REM620 Appl
REM620 Appl
This document and parts thereof must not be reproduced or copied without written permission from
ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized
purpose.
The software or hardware described in this document is furnished under a license and may be used,
copied, or disclosed only in accordance with the terms of such license.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names
mentioned in this document may be trademarks or registered trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
www.abb.com/relion
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or product
description and are not to be deemed as a statement of guaranteed properties. All persons responsible
for applying the equipment addressed in this manual must satisfy themselves that each intended
application is suitable and acceptable, including that any applicable safety or other operational
requirements are complied with. In particular, any risks in applications where a system failure and/or
product failure would create a risk for harm to property or persons (including but not limited to
personal injuries or death) shall be the sole responsibility of the person or entity applying the
equipment, and those so responsible are hereby requested to ensure that all measures are taken to
exclude or mitigate such risks.
This product has been designed to be connected and communicate data and information via a network
interface which should be connected to a secure network. It is the sole responsibility of the person or
entity responsible for network administration to ensure a secure connection to the network and to take
the necessary measures (such as, but not limited to, installation of firewalls, application of
authentication measures, encryption of data, installation of anti virus programs, etc.) to protect the
product and the network, its system and interface included, against any kind of security breaches,
unauthorized access, interference, intrusion, leakage and/or theft of data or information. ABB is not
liable for any such damages and/or losses.
This document has been carefully checked by ABB but deviations cannot be completely ruled out. In
case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than
under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or
damage resulting from the use of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European Communities on the
approximation of the laws of the Member States relating to electromagnetic compatibility (EMC
Directive 2014/30/EU) and concerning electrical equipment for use within specified voltage limits (Low-
voltage directive 2014/35/EU). This conformity is the result of tests conducted by ABB in accordance
with the product standard EN 60255-26 for the EMC directive, and with the product standards EN
60255-1 and EN 60255-27 for the low voltage directive. The product is designed in accordance with the
international standards of the IEC 60255 series.
Contents
Contents
1 Introduction............................................................................................... 9
1.1 This manual.............................................................................................................................................. 9
1.2 Intended audience...................................................................................................................................9
1.3 Product documentation.......................................................................................................................10
1.3.1 Product documentation set................................................................................................ 10
1.3.2 Document revision history...................................................................................................11
1.3.3 Related documentation........................................................................................................ 11
1.4 Symbols and conventions.................................................................................................................... 11
1.4.1 Symbols....................................................................................................................................11
1.4.2 Document conventions........................................................................................................ 12
1.4.3 Functions, codes and symbols............................................................................................13
2 REM620 overview.................................................................................... 18
2.1 Overview..................................................................................................................................................18
2.1.1 Product version history........................................................................................................ 18
2.1.2 PCM600 and IED connectivity package version.............................................................. 18
2.2 Operation functionality........................................................................................................................19
2.2.1 Optional functions................................................................................................................ 19
2.3 Physical hardware..................................................................................................................................19
2.4 Local HMI.................................................................................................................................................22
2.4.1 Display..................................................................................................................................... 22
2.4.2 LEDs......................................................................................................................................... 23
2.4.3 Keypad..................................................................................................................................... 23
2.5 Web HMI.................................................................................................................................................. 25
2.6 Authorization ........................................................................................................................................ 26
2.6.1 Audit trail.................................................................................................................................27
2.7 Communication .................................................................................................................................... 29
2.7.1 Self-healing Ethernet ring................................................................................................... 30
2.7.2 Ethernet redundancy............................................................................................................30
2.7.3 Process bus............................................................................................................................ 32
2.7.4 Secure communication........................................................................................................ 34
REM620 7
Application Manual
Contents
5 Glossary.................................................................................................. 133
8 REM620
Application Manual
1MRS757655 E Introduction
1 Introduction
REM620 9
Application Manual
Introduction 1MRS757655 E
Figure 1: The intended use of documents during the product life cycle
10 REM620
Application Manual
1MRS757655 E Introduction
1.4.1 Symbols
The electrical warning icon indicates the presence of a hazard which
could result in electrical shock.
The warning icon indicates the presence of a hazard which could result in
personal injury.
REM620 11
Application Manual
Introduction 1MRS757655 E
The information icon alerts the reader of important facts and conditions.
The tip icon indicates advice on, for example, how to design your project
or how to use a certain function.
12 REM620
Application Manual
1MRS757655 E Introduction
REM620 13
Application Manual
Introduction 1MRS757655 E
14 REM620
Application Manual
1MRS757655 E Introduction
REM620 15
Application Manual
Introduction 1MRS757655 E
16 REM620
Application Manual
1MRS757655 E Introduction
REM620 17
Application Manual
REM620 overview 1MRS757655 E
2 REM620 overview
2.1 Overview
REM620 is a dedicated motor management relay perfectly aligned for the
protection, control, measurement and supervision of medium-sized and large
asynchronous and synchronous motors requiring also differential protection in the
manufacturing and process industry.
®
REM620 is a member of ABB’s Relion protection and control product family and its
620 series. The 620 series relays are characterized by their functional scalability and
withdrawable-unit design.
The 620 series has been designed to unleash the full potential of the IEC 61850
standard for communication and interoperability of substation automation devices.
The 620 series relays support a range of communication protocols including IEC
61850 with Edition 2 support, process bus according to IEC 61850-9-2 LE, IEC
®
60870-5-103, Modbus and DNP3. Profibus DPV1 communication protocol is
supported by using the protocol converter SPA-ZC 302.
18 REM620
Application Manual
1MRS757655 E REM620 overview
- Event Viewer
- Disturbance Handling
- Application Configuration
- Signal Matrix
- Graphical Display Editor
- Communication Management
- IED User Management
- IED Compare
- Firmware Update
- Fault Record tool
- Load Record Profile
- Differential Characteristics Tool
- Lifecycle Traceability
- Configuration Wizard
- AR Sequence Visualizer
- Label Printing
- IEC 61850 Configuration
- IED Configuration Migration
Download connectivity packages from the ABB Web site www.abb.com/
substationautomation or directly with Update Manager in PCM600.
REM620 19
Application Manual
REM620 overview 1MRS757655 E
20 REM620
Application Manual
1MRS757655 E REM620 overview
Rated values of the current and voltage inputs are basic setting parameters of the
protection relay. The binary input thresholds are selectable within the range 16…176
V DC by adjusting the binary input setting parameters.
The connection diagrams of different hardware modules are presented in this
manual.
See the installation manual for more information about the case and the
plug-in unit.
1 The 0.2/1 A input is normally used in applications requiring sensitive earth-fault protection and
featuring core-balance current transformers
REM620 21
Application Manual
REM620 overview 1MRS757655 E
Overcurrent protection
SG1 DR Earth-fault protection
Enabled Trigger
Voltage protection
SG4 AR Supervision
Enabled Disable Autoreclose in progress
Arc detected
SG5
Enabled
SG6
Enabled
2.4.1 Display
The LHMI includes a graphical display that supports two character sizes. The
character size depends on the selected language. The amount of characters and
rows fitting the view depends on the character size.
22 REM620
Application Manual
1MRS757655 E REM620 overview
Table 4: Display
3 4
1 Header 3 Content
2 Icon 4 Scroll bar (displayed when needed)
Figure 3: Display layout
2.4.2 LEDs
The LHMI includes three protection indicators above the display: Ready, Start and
Trip.
There are 11 matrix programmable LEDs and 16 programmable push buttons with
LEDs on front of the LHMI. The LEDs can be configured with PCM600 and the
operation mode can be selected with the LHMI, WHMI or PCM600.
2.4.3 Keypad
The LHMI keypad contains push buttons which are used to navigate in different
views or menus. With the push buttons you can give open or close commands to
objects in the primary circuit, for example, a circuit breaker, a contactor or a
disconnector. The push buttons are also used to acknowledge alarms, reset
indications, provide help and switch between local and remote control mode.
REM620 23
Application Manual
REM620 overview 1MRS757655 E
Figure 4: LHMI keypad with object control, navigation and command push buttons
and RJ-45 communication port
The LHMI keypad on the left side of the protection relay contains 16 programmable
push buttons with red LEDs.
The buttons and LEDs are freely programmable, and they can be configured both
for operation and acknowledgement purposes. That way, it is possible to get
acknowledgements of the executed actions associated with the buttons. This
combination can be useful, for example, for quickly selecting or changing a setting
group, selecting or operating equipment, indicating field contact status or
indicating or acknowledging individual alarms.
24 REM620
Application Manual
1MRS757655 E REM620 overview
REM620 25
Application Manual
REM620 overview 1MRS757655 E
2.6 Authorization
Four user categories have been predefined for the LHMI and the WHMI, each with
different rights and default passwords.
The default passwords in the protection relay delivered from the factory can be
changed with Administrator user rights.
If the relay-specific Administrator password is forgotten, ABB can provide a one-
time reliable key to access the protection relay. For support, contact ABB. The
recovery of the Administrator password takes a few days.
User authorization is disabled by default for LHMI but WHMI always uses
authorization.
26 REM620
Application Manual
1MRS757655 E REM620 overview
REM620 27
Application Manual
REM620 overview 1MRS757655 E
PCM600 Event Viewer can be used to view the audit trail events and process related
events. Audit trail events are visible through dedicated Security events view. Since
only the administrator has the right to read audit trail, authorization must be used
in PCM600. The audit trail cannot be reset, but PCM600 Event Viewer can filter data.
Audit trail events can be configured to be visible also in LHMI/WHMI Event list
together with process related events.
To expose the audit trail events through Event list, define the Authority
logging level parameter via Configuration > Authorization > Security.
This exposes audit trail events to all users.
28 REM620
Application Manual
1MRS757655 E REM620 overview
2.7 Communication
The protection relay supports a range of communication protocols including IEC
®
61850, IEC 61850-9-2 LE, IEC 60870-5-103, Modbus and DNP3. Profibus DPV1
communication protocol is supported by using the protocol converter SPA-ZC 302.
Operational information and controls are available through these protocols.
However, some communication functionality, for example, horizontal
communication between the protection relays, is only enabled by the IEC 61850
communication protocol.
The IEC 61850 communication implementation supports all monitoring and control
functions. Additionally, parameter settings, disturbance recordings and fault
records can be accessed using the IEC 61850 protocol. Disturbance recordings are
available to any Ethernet-based application in the IEC 60255-24 standard
COMTRADE file format. The protection relay can send and receive binary signals
from other devices (so-called horizontal communication) using the IEC 61850-8-1
GOOSE profile, where the highest performance class with a total transmission time
of 3 ms is supported. Furthermore, the protection relay supports sending and
receiving of analog values using GOOSE messaging. The protection relay meets the
GOOSE performance requirements for tripping applications in distribution
substations, as defined by the IEC 61850 standard.
The protection relay can support five simultaneous clients. If PCM600 reserves one
client connection, only four client connections are left, for example, for IEC 61850
and Modbus.
All communication connectors, except for the front port connector, are placed on
integrated optional communication modules. The protection relay can be
REM620 29
Application Manual
REM620 overview 1MRS757655 E
Client A Client B
Network A
Network B
30 REM620
Application Manual
1MRS757655 E REM620 overview
PRP
Each PRP node, called a double attached node with PRP (DAN), is attached to two
independent LANs operated in parallel. These parallel networks in PRP are called
LAN A and LAN B. The networks are completely separated to ensure failure
independence, and they can have different topologies. Both networks operate in
parallel, thus providing zero-time recovery and continuous checking of redundancy
to avoid communication failures. Non-PRP nodes, called single attached nodes
(SANs), are either attached to one network only (and can therefore communicate
only with DANs and SANs attached to the same network), or are attached through a
redundancy box, a device that behaves like a DAN.
COM600
SCADA
REM620 31
Application Manual
REM620 overview 1MRS757655 E
HSR
HSR applies the PRP principle of parallel operation to a single ring, treating the two
directions as two virtual LANs. For each frame sent, a node, DAN, sends two frames,
one over each port. Both frames circulate in opposite directions over the ring and
each node forwards the frames it receives, from one port to the other. When the
originating node receives a frame sent to itself, it discards that to avoid loops;
therefore, no ring protocol is needed. Individually attached nodes, SANs, such as
laptops and printers, must be attached through a “redundancy box” that acts as a
ring element. For example, a 615 or 620 series protection relay with HSR support
can be used as a redundancy box.
32 REM620
Application Manual
1MRS757655 E REM620 overview
Common Ethernet
Station bus (IEC 61850-8-1), process bus (IEC 61850-9-2 LE) and IEEE 1588 v2 time synchronization
GOOSE
GOOSE
GOOSE
GOOSE
GOOSE
GOOSE
GOOSE
SMV
SMV
SMV
SMV
SMV
SMV
SMV
Figure 10: Process bus application of voltage sharing and synchrocheck
The 620 series supports IEC 61850 process bus with sampled values of analog
currents and voltages. The measured values are transferred as sampled values
using the IEC 61850-9-2 LE protocol which uses the same physical Ethernet network
as the IEC 61850-8-1 station bus. The intended application for sampled values is
sharing the measured voltages from one 620 series protection relay to other
devices with phase voltage based functions and 9-2 support.
The 620 series protection relays with process bus based applications use IEEE 1588
v2 Precision Time Protocol (PTP) according to IEEE C37.238-2011 Power Profile for
high accuracy time synchronization. With IEEE 1588 v2, the cabling infrastructure
requirement is reduced by allowing time synchronization information to be
transported over the same Ethernet network as the data communications.
REM620 33
Application Manual
REM620 overview 1MRS757655 E
Primary Secondary
IEEE 1588 v2 IEEE 1588 v2
master clock master clock
(optional)
IEC 61850
HSR
SMV traffic
Backup 1588
master clock
Figure 11: Example network topology with process bus, redundancy and IEEE 1588
v2 time synchronization
The process bus option is available for all 620 series protection relays equipped
with phase voltage inputs. Another requirement is a communication card with IEEE
1588 v2 support (COM0031...COM0034 or COM0037). See the IEC 61850 engineering
guide for detailed system requirements and configuration details.
34 REM620
Application Manual
1MRS757655 E REM620 default configurations
1 Function uses calculated value when the high-impedance based restricted earth-fault protection
is used
2 Function uses calculated value when the rotor earth-fault protection is used
REM620 35
Application Manual
REM620 default configurations 1MRS757655 E
36 REM620
Application Manual
1MRS757655 E REM620 default configurations
REM620 37
Application Manual
REM620 default configurations 1MRS757655 E
38 REM620
Application Manual
1MRS757655 E REM620 default configurations
Figure 12: Drawing symbol used in the manual and the default connection of the LED
function blocks in the configurations
REM620 39
Application Manual
REM620 default configurations 1MRS757655 E
N
n Positive
Current
a Direction
da dn
REM620
Uab X100
X120
2) + 1
1 1/5A Uaux
P1 IL1_N -
2
S1
2 N
S2
3 1/5A 3
P2 IL2_N IRF
4 N
4
5 1/5A
IL3_N 5
6 N
7 1/5A PO1
IL1
8 N 6
9 1/5A 7
IL2
P1 S1 10 N PO2
11 1/5A
S2 IL3 8
P2 12 N
9
13 1/5A
10
Io
14 N SO1
11
12
M X130
13
SO2
3~ 1
2
BI 1
14
16
3 PO3
BI 2
4
P2
S2 17
5 15
S1 BI 3 19
P1
6 TCS1 18
20
7 22
BI 4
8 PO4
60 - 21
9 210V
U_SYN 23
10 N
TCS2
60 - 24
11 210V
U1
12 N
60 -
13 210V
U2
14 N
60 -
15 210V
U3
16 N
60 -
17 210V
Uo
18 N
X105
X110
X115 X115
1 14
BI 1
2 SO1
16
3
BI 2 15
4 17
5 SO2
BI 3 19
6
18
20
BI 4 SO3
7
22
8 21
BI 5 23
9
SO4
BI 6 24
10
11
BI 7
12
BI 8
13
X13
1)
Light sensor input 1
X14
1)
Light sensor input 2
X15
1) 1) Order selectable -Optional
Light sensor input 3
2) The IED features an automatic short-circuit
mechanism in the CT connector when plug-in
unit is detached
40 REM620
Application Manual
1MRS757655 E REM620 default configurations
L1
L2
L3
Positive
Current
Direction
REM620
X100
X130 + 1
Uaux
1 0.2/1A -
2
2 Io
N 3
IRF
X131 4
5
I 4
IL1
5 PO1
7
U1 6
8 7
X132
PO2
I 4
IL2 8
5 9
7 10
U2
8 SO1
X133 11
12
I 4 13
IL3
5 SO2
7 14
U3
8 16
PO3
17
15
19
P1 S1
TCS1 18
S2
20
P2 22
PO4
21
23
M TCS2 24
3~
X105
X110 X110
1 14
BI 1
2 SO1
16
3
BI 2 15
4 17
5 SO2
BI 3 19
6
18
20
BI 4 SO3
7
22
8 21
BI 5 23
9
SO4
BI 6 24
10
11
BI 7
12
BI 8
13
X115 X115
1 14
BI 1
2 SO1
16
3
BI 2 15
4 17
5 SO2
BI 3 19
6
18
20
BI 4 SO3
7
22
8 21
BI 5 23
9
SO4
BI 6 24
10
11
BI 7
12
BI 8
13
X13
1)
Light sensor input 1
X14
1)
Light sensor input 2
X15
1)
Light sensor input 3
1) Order selectable -Optional
Figure 14: Connection diagram for the configuration with SIM0002 module
REM620 41
Application Manual
REM620 default configurations 1MRS757655 E
L1
L2
L3
Positive
Current
Direction
REM620
X100
X130 + 1
Uaux
1 0.2/1A -
2
2 Io
N 3
IRF
X131 4
L1/A
5
I 1
IL1
2 PO1
7
U1 6
8 7
X132
L2/B PO2
I 1
IL2 8
2 9
7 10
U2
8 SO1
X133 11
L3/C 12
I 1 13
IL3
2 SO2
7 14
U3
8 16
PO3
17
15
19
P1 S1
TCS1 18
S2
20
P2 22
PO4
21
23
M TCS2 24
3~
X105
X110 X110
1 14
BI 1
2 SO1
16
3
BI 2 15
4 17
5 SO2
BI 3 19
6
18
20
BI 4 SO3
7
22
8 21
BI 5 23
9
SO4
BI 6 24
10
11
BI 7
12
BI 8
13
X115 X115
1 14
BI 1
2 SO1
16
3
BI 2 15
4 17
5 SO2
BI 3 19
6
18
20
BI 4 SO3
7
22
8 21
BI 5 23
9
SO4
BI 6 24
10
11
BI 7
12
BI 8
13
X13
1)
Light sensor input 1
X14
1)
Light sensor input 2
X15
1)
Light sensor input 3
1) Order selectable -Optional
Figure 15: Connection diagram for the configuration with SIM0005 module
42 REM620
Application Manual
1MRS757655 E REM620 default configurations
X105/
BIO0005 module
X110 X105/
X110
1
BI 1 14
2
SO1
3 16
BI 2 15
4
17
5 SO2
BI 3
6 19
18
20
BI 4
7 SO3
22
8
BI 5 21
9 23
SO4
BI 6 24
10
11
BI 7
12
BI 8
13
BIO0007 module
X105
X105
1
BI 1
HSO1
2
BI 2 15
16
3 HSO2
BI 3
19
4 20
BI 4
5
HSO3
6
BI 5 23
24
7
BI 6
8
BI 7
9
BI 8
10
Figure 17: Optional BIO0007 module for fast outputs (slot X105)
REM620 43
Application Manual
REM620 default configurations 1MRS757655 E
RTD003 module
X105/
X110
5 mA
mA 1
6
7 mA
mA 2
8
9
RTD 1
10
11
RTD 2
12
13
RTD 3
14
15 Common RTD GND
16 Common RTD GND
17
RTD 4
18
19
RTD 5
20
21
RTD 6
22
44 REM620
Application Manual
1MRS757655 E REM620 default configurations
REM620 45
Application Manual
REM620 default configurations 1MRS757655 E
3.5.1 Applications
The default configuration is designed for differential protection and mainly
intended for comprehensive protection and control functionality of circuit breaker
controlled asynchronous motors. With minor modifications this default
configuration can be applied also for contactor controlled motors.
The IED with a default configuration is delivered from the factory with default
settings and parameters. The end-user flexibility for incoming, outgoing and
internal signal designation within the IED enables this configuration to be further
adapted to different primary circuit layouts and the related functionality needs by
modifying the internal functionality using PCM600.
The default configuration can also be used with double bus
arrangements. If the voltages are measured from the bus side in a double
busbar configuration, an external voltage switch is needed to bring the
right voltage set to the IED.
The configuration can also be modified to be used with several different
start connection schemes by utilizing the available controllable blocks.
46 REM620
Application Manual
1MRS757655 E REM620 default configurations
3.5.2 Functions
REM620
Uo
UL1UL2UL3
U12 0. 0 kV
P 0.00 kW
- High-Speed Output module (optional)
- Local/Remote push-button on LHMI
Q 0.00 kVAr
IL2 0 A
- Self-supervision
3I 2× 2× - Time synchronization: IEEE-1588,
I ESC Clear
3Ib Interfaces:
2× 2× Ethernet: TX (RJ-45), FX (LC)
OPTS TCS Serial: Serial glass fiber (ST),
3× 2×
OPTM TCM RS-485, RS-232/485
P>/Q> Q>→, 3U<
Redundant protocols:
32R/32O 32Q, 27
HSR
PRP
2× 2× 2× Io RSTP
P< X< 3I(U)> 3I>→
32U 40 51V 67-1
2×
3I>>→ CVPSOF
CONTROL AND INDICATION 1) MEASUREMENT
67-2 SOFT/21/50
U12 - I, U, Io, Uo, P, Q, E, pf, f
Object Ctrl 2) Ind 3)
- Limit value supervision
CB 3 - - Load profile
- Power Quality functions
DC 4 4 - RTD/mA measurements
ES - Symmetrical components
Io>>> Io> Io>> 3 3
50N/51N 51N-1 51N-2 1)
Check availability of binary inputs/outputs
from technical documentation Analog interface types 1)
2)
Control and indication function for
Io primary object Current transformer 7
3)
Status indication function for
Voltage transformer 5
primary object
UL1UL2UL3
Io>→ Io>>→ 1)
Conventional transformer inputs
67N-1 67N-2
Uo SYNC ESTART
25 ESTART
U12
4× 3× 2× 2×
3U< Uo> U2> U1<
27 59G 47O- 47U+
U12
M REMARKS
12×RTD
4×mA 18×
MAP Io>R Optional 3× No. of Calculated OR Alternative
3Ib MAP 64R function instances value function to be
Io/Uo
defined when
ordering
Figure 19: Functionality overview of default configuration with conventional instrument transformer
inputs
REM620 47
Application Manual
REM620 default configurations 1MRS757655 E
48 REM620
Application Manual
1MRS757655 E REM620 default configurations
REM620 49
Application Manual
REM620 default configurations 1MRS757655 E
50 REM620
Application Manual
1MRS757655 E REM620 default configurations
REM620 51
Application Manual
REM620 default configurations 1MRS757655 E
Additionally, all the digital inputs that are connected by default are also enabled
with the setting. Default triggering settings are selected depending on the
connected input signal type. Typically all protection START signals are selected to
trigger the disturbance recorded by default.
52 REM620
Application Manual
1MRS757655 E REM620 default configurations
X120 X130
1 1/5A 60 -
9 210V
IL1_N U_SYN
2 N 10 N
3 1/5A 60 -
11 210V
IL2_N 3IB U1
4 N 12 N
5 1/5A 60 -
13 210V
IL3_N U2 3U
6 N 14 N
60 -
7 1/5A 15 210V
IL1 U3
16 N
8 N
9 1/5A 60 -
17 210V
IL2 3I Uo
10 N 18 N
11 1/5A
IL3
12 N
13 1/5A
Io
14 N
The physical analog channels of all functions which require current or voltage inputs
in this configuration are listed in Table 18. Meaning of the symbols is explained in
Table 17.
REM620 53
Application Manual
REM620 default configurations 1MRS757655 E
Symbol Description
x The analog channel is assigned to the function by default.
C The function can be set to use residual voltage or current calculated based on
the three-phase input. Only applicable for functions which need residual volt-
age or current as input.
D The analog channel is dedicated to the function. When the corresponding func-
tion is taken into use, other functions cannot use this analog channel any
more. The other functions can be set to use calculated values instead of physi-
cal measured value or select an alternative operation mode not requiring this
physical measured channel. However, some functions might not have such op-
eration modes and might become unusable in the configuration. All functions
marked to use the same HW channel under the same column should be
checked to make sure the functions work.
54 REM620
Application Manual
1MRS757655 E REM620 default configurations
REM620 55
Application Manual
REM620 default configurations 1MRS757655 E
56 REM620
Application Manual
1MRS757655 E REM620 default configurations
connected) VTs from the system. When star connected VT is available in the system,
the VT inputs in the IED are star connected and configuration setting is suitably
changed. In addition, the signal marked with Uo represents the measured residual
voltage via open-delta connected VTs.
The signal marked Usyn is measured from the VT on the terminal side of the motor.
This signal is used to check synchronizing.
The relay offers six different settings groups which can be set based on individual
needs. Each group can be activated or deactivated using the setting group settings
available in the relay.
There are 16 programmable push buttons offered in the front panel of the unit. The
relay offers six different settings groups which can be set based on individual
needs.
Each group can then, be activated or deactivated by using a programmable button.
In addition to this, the programmable button can be also used for emergency start
and emergency stop, manual trigger of disturbance recorder, master trip lockout
reset, circuit breaker control interlocking bypass, restart inhibit, and so on.
PROTECTION
SG_LOGIC_SEL
SG_1_ACT
BI_SG_2 SG_2_ACT
BI_SG_3 SG_3_ACT
BI_SG_4 SG_4_ACT
BI_SG_5 SG_5_ACT
BI_SG_6 SG_6_ACT
BEH_BLK
BEH_TST
SRGAPC1_S1
AND
SRGAPC1_S2
AND
FKEYGGIO1 SPCGAPC1
SRGAPC1_S3
R_TRIG
BLOCK AND
L1 K1 IN1 O1 SRGAPC1_S4 R_TRIG_Q
OR CLK Q
L2 K2 IN2 O2 AND
L3 K3 IN3 O3 SRGAPC1_S5
L4 K4 IN4 O4 AND
L5 K5 IN5 O5 SRGAPC1_S6
L6 K6 IN6 O6 AND
L7 K7 IN7 O7
L8 K8 IN8 O8 SPCGAPC1_EMERGENCY_START
L9 K9 IN9 O9 SPCGAPC1_DR_MANUAL_TRIGGER
L10 K10 IN10 O10 SPCGAPC1_LOCKOUT_RESET
L11 K11 IN11 O11 SPCGAPC1_ITL_BYPASS_ENABLE
L12 K12 IN12 O12 SPCGAPC1_RESTART_INHIBIT
L13 K13 IN13 O13
L14 K14 IN14 O14
L15 K15 IN15 O15
L16 K16 IN16 O16
SRGAPC1
S1 Q1 BI_SG_2
AND R1 Q2 BI_SG_3
SPCGAPC1_O2
S2 Q3 BI_SG_4
AND R2 Q4 BI_SG_5
SPCGAPC1_O3
S3 Q5 BI_SG_6
R_TRIG_Q
AND R3 Q6
SPCGAPC1_O4
S4 Q7
AND R4 Q8
SPCGAPC1_O5
S5
AND R5
SPCGAPC1_O6
S6
R6
S7
R7
S8
R8
REM620 57
Application Manual
REM620 default configurations 1MRS757655 E
TPGAPC3
IN2 OUT2
MPDIF1
3dl>M/G (1)
87M/G (1)
3I OPERATE LED 1
3IB OPR_LS
BLOCK OPR_HS
LED 2
BLK_OPR_LS INT_BLKD
BLK_OPR_HS
The motor differential protection MPDIF1 is used to detect motor internal winding
faults. The OPERATE output is connected to the Master Trip and also connected to
signal output X110-SO4 via generic timer TPGAPC3 .The OPR_LS output is connected
to alarm LED 1 and the OPR_HS output is connected to alarm LED 2.
58 REM620
Application Manual
1MRS757655 E REM620 default configurations
PHLPTOC1
3I>(1)
51P-1(1)
3I OPERATE
BLOCK START
ENA_MULT
PHHPTOC2
PHIPTOC1
3I>>>(1) PHHPTOC1
50P/51P(1) 3I>>(1)
51P-2(1)
DPHLPDOC1
3I>→(1)
67-1(1)
OR LED 4
3U OPERATE
3I
START
NON_DR
ENA_MULT
DPHHPDOC2
DPHHPDOC1
3I>> (1)
67-2(1)
3U OPERATE
3I
START
NON_DR
ENA_MULT
JAMPTOC1
Ist>(1)
51LR(1)
3I OPERATE
STTPMSU1_MOT_START BLOCK
Seven overcurrent stages in total are offered for overcurrent and short-circuit
protection. Three stages are for directional functionality DPHxPDOC, while the
others are only for non-directional overcurrent protection PHxPTOC.
PHLPTOC1 can be used for overcurrent protection, and PHIPTOC1 for the short-
circuit protection. The operation of PHIPTOC1 is not blocked as default by any
functionality and it should be set over the motor start current level to avoid
unnecessary operation.
The motor load jam protection JAMPTOC1 is used for protecting the motor in stall
or mechanical jam situations during the running state. The motor jam protection
function JAMPTOC1 is blocked by the motor start-up protection function.
The OPERATE outputs are connected to the Master Trip. The OPERATE outputs are
also connected to the alarm LED 4, except for PHIPTOC1, which is connected to the
alarm LED 3. LED 3 is used for short-circuit protection alarm indication; LED 4 is
used for combined protection alarm indication, including overcurrent protection,
earth-fault protection, phase unbalance protection, voltage protection, motor jam
protection, loss of load protection and frequency protection.
REM620 59
Application Manual
REM620 default configurations 1MRS757655 E
EARTH-FAULT PROTECTION
EFLPTOC1
Io>(1)
51N-1(1)
Io OPERATE
BLOCK START
ENA_MULT
OR LED 4
EFHPTOC1 DEFLPDEF1
Io>>(1) Io>→ (1)
51N-2(1) 67N-1(1)
Io OPERATE
Io OPERATE Uo START
DEFHPDEF1
EFIPTOC1 Io>>→ (1)
Io>>>(1) 67N-2(1)
50N/51N(1) Io OPERATE
Uo START
BLOCK
Io OPERATE
ENA_MULT
BLOCK START
RCA_CTL
ENA_MULT
PHIPTOC1_START
60 REM620
Application Manual
1MRS757655 E REM620 default configurations
PHPTOV3
PHPTOV2
PHPTOV1
3U>(1)
59(1)
3U OPERATE
BLOCK START
PHPTUV3
OR LED 4
PHPTUV2
PHPTUV1
3U<(1)
27(1)
3U OPERATE
STTPMSU1_MOT_START
OR BLOCK START
SEQSPVC1_FUSEF_U
REM620 61
Application Manual
REM620 default configurations 1MRS757655 E
PSPTUV2
PSPTUV1
U1<(1)
47U+(1)
3U OPERATE
BLOCK START
OR LED 4
NSPTOV2
NSPTOV1
U2>(1)
47O-(1)
3U OPERATE
STTPMSU1_MOT_START
OR BLOCK START
X105-BI1
Rotation Direction
62 REM620
Application Manual
1MRS757655 E REM620 default configurations
ROVPTOV3
ROVPTOV2
ROVPTOV1
Uo>(1)
59G(1)
Uo OPERATE LED 4
BLOCK START
PHAPTOV1
U_A> (1)
59_A (1)
U_A_AB OPERATE
BLOCK START
PHAPTUV1
U_A< (1)
27_A (1)
U_A_AB OPERATE
BLOCK START
REM620 63
Application Manual
REM620 default configurations 1MRS757655 E
LED 10
ESMGAPC1_ST_EMERG_ENA
LED 5
ESMGAPC1 MPTTR1
ESTART(1) 3Ith>M(1)
ESTART(1) 49M(1) TPGAPC2
3I
3I ST_EMERG_ENA BLOCK OPERATE IN1 OUT1
BLOCK START_EMERG ALARM IN2 OUT2 X115-SO3
X110-RTD6
MVGAPC1 CCBRBRF1_EXE_OP
X105-BI3 I1 Q1
RESTART INHIBIT
External Restart Inhibit SPCGAPC1_O12_RESTART_INHIBIT
OR LED 6
TPSGAPC1 TRPPTRC1_TRIP
STTPMSU1_LOCK_START
TRPPTRC1_TRIP MNSPTOC1_BLK_RESTART
OR IN1 OUT1
CBXCBR1_EXE_OP MNSPTOC2_BLK_RESTART
IN2 OUT2
The emergency start function ESMGAPC1 allows motor start-ups, although the
calculated thermal level or cumulative start-up time counter is blocking the restart.
The emergency start is enabled for ten minutes after the selected binary input
X105- BI2 is energized. On the rising edge of the emergency start signal, various
events occur.
• The calculated thermal level in MPTTR1 is set slightly below the restart inhibit
level to allow at least one motor start-up
• The value of the cumulative start-up time counter STTPMSU1 is set slightly below
the set restart inhibit value to allow at least one motor start-up
• Set start value of the MAPGAPC1 function is increased (or decreased) depending
on the Start value Add setting
• Alarm LED 10 is activated
A new emergency start cannot be made until the emergency start signal has been
reset and the emergency start time of ten minutes has expired.
The thermal overload protection function MPTTR1 detects short- and long term
overloads under varying load conditions. When the emergency start request is
issued for the emergency start function, it activates the corresponding input of the
thermal overload function. When the thermal overload function has issued a restart
blocking, which inhibits the closing of the breaker when the machine is overloaded,
the emergency start request removes this blocking and enables the restarting of
the motor. The OPERATE output of MPTTR1 is connected to alarm LED 5, which is
used for thermal overload protection alarm indication. The ALARM output of MPTTR1
is connected to output X115-SO3 via generic timer TPGAPC2.
The restart inhibit is activated for a set period when a circuit breaker is opened.
This is called remanence voltage protection, where the motor has damping
remanence voltage after circuit breaker opening. Reclosing after a too short period
64 REM620
Application Manual
1MRS757655 E REM620 default configurations
of time can lead to stress for the machine and other apparatuses. The remanence
voltage protection waiting time can be set to a timer function TPSGAPC1. The alarm
LED 6 is used for restart inhibit alarm indication.
The restart inhibit is also activated when one of the conditions is met.
• An active trip command
• Motor start-up supervision has issued lockout
• Motor unbalance function has issued restart blocking
• An external restart inhibit is activated by one push button through
SPCGAPC1_O12 or by a binary input X105-BI3 via MVGAPC1
STTPMSU1
IS²t >,n>(1)
49,66,48,51LR(1)
X115-BI1
3I OPR_IIT STTPMSU1_OPR_IIT
CB Closed Position BLOCK OPR_STALL STTPMSU1_OPR_STALL
BLK_LK_ST MOT_START STTPMSU1_MOT_START
X115-BI7 LOCK_START STTPMSU1_LOCK_START
CB_CLOSED
Speed Switch STALL_IND
ESMGAPC1_ST_EMERG_ENA ST_EMERG_ENA TPGAPC2
IN2 OUT2
MDSOPT1
OPTS(1)
OPTM(1)
X130-BI1
DC1 Closed Position AND POS_ACTIVE ALARM LED 9
With the motor start-up supervision function STTPMSU1, the starting of the motor
is supervised by monitoring three-phase currents or the status of the energizing
circuit breaker of the motor.
When the emergency start request is activated by ESMGAPC1 and STTPMSU1 is in
lockout state, the lockout LOCK_START is deactivated and emergency start is
available. The MOT_START output of STTPMSU1 is connected to output X115-SO1 via
generic timer TPGAPC2.
The motor running time counter MDSOPT1 provides history data since last
commissioning. The counter counts the total number of motor running hours and is
incremented when the energizing circuit breaker is closed. The alarm of the runtime
counter is connected to alarm LED 9. LED 9 is used for general supervision of trip
circuit, current measurement circuit, voltage measurement circuit and motor
operation time.
REM620 65
Application Manual
REM620 default configurations 1MRS757655 E
MNSPTOC2
MNSPTOC1
I2>M(1)
46M(1)
I2 OPERATE
BLOCK ALARM
BLK_RESTART
PREVPTOC1
I2>>(1)
46R(1)
LED 4
I2 OPERATE OR
CCSPVC1_FAIL
OR BLOCK START
X105-BI1
Rotation Direction
LOFLPTUC2
LOFLPTUC1
3I<(1)
37(1)
3I OPERATE
BLOCK START
66 REM620
Application Manual
1MRS757655 E REM620 default configurations
FREQUENCY PROTECTION
FRPFRQ6
FRPFRQ5
FRPFRQ4
FRPFRQ3
FRPFRQ2
FRPFRQ1
f>/f<,df/dt(1)
81(1)
3U OPERATE LED 4
BLOCK OPR_UFRQ
OPR_OFRQ
OPR_FRG
START
ST_UFRQ
ST_OFRQ
ST_FRG
REM620 67
Application Manual
REM620 default configurations 1MRS757655 E
MPDIF1_OPERATE
PHLPTOC1_OPERATE
PHHPTOC1/2_OPERATE
PHIPTOC1_OPERATE CCBRBRF1
DPHLPDOC1_OPERATE 3I>/Io>BF(1)
DPHHPDOC1/2_OPERATE
51BF/51NBF(1)
EFLPTOC1_OPERATE 3I CB_FAULT_AL
DEFHPDEF1_OPERATE CB_FAULT
PREVPTOC1_OPERATE
JAMPTOC1_OPERATE
STTPMSU1_OPR_IIT
STTPMSU1_OPR_STALL
ARCSARC1/2/3_OPERATE
X115-BI1
CB Closed Position
The breaker failure protection CCBRBRF1 is initiated via the START input by a
number of different protection stages in the relay. The breaker failure protection
function offers different operating modes associated with the circuit breaker
position and the measured phase and residual currents.
The breaker failure protection has two operating outputs: TRRET and TRBU. The
TRRET output is used for retripping its own breaker through the Master Trip 1. The
TRBU output is used to give a backup trip to the breaker feeding upstream. For this
purpose, the TRBU output signal is connected to power output X100-PO2 and alarm
LED 7. LED 7 is used for backup TRBU operate indication.
