Lecture 6pdf-Analysis and Design of Slabs
Lecture 6pdf-Analysis and Design of Slabs
FF=1.0 kPa
Ceiling=1.0 kPa
Electromechanical=0.10 kPa
Concrete unit weight= 24 kN/m3
LL=2.40 kPa
Beam size= 300mm by 600mm
111.607
ℎ𝑚𝑖𝑛 = ቐ111.607
130.208 Governs !
ℎ = 135 𝑚𝑚
Wu=1.2(5.34) + 1.6(2.40)
Wu=10.248 kN/m
Location Coeff
1 1/24
12 1/14
2 1/10
2 1/11
23 1/16
3 1/11
3 1/11
34 1/16
4 1/11
4 1/10
45 1/14
5 1/24
𝐴𝑏 𝜋/4(10)2
𝐴𝑠
1000=
315.7
(1000) = 248.78 Governs !
𝑠 = 245 𝑚𝑚
Asmin = 0.0020Ag
Asmin = 0.0020(1000)(135)
Asmin = 270 mm2
𝐴𝑏 𝜋/4(10)2
𝐴𝑠
1000=
270 (1000)
= 290.888 Governs !
LL=2.40 kPa
Flr. Fin=1.0kPa
𝛾𝑐𝑜𝑛𝑐 =23.6kN/m3
Ceiling=0.70kPa
Electromech=0.10kPa
Beam=300mmx450mm
B. Design Load, Wu
WDL=[0.70+1.0+0.1+23.6(0.125)](1 m strip)
WDL=4.75 kN/m
WLL=2.40(1 m strip)
WLL=2.40 kN/m
Wu=1.2(4.75) + 1.6(2.40)
Wu=9.54kN/m
Main Reinforcement
𝐴𝑏
𝐴𝑠𝑚𝑖𝑛 = 0.0020𝐴𝑔 1000 = 452
𝑠≤ 𝐴 𝑠
= 0.002(1000)(125) 3ℎ = 375
= 250 mm2 450
L/S ≤ 2.0
hmin= 133.333 𝑚𝑚
h= 135 𝑚𝑚
5
m = = 0.714
7
qu = 1.2[1.25+0.1+0.55+24(0.135)]+1.6(3.8)
qu = 12.248 KPa
𝐻−0.062 0.714−0.7
=
0.055−0.062 0.8−0.7
H=0.06102
𝐻𝐸−0.047 0.714−0.7
=
0.041−0.047 0.8−0.7
HE=0.04616
M= Cqu𝑙𝑛2 (1.0)
qu = 12.248 KPa
ln = 4.7 m
𝐴𝑏 𝜋/4(10)2
𝐴𝑠
1000=
499.4
(1000) = 157.270 𝐴𝑠𝑚𝑖𝑛 = 0.0020𝐴𝑔
𝑠=൞ 2ℎ = 2 135 = 270 = 0.002(1000)(135)
450 = 270 mm2
SHORT DIRECTION
LOCATION COEFF MOMENT b d 𝜌𝑅𝐸𝑄 As Asmin Spacing
M= Cqu𝑙𝑛2 (1.0)
qu = 12.248 KPa
ln = 4.7 m
𝐴𝑏 𝜋/4(10)2
𝐴𝑠
1000=
332.2
(1000) = 236.423
𝑠=൞ 2ℎ = 2 135 = 270
450
𝐴𝑠𝑚𝑖𝑛 = 0.0020𝐴𝑔
= 0.002(1000)(135)
= 270 mm2
LONG DIRECTION
LOCATION COEFF MOMENT b d 𝜌𝑅𝐸𝑄 As Asmin Spacing
FF=1.0 kPa
Ceiling=1.0 kPa
Electromechanical=0.10 kPa
Concrete unit weight= 24 kN/m3
LL=2.40 kPa
Beam size= 300mm by 550mm
hmin = perimeter/180
4(5000)
hmin= 180
hmin= 111.111 𝑚𝑚
h= 115 𝑚𝑚
5
m = = 1.0
5
qu = 1.2[1.0+0.1+1.0+24(0.115)]+1.6(2.4)
qu = 9.672 kPa
LOCATION COEFF
A=0.025 A 0.025
AE=0.037 AE 0.037
E=0.049 E 0.049
M= Cqu𝑙𝑛2 (1.0)
qu = 9.672 KPa
ln = 4.7 m
SHORT DIRECTION
LOCATION COEFF MOMENT b d 𝜌𝑅𝐸𝑄 As Asmin Spacing
LOCATION COEFF
A=0.025 A 0.025
AB=0.037 AB 0.037
B=0.049 B 0.049
M= Cqu𝑙𝑛2 (1.0)
qu = 9.672 KPa
ln = 4.7 m
𝐴𝑏 𝜋/4(10)2
𝐴𝑠
1000=
329.3
(1000) = 343.448 𝐴𝑠𝑚𝑖𝑛 = 0.0020𝐴𝑔
𝑠=൞ 2ℎ = 2 115 = 230 = 0.002(1000)(115)
450 = 230 mm2
LONG DIRECTION
LOCATION COEFF MOMENT b d 𝜌𝑅𝐸𝑄 As Asmin Spacing