VF 2045-Smoke
VF 2045-Smoke
VF2045-00 / VF2046-00
Standard Features
• High signal-to-noise ratio and sensitivity stability
effective in a wide range of environmental conditions
• Wide viewing angle alarm indicators
• Automatic drift compensation and
maintenance indication
• Built-in magnetic test feature
• Break-away, hidden locking feature
for use with NS bases
• UL 268 7th Edition listed
VF2045 VF2046 • Optimized reduction to false alarms and
enhanced reaction time to real fires
Product Overview
The VF2045 and VF2046 are conventional multi-criteria Photoelectric Smoke Detectors. They can be used in all
open areas where Photoelectric Smoke Detectors are required. The newly developed multi-spectrum smoke
categorization technology detects smoldering and flaming fires fueled by traditional materials and polyurethane
while reducing nuisance alarms.
The detector utilizes a green/red LED for indication of status. In a normal standby condition, the LED flashes green
every 3 seconds. When the detector senses that its sensitivity has drifted outside the UL listed sensitivity window,
the LED will flash Red every 3 seconds. When the detector senses smoke and goes into alarm status, the LED will
latch on Red.
The detector utilizes an IR-LED and Blue LED to distinguish smoke characteristics.
The VF2046 adds a heat sensing element to also detect 20°F/minute rate of temperature rise or 135°F temperature,
whichever occurs first.
APPROVED
Manufactured by Kentec Electronics Ltd.
Dartford, DA11JQ, United Kingdom PENDING
PENDING
VES Fire Detection Systems | 620 Allendale Road | King of Prussia, PA 19406 | 800.270.3066 | www.ves-network.com
©2021 VES Fire Detection Systems. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Revised July 2021
Technical Specifications
VF2045 VF2046
Sensing Element Smoke (IR LED, Blue LED, Photodiode) Smoke (IR LED, Blue LED, Photodiode)
Heat (Thermistor)
Supply Voltage Operating Voltage Range 8-35 VDC
Absolute Max Voltage 42 VDC
Maximum Voltage Ripple 8200mVAC
Maximum Input Capacitance 0.01uF
Current Consumption Standby Current 59μA
Remote Indicator Current 8.0mA (Internally Limited)
Minimum Allowable Alarm Current 5mA
Maximum Allowable Alarm Current 150mA
Startup Time 25s (Max)
Current 160A (Max)
Reset Time 100ms (Min)
Voltage 2.5V (Min)
Smoke Density Range 1.50 - 3.50%/ft @ 300 FPM Open Area
1.50 - 3.50%/ft @ 1000 FPM In Duct
1.50 - 3.50%/ft @ 2000 FPM In Duct
1.50 - 3.50%/ft @ 3000 FPM In Duct
1.50 - 3.50%/ft @ 4000 FPM In Duct
Compatible Bases VF2050-00 and VF2051-00
Heat Sensitivity Range NA 135°F or 20°F/ min rise (whichever occurs first)
Operating Temperature Range 32°F to 120°F
UL Listed Ambient Temperature 32°F to 120°F
Storage Temperature Range -22°F to +140°F
Operating Humidity Limit <95%RH at 104°F, <80%RH at 120°F
Dimension 3.94” diameter x 1.77” tall 3.94” diameter x 2.18” tall
Color Ivory
Weight 3.4 oz
VES Fire Detection Systems | 620 Allendale Road | King of Prussia, PA 19406 | 800.270.3066 | www.ves-network.com
©2021 VES Fire Detection Systems. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Revised July 2021