68 REM620
Application Manual
1MRS757655 E REM620 default configurations
X110-RTD1 MAX3
IN1 OUT
IN2
MAPGAPC1
X110-RTD2
MAP(1)
IN3
MAP(1)
AI_VALUE OPERATE
X110-RTD3
ENA_ADD START
BLOCK
X110-RTD4
X110-RTD5
MAPGAPC2
MAP(2)
MAP(2)
X110-RTD6 MOTOR_AMBIENT_TEMPERATURE
LED 4
AI_VALUE OPERATE OR
ENA_ADD START
BLOCK
MAPGAPC3
MAP(3)
MAP(3)
AI_VALUE OPERATE
ENA_ADD START
BLOCK
REM620 69
Application Manual
REM620 default configurations 1MRS757655 E
ARC PROTECTION
ARCSARC3
ARCSARC2
ARCSARC1
ARC(1)
50L/50NL(1)
3I OPERATE LED 11
Io FLT_ARC_DET
BLOCK
REM_FLT_ARC
OPR_MODE
70 REM620
Application Manual
1MRS757655 E REM620 default configurations
DISTURBANCE RECORDER
RDRE1
PHLPTOC1_OPERATE
PHHPTOC1/2_OPERATE
PHIPTOC1_OPERATE OR PHLPTOC1_START C1 TRIGGERED
DPHLPDOC1_OPERATE PHHPTOC1_START C2
DPHHPDOC1/2_OPERATE PHHPTOC2_START C3
PHIPTOC1_START C4
EFLPTOC1_OPERATE DPHLPDOC1_START C5
EFHPTOC1_OPERATE DPHHPDOC1_START C6
EFIPTOC1_OPERATE OR DPHHPDOC2_START C7
DEFLPDEF1_OPERATE C8
DEFHPDEF1_OPERATE EFLPTOC1_START C9
EFHPTOC1_START C10
EFIPTOC1_START C11
DEFLPDEF1_START C12
DEFHPDEF1_START C13
C14
ROVPTOV1/2/3_START C15
ROVPTOV1/2/3_OPERATE C16
PHPTUV1/2/3_START C17
PHPTOV1/2/3_START C18
OR
PSPTUV1/2_START FRPFRQ1/2/3/4/5/6_START C19
NSPTOV1/2_START FRPFRQ1/2/3/4/5/6_OPERATE C20
MNSPTOC1_START C21
MNSPTOC2_START C22
PHPTUV1/2/3_OPERATE MNSPTOC1/2_BLK_RESTART C23
PHPTO V1/2/3_OPERATE MNSPTOC1/2_OPERATE C24
OR
PSPTUV1/2_OPERATE LOFLPTUC1_START C25
NSPTOV1/2_OPERATE LOFLPTUC1_START C26
LOFLPTUC1/2_OPERATE C27
MPTTR1_ALARM C28
MPTTR1_BLK_RESTART C29
MPTTR1_OPERATE C30
PREVPTOC1_START C31
PREVPTOC1_OPERATE C32
ESMGAPC1_ST_EMERG_ENA C33
MPDIF1_OPERATE C34
MPDIF1_OPR_LS C35
MPDIF1_OPR_HS C36
C37
JAMPTOC1_OPERATE C38
STTPMSU1_MOT_START C39
STTPMSU1_LOCK_START C40
STTPMSU1_OPR_IIT C41
STTPMSU1_OPR_STALL C42
ARCSARC1/23_ARC_FLT_DET C43
ARCSARC1_OPERATE C44
ARCSARC2_OPERATE C45
ARCSARC3_OPERATE C46
SEQSPVC1_FUSEF_3PH C47
SEQSPVC1_FUSEF_U C48
CCSPVC1_FAIL C49
CCBRBRF1_TRRET C50
CCBRBRF1_TRBU C51
X115_BI1_CB_CLOSED C52
X115_BI2_CB_OPEN C53
X105_BI2_EMERGENCY_START_ENABLE C54
X105_BI8_BUS_VT_MCB_OPEN C55
X105_BI7_LINE_VT_MCB_OPEN C56
X105_BI3_EXTERNAL_RESTART_INHIBIT C57
X115_BI7_SPEED_SWITCH C58
MDSOPT1_ALARM C59
MAPGAPC1_START C60
MAPGAPC2_START C61
MAPGAPC3_START C62
MAPGAPC1/2/3_OPERATE C63
SPCGAPC1_O9_DR_MANUAL_TRIGGER C64
All START and OPERATE outputs from the protection stages are routed to trigger the
disturbance recorder or, alternatively, only to be recorded by the disturbance
recorder, depending on the parameter settings. Additionally, some selected signals
from different functions and eight binary inputs totally from X110 and X115 are also
connected.
The manual trigger signal from push button is used to trigger disturbance recorder
manually as needed.
The disturbance recorder main application sheet contains the
disturbance recorder function block and the connections to variables.
REM620 71
Application Manual
REM620 default configurations 1MRS757655 E
TCSSCBR1
TCS(1)
TCM(1)
TRPPTRC1_TRIP
OR BLOCK ALARM
X115-BI2
CB Open Position
CCSPVC1
MCS 3I(1)
CSM 3I(1)
3I FAIL
Io ALARM
BLOCK
OR LED 9
SEQSPVC1
FUSEF(1)
60(1)
3I FUSEF_3PH
3U FUSEF_U
BLOCK
X115-BI1 CB_CLOSED
CB Closed Position DISCON_OPEN
X115-BI8 MINCB_OPEN
One trip circuit supervision function is in used by default, TCSSCBR1 for power
output X100-PO3. Both functions are blocked by the Master Trip TRPPTRC1 and the
circuit breaker open signal. The ALARM output indication is connected to the LED 9.
It is assumed that there is no external resistor in the circuit breaker
tripping coil circuit connected in parallel with the circuit breaker normally
open auxiliary contact.
72 REM620
Application Manual
1MRS757655 E REM620 default configurations
SECRSYN1
X115-BI8
SYNC(1)
25(1)
Bus MCB Open Position
3U SYNC_INPRO
The main purpose of the synchronism and energizing check SECRSYN1 is to provide
control over the closing of the circuit breakers in power networks and prevent the
closing if the conditions for synchronism are not fulfilled. The energizing function
allows closing, for example, when one side of the breaker is dead.
SECRSYN1 measures the bus and motor terminal voltages and compares them to
set conditions. When all the measured quantities are within set limits, the SYNC_OK
output is activated for allowing closing or closing the circuit breaker. The SYNC_OK
output signal is connected to the ENA_CLOSE input of CBXCBR1 through control.
To ensure the validity of the measured voltages on both sides, Bus MCB Open
Position X115-BI8, Line MCB Open Position X105-BI7 and FUSEF_U from
SEQSPVC1 are connected to block SECRSYN1.
REM620 73
Application Manual
REM620 default configurations 1MRS757655 E
MASTER TRIP
MPDIF1_OPERATE
PHLPTOC1_OPERATE
PHHPTOC1/2_OPERATE
PHIPTOC1_OPERATE
DPHLPDOC1_OPERATE
DPHHPDOC1/2_OPERATE
EFLPTOC1_OPERATE
EFHPTOC1_OPERATE
EFIPTOC1_OPERATE
DEFLPDEF1_OPERATE X115-SO2
TRPPTRC1
DEFHPDEF1_OPERATE
ROVPTOV1/2/3_OPERATE Master Trip(1)
PHPTOV1/2/3_OPERATE 94/86(1)
PHPTUV1/2/3_OPERATE
OR OPERATE
PSPTUV1/2_OPERATE TRIP
NSPTO V1/2_OPERATE
BLOCK CL_LKOUT
FRPFRQ1/2/3/4/5/6_OPERATE
MNSPTOC1/2_OPERATE RST_LKOUT
LOFLPTUC1/2_OPERATE
STTPMSU1_OPR_IIT
STTPMSU1_OPR_STALL
JAMPTOC1_OPERATE
MPTTR1_OPERATE OR X100-PO3
PREVPTOC1_OPERATE CBXCBR1_EXE_OP
MVGAPC1 ARCSARC1/2/3_OPERATE
CCBRBRF1_TRRET
X105-BI4 I4 Q4
MAPGAPC1/2/3_OPERATE
External Trip
SPCGAPC1_O10_LO CKOUT_RESET
The operating signals from the protections and an external trip X105-BI4 via
MVGAPC1 are connected to signal output X115-SO2 and the trip output contact
X100-PO3 via the corresponding Master Trip TRPPTRC1. The opening control
commands to the circuit breaker from the local or remote CBXCBR1_EXE_OP are
connected directly to the output X100-PO3.
TRPPTRC1 provides the lockout/latching function, event generation and the trip
signal duration setting. If the lockout operation mode is selected, SPCGAPC1_O10 is
connected to the RST_LKOUT input of the Master Trip to enable external reset with a
push button.
DCSXSWI1
DCS(1)
X130-BI2
DCS(1)
DC1 Open Position
POSOPEN OPENPOS
POSCLOSE CLOSEPOS
X130-BI1
OKPOS
DC1 Closed Position AND
X115-BI2
DCS(2)
X130-BI4
DCS(2) AND
X115-BI1
DC2 Open Position CB Closed Position
CBXCBR1
PO SOPEN OPENPOS
PO SCLOSE CLOSEPOS
X130-BI3
OKPOS
OR I↔O CB(1)
DC2 Closed Position I↔O CB(1) CB_OPEN_COMMAND
TRPPTRC1_TRIP POSOPEN SELECTED
SECRSYN1_SYNC_OK AND POSCLOSE EXE_OP CBXCBR1_EXE_OP
ENA_OPEN EXE_CL CB_CLOSE_COMMAND
ENA_CLOSE OPENPOS
ESSXSWI1 BLK_OPEN CLOSEPOS
ESS(1) RESTART INHIBIT BLK_CLOSE OKPOS
X100-PO4
X115-BI6
ESS(1) AU_OPEN OPEN_ENAD
ES Open Position
POSOPEN OPENPOS AU_CLOSE CLOSE_ENAD X100-PO1
X115-BI5 POSCLOSE CLOSEPOS TRIP
OKPOS SYNC_OK
ES Closed Position
SPCGAPC1_O11_ITL_BYPASS_ENABLE SYNC_ITL_BYP
X115-BI4
SSCBR1
CBCM(1)
CB Spring Charged
52CM(1)
X115-BI3 TRV_T_OP_ALM
3I
Gas Pressure Alarm BLOCK TRV_T_CL_ALM
POSOPEN SPR_CHR_ALM
POSCLOSE OPR_ALM
CB_OPEN_COMMAND OPEN_CB_EXE
OPR_LO OR LED 8
IPOW_ALM
CB_CLOSE_COMMAND CLOSE_CB_EXE IPOW_LO
PRES_ALM_IN CB_LIFE_ALM
MVGAPC1 PRES_LO_IN
SPR_CHR_ST
MON_ALM
PRES_ALM
X105-BI6
SPR_CHR PRES_LO
Emergency Stop RST_IPOW OPENPOS
I2 Q2 RST_CB_WEAR INVALIDPOS
RST_TRV_T CLOSEPOS
X105-BI5 I3 Q3 RST_SPR_T
OR
Emergency Start
SPCGAPC1_O8_EMERGENCY_START
74 REM620
Application Manual
1MRS757655 E REM620 default configurations
There are two types of disconnector and earthing switch blocks available.
DCSXSWI1...4 and ESSXSWI1...3 are status-only type, and DCXSWI1...4 and ESXSWI1…
3 are controllable type. By default, the status-only blocks are connected in the
standard configuration logic. If a controllable operation is preferred, the
controllable type of disconnector and earthing switch blocks can be used, instead
of the status-only type. The connection and configuration of the control blocks can
be made using PCM600.
The binary inputs 1 and 2 of the card X130 are used for busbar disconnector 1
DCSXSWI1 position indication. The binary inputs 3 and 4 of the card X130 are used
for busbar disconnector 2 DCSXSWI2 position indication.
The binary inputs 7 and 8 of card X110 are designed for the position indication of
the earthing switch.
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The
input can be activated by the configuration logic, which is a combination of the
position statuses of related primary equipment (disconnector and earthing switch),
the condition of the circuit breaker (CB gas pressure alarm, CB spring charged), and
the Master Trip logics. The OKPOS output from the DCSXSWI block defines if the
disconnector is definitely either open or close. This, together with non-active trip
signal activates the ENA_CLOSE signal to the circuit breaker control function block.
The open operation is always enabled.
The circuit breaker closing is blocked when the BKL_CLOSE input is activated, which
is connected to motor restart inhibit logic. When all conditions of the circuit breaker
closing are fulfilled, the CLOSE_ENAD output of the CBXCBR1 is activated and PO1
output X100-PO1 is closed.
Emergency stop signal to AU_OPEN input of CBXCBR1 via MVGAPC1 is used to open
the breaker by one push button through SPCGAPC1_O8 or by a binary input X105-
BI5. Emergency start signal to AU_CLOSE input of CBXCBR1 via MVGAPC1 is used to
REM620 75
Application Manual
REM620 default configurations 1MRS757655 E
close the breaker by one push button through SPCGAPC1_O16 or by a binary input
X105-BI6.
One push button can be used through SPCGAPC1_O11, which is connected to
SYNC_ITL_BYP input of the CBXCBR1, to ignore the status of ENA_CLOSE input
However, the BKL_CLOSE input signals are not bypassed with the interlocking
bypass functionality as they always have a higher priority.
If the ENA_CLOSE signal is completely removed from the breaker control
function block CBXCBR1 with PCM600, the function assumes that the
breaker-closing commands are allowed continuously.
The circuit breaker condition monitoring function SSCBR1 supervises the circuit
breaker status based on the binary input information connected and the measured
current levels. SSCBR introduces various supervision methods. The corresponding
supervision alarm signals are routed to LED 8.
PHLPTOC1_START
PHHPTOC1/2_START COMMON ALARM INDICATION 1 & 2
PHIPTOC1_START
DPHLPDOC1_START
DPHHPDOC1/2_START
EFLPTOC1_START
EFHPTOC1_START
EFIPTOC1_START
DEFLPDEF1_START
DEFHPDEF1_START
ROVPTOV1/2/3_START
OR
PHPTOV1/2/3_START
PHPTUV1/2/3_START
PSPTUV1/2_START
NSPTOV1/2_START
FRPFRQ1/2/3/4/5/6_START
MNSPTOC1/2_START
LOFLPTUC1/2_START
STTPMSU1_MOT_STARTUP
STTPMSU1_LOCK_START
PREVPTOC1_START TPGAPC1
MAPGAPC1/2/3_START X100-SO1
IN1 OUT1
IN2 OUT2
MPDIF1_OPERATE
PHLPTOC1_OPERATE
X100-SO2
PHHPTOC1/2_OPERATE
PHIPTOC1_OPERATE
DPHLPDO C1_OPERATE
DPHHPDOC1/2_OPERATE
EFLPTOC1_OPERATE
EFHPTOC1_OPERATE
EFIPTOC1_OPERATE
DEFLPDEF1_OPERATE
DEFHPDEF1_OPERATE
ROVPTOV1/2/3_OPERATE
PHPTOV1/2/3_OPERATE
OR
PHPTUV1/2/3_OPERATE
PSPTUV1/2_OPERATE
NSPTO V1/2_OPERATE
FRPFRQ1/2/3/4/5/6_OPERATE
MNSPTOC1/2_OPERATE
LOFLPTUC1/2_OPERATE
STTPMSU1_OPR_IIT
STTPMSU1_OPR_STALL
JAMPTOC1_OPERATE
PREVPTOC1_OPERATE
ARCSARC1/2/3_OPERATE
MPTTR1_OPERATE
MAPGAPC1/2/3_OPERATE
The signal outputs from the relay are connected to give dedicated information.
• Start of any protection function X100-SO1
• Operate of any protection function X100-SO2
TPGAPC function blocks are used for setting the minimum pulse length for the
outputs. There are four generic timers TPGAPC1…4 available in the relay. The
76 REM620
Application Manual
1MRS757655 E REM620 default configurations
remaining ones, which are not described in the functional diagram, are available in
PCM600 for connection where applicable.
POWER QUALITY
CMHAI1
PQM3I(1)
PQM3I(1)
BLOCK ALARM
VMHAI1
PQM3U(1)
PQM3V(1)
BLOCK ALARM
PHQVVR1
PQMU(1)
PQMV(1)
BLOCK ALARM
OPERATE
START
SWELLST
DIPST
INTST
VSQVUB1
PQUUB(1)
PQVUB(1)
BLOCK MN_UNB_AL
PCT_UNB_AL
OBS_PR_ACT
The power quality function CMHAI1 is used to measure the harmonic contents of
the phase current.
The power quality function VMHAI1 is used to measure the harmonic contents of the
phase voltages.
The power quality function PHQVVR1 is used to measure the voltage variation, that
is, sags and swells.
REM620 77
Application Manual
REM620 default configurations 1MRS757655 E
The voltage unbalance power quality function VSQVUB1 monitors the voltage
unbalance conditions in power networks. It is used to monitor the commitment of
power supply utility of providing a balanced voltage supply on a continuous basis.
VSQVUB provides statistics which can be used to verify the compliance of the
power quality.
The above functions are included in default configuration for demonstration
purposes only, but not configured by default. The functions can be configured as
needed.
MEASUREMENT FUNCTION
LOW_ALARM LOW_ALARM
LO W_WARN LOW_WARN
PEMMXU1
P, E (1)
P, E (1)
RSTACM
CMMXU2 VAMMXU2
3I (2) U_A (2)
3I (2) V_A (2)
BLOCK HIGH_ALARM BLOCK HIGH_ALARM
HIGH_WARN HIGH_WARN
LOW_ALARM LOW_ALARM LDPRLRC1
LOW_WARN LOW_WARN LOADPROF (1)
LOADPROF (1)
RSTMEM MEM_WARN
MEM_ALARM
CSMSQI1 VSMSQI1
I1, I2, I0 (1) U1, U2, U0 (1)
I1, I2, I0 (1) V1, V2, V0 (1)
FLTRFRC1
FAULTREC (1)
CSMSQI2 RESVMMXU1 FAULTREC (1)
I1, I2, I0 (2) Uo (1) BLOCK
I1, I2, I0 (2) Vn (1) CB_CLRD
BLOCK HIGH_ALARM
HIGH_WARN
RESCMMXU1
Io (1)
In (1)
BLOCK HIGH_ALARM
HIGH_WARN
The phase current inputs to the relay are measured by the three-phase current
measurement function CMMXU1/2. The current input is connected to the X120 card
in the back panel. The sequence current measurement CSMSQI1/2 measures the
sequence current and the residual current measurement RESCMMXU1 measures the
residual current.
The three-phase bus side phase voltage inputs to the relay are measured by the
three-phase voltage measurement VMMXU1. The voltage input is connected to the
X130 card in the back panel. The sequence voltage measurement VSMSQI1 measures
the sequence voltage and the residual voltage measurement RESVMMXU1 measures
the residual voltage.
78 REM620
Application Manual
1MRS757655 E REM620 default configurations
The measurements can be seen in the LHMI and they are available under the
measurement option in the menu selection. Based on the settings, function blocks
can generate low alarm or warning and high alarm or warning signals for the
measured current values.
The frequency measurement FMMXU1 of the power system and the three-phase
power and energy measurement PEMMXU1 are available. Load profile record
LDPRLRC1 is included in the measurements sheet. LDPRLRC1 offers the ability to
observe the loading history of the corresponding bay. FLTRFRC1 is used to record
the monitored data during the fault condition. The records enable the analysis of
recent power system events.
HIGH-IMPEDANCE OR FLUX-BALANCE
BASED DIFFERENTIAL PROTECTION FOR
MOTORS
MHZPDIF1
3dIHi>M(1)
87MH(1)
ID_A OPERATE
ID_B START
ID_C
BLOCK
REM620 79
Application Manual
REM620 default configurations 1MRS757655 E
MREFPTOC1
Io>R(1)
64R(1)
Io OPERATE
BLOCK START
ALARM
80 REM620
Application Manual
1MRS757655 E REM620 default configurations
INTERCONNECTION FUNCTIONS
DQPTUV2
DQPTUV1
Q> -> ,3U< (1)
32Q, 27 (1)
3U OPERATE
BLOCK START
LVRTPTUV3
LVRTPTUV2
LVRTPTUV1
U<RT (1)
27RT (1)
3U OPERATE
BLOCK START
REM620 81
Application Manual
REM620 default configurations 1MRS757655 E
DUPPDPR2
DUPPDPR1
P< (1)
32U (1)
3U OPERATE
3I START
DISABLE
BLOCK
DOPPDPR3
DOPPDPR2
DOPPDPR1
P>/Q> (1)
32R/32O (1)
3U OPERATE
3I START
BLOCK
82 REM620
Application Manual
1MRS757655 E REM620 default configurations
THREE-PHASE UNDEREXCITATION
PROTECTION
UEXPDIS2
UEXPDIS1
X< (1)
40 (1)
3U OPERATE
3I START
EXT_LOS_DET
BLOCK
REM620 83
Application Manual
REM620 default configurations 1MRS757655 E
X130
PHAPTOV1
60 -
9 210V
U_SYN Usyn ULTVTR2
10 N
60 - SECRSYN1
11 210V
U1
12 N
60 -
13 210V
U2 3U ULTVTR1 PHPTOV1
14 N
60 -
15 210V
U3
16 N
60 -
17 210V
Uo Uo RESTVTR1 ROVPTOV1
18 N *Measured Uo
The IEC 61850-9-2 LE stream always contains UL1, UL2, UL3 and Uo. When
the three phase voltage channels are received from IEC 61850-9-2 LE, the
setting VT connection in Configuration > Analog inputs > Voltage
(3U,VT) must be “Wye”.
84 REM620
Application Manual
1MRS757655 E REM620 default configurations
X130
PHAPTOV1
60 -
9 210V
U_SYN Usyn ULTVTR2
10 N
60 - SECRSYN1
11 210V
U1
12 N 9-2
13
60 - LE
210V
U2 ULTVTR1 PHPTOV1
14 N
60 -
15 210V
U3
16 N
60 -
17 210V
Uo Uo RESTVTR1 ROVPTOV1
18 N *Measured Uo
Figure 50: ULTVTR1 uses three phase voltages from received IEC 61850-9-2 LE
sample value
X130
PHAPTOV1
60 -
9 210V
U_SYN Usyn ULTVTR2
10 N
60 - SECRSYN1
11 210V
U1
12 N
60 -
13 210V
U2 3U ULTVTR1 PHPTOV1
14 N
60 -
15 210V
U3
16 N
60 - 9-2
17 210V LE
Uo RESTVTR1 ROVPTOV1
18 N *Measured Uo
Figure 52: RESTVTR1 uses residual voltages from received IEC 61850-9-2 LE sample
value
REM620 85
Application Manual
REM620 default configurations 1MRS757655 E
RESTVTR1
Uo ALARM RESTVTR1[1]_ALARM
WARNING RESTVTR1[1]_WARNING
SMVRCV can also be connected to both ULTVTR1 and RESTVTR1. This means that
both the three phase voltages U1, U2, U3 and the residual voltage Uo are replaced by
the received IEC 61850-9-2 LE sample value.
All three signals UL1, UL2 and UL3 must always be connected between
SMVRCV and ULTVTR1.
The IEC 61850-9-2 LE stream always contains UL1, UL2, UL3 and Uo. When
the three phase voltage channels are received from IEC 61850-9-2 LE, the
setting VT connection in Configuration > Analog inputs > Voltage
(3U,VT) must be “Wye”.
X130
PHAPTOV1
60 -
9 210V
U_SYN Usyn ULTVTR2
10 N
60 - SECRSYN1
11 210V
U1
12 N 9-2
13
60 - LE
210V
U2 ULTVTR1 PHPTOV1
14 N
60 -
15 210V
U3
16 N
60 - 9-2
17 210V LE
Uo RESTVTR1 ROVPTOV1
18 N *Measured Uo
Figure 54: Both ULTVTR1 and RESTVTR1 use voltages from received IEC 61850-9-2 LE
sample value
86 REM620
Application Manual
1MRS757655 E REM620 default configurations
from the received IEC 61850-9-2 LE sample value. All functions which have U_SYN
input begin working with the IEC 61850-9-2 LE sample value.
Only UL1 must be connected between SMVRCV and ULTVTR2 in the
Application Configuration tool.
The IEC 61850-9-2 LE stream always contains UL1, UL2, UL3 and Uo. When
U_SYN as a single channel input is received from IEC 61850-9-2 LE, the
setting VT connection in Configuration > Analog inputs > Voltage
(3UB,VT)// must be “UL1”.
X130
9-2 PHAPTOV1
60 - L E
9 210V
U_SYN ULTVTR2
10 N
60 - SECRSYN1
11 210V
U1
12 N
60 -
13 210V
U2 3U ULTVTR1 PHPTOV1
14 N
60 -
15 210V
U3
16 N
60 -
17 210V
Uo Uo RESTVTR1 ROVPTOV1
18 N *Measured Uo
Figure 56: ULTVTR2 uses UL1 voltage from received IEC 61850-9-2 LE sample value
3.6.1 Applications
The default configuration is designed for motor protection with current and voltage
based protection and measurement functions and is mainly intended for
comprehensive protection and control of circuit breaker controlled asynchronous
motors. With minor modifications this default configuration can be applied also for
contactor controlled motors. There is also an option for mA/RTD measurement and
protection.
The IED with a default configuration is delivered from the factory with default
settings and parameters. The end-user flexibility for incoming, outgoing and
internal signal designation within the IED enables this configuration to be further
adapted to different primary circuit layouts and the related functionality needs by
modifying the internal functionality using PCM600.
REM620 87
Application Manual
REM620 default configurations 1MRS757655 E
3.6.2 Functions
U12 0. 0 kV
P 0.00 kW
- High-Speed Output module (optional)
- Local/Remote push-button on LHMI
Q 0.00 kVAr
IL2 0 A
- Self-supervision
2× 2× - Time synchronization: IEEE-1588,
I ESC Clear
Interfaces:
2× 2× Ethernet: TX (RJ-45), FX (LC)
OPTS TCS Serial: Serial glass fiber (ST),
3× 2×
OPTM TCM RS-485, RS-232/485
P>/Q> Q>→, 3U<
Redundant protocols:
32R/32O 32Q, 27
HSR
PRP
2× 2× 2× Io RSTP
P< X< 3I(U)> 3I>→
32U 40 51V 67-1
2×
3I>>→ CVPSOF
CONTROL AND INDICATION 1) MEASