 5 − 20)𝐾
𝑠 𝑚
(𝑘𝑔−𝐾)
1𝑘𝐽 𝑠
𝑄 = 43177. 9085 𝑊
𝑠
3
𝑘𝑔 𝑘𝐽 1000𝐽
𝑄 = 1. 2 ×2466 × ×3. 405702778 ×(30. 5 − 20)𝐾
𝐿 𝑚
𝑘𝑔
1𝑘𝐽 𝑠
𝑄𝐿 = 105820. 6344 𝑊
(outdoor air, duct leakage, and heat gain, reheat, fan, and pump energy,
18.1).
CHAPTER 7: PSYCHOMETRICS
• Introduction
examine some of the most common processes used in HVAC and how
9.6
9.6 + 7.925
𝑅𝑆𝐻𝐹 = 0. 5478
Outdoor Air Sensible Heat
𝑂𝐴𝑆𝐻 = 1. 20 𝑥 𝑉𝑒𝑛𝑡𝑖𝑙𝑎𝑡𝑖𝑜𝑛 (𝐿/𝑠) 𝑥 ∆𝑡
𝑂𝐴𝑆𝐻 = 1. 20 𝑥 383. 4713 𝑥 (31 − 21)
𝑂𝐴𝑆𝐻 = 4. 6016556 𝐾𝑊
Outdoor Air Latent Heat
𝑂𝐴𝐿𝐻 = 3. 0 𝑥 𝑉𝑒𝑛𝑡𝑖𝑙𝑎𝑡𝑖𝑜𝑛 (𝐿/𝑠) 𝑥 ∆𝑊
𝑂𝐴𝐿𝐻 = 3. 0 𝑥 383. 4713𝑥(28. 5 − 7. 7)
𝑂𝐴𝐿𝐻 = 23. 9286091 𝐾𝑊
𝑅𝑆𝐻𝐹 = 0. 5375
Total Sensible Heat (Tsh)
𝑇𝑆𝐻 = 𝑅𝑆𝐻 + 𝑂𝐴𝑆𝐻
𝑇𝑆𝐻 = 9. 6 𝐾𝑊 + 4. 6016556 𝐾𝑊
𝑇𝑆𝐻 = 14. 2017 𝐾𝑊
Total Latent Heat (Tlh)
𝑇𝐿𝐻 = 𝑅𝐿𝐻 + 𝑂𝐴𝐿𝐻
𝑇𝐿𝐻 = 7. 925 𝐾𝑊 + 4. 6016556 𝐾𝑊
𝑇𝐿𝐻 = 12. 5267
Grand Total Heat (Gth)
𝐺𝑇𝐻 = 𝑇𝑆𝐻 + 𝑇𝐿𝐻
𝐺𝑇𝐻 = 14. 2017 𝐾𝑊 + 12. 5267 𝐾𝑊
𝐺𝑇𝐻 = 26. 7284 𝐾𝑊
Grand Sensible Heat Factor (Gshf)
14.2017
𝐾𝑊
26.7284
𝐾𝑊
𝐺𝑆𝐻𝐹 = 0. 5313
metals and may use different types of ducts within a single setup. Ducts
are channels that allow air to flow through heating, ventilation, and air
conditioning (HVAC) systems to bring in fresh air and remove stale air. The
key airflows include supply air, which enters the space; return air, which
leaves the space; and exhaust air, which is vented outside. Ducts often
carry ventilation air as part of the supply to maintain indoor air quality
150 GPM
Interpolate:
air into and out of conditioned spaces to maintain the right temperature,
humidity, and air quality. This process relies on an air distribution system
Ducts are crucial in air distribution as they are the pathways for air
within the HVAC system. They deliver fresh air to occupied spaces and
remove stale air, ensuring a continuous cycle that supports comfort. The
duct system includes different types of airflow: supply air that enters the
space, return air that is recirculated, and exhaust air that is vented
outside. Ventilation air is often part of the supply of air, bringing fresh
outdoor air into the system to maintain good indoor air quality, which is
Air distribution systems are made from materials like fiberglass and
coated metals, chosen based on the building’s needs and the system’s
cost, and the environment. The system’s design often combines different
indoor air quality and ensuring thermal comfort. Proper selection and
• BILLS OF MATERIALS
U/COST
PRODUCT QTY UNIT (PHP) TOTAL COST
DESCRIPTION (PHP)
AIR CONDITIONING UNIT
ACCU (RXYQ120TAYDU) -
33.4kW 7 UNITS 314679.00 2202753.00
FCU (FXFQ48TVJU) - 14kW 17 UNITS 168000.00 2856000.00
DUCTING
G. I. SHEETS # 18 25 UNITS 2450.00 61250.00
G. I. SHEETS # 18 15 UNITS 1422.00 21330.00
PIPING
COPPER PIPE, HD TYPE L 46 LENGTH 3620.00 166520.00
COPPER PIPE, HD TYPE L 23 LENGTH 3165.00 72795.00
TOTAL 5307853.00
reduce energy use. The system will have to work harder to cool as it takes
resistant windows, into areas where the HVAC system operates. These
modifications can decrease the load of the cooling system and reduce
cooling units, air filters, and ventilation parts, regularly can prevent
proper care will extend the system's lifespan and maintain its efficiency.
very low and does not cause harm to the ozone layer, making it a
REFERENCES
• Ng, G.(2023, April 3). Extreme heat in the Philippines: The impact
on health. Medical Channel Asia
https://medicalchannelasia.com/extreme-heat-in-the-philippines-the-
impact-on-health/
• Philippines: Air conditioner demand 2022.
(2023, June 26). Statista.
https://www.statista.com/statistics/909967/philip
pines-ac-demand- HYPERLINK
"http://www.statista.com/statistics/909967/philip
pines-ac-demand-units/"units/
• Philippines air conditioning market - Forecast (2020 - 2025).
(2020, December 29). LinkedIn.
https://www.linkedin.com/pulse/philippines-air-conditioning-market-
forecast-2020-2025-prapul-palli
• McQuiston, F. C., Spitler, J. D., & Parker, J. D. (2005). Heating,
Ventilating, and Air Conditioning:
Analysis and Design (6th ed.). Pearson Education, Inc
• Weather Climate. Summary of the climate of Taytay, Rizal.
https://weatherandclimate.com/philippines/rizal/taytay#:~:text=The
%20district's%20yearly%20temperature
%20is,%25%20of%20the%20time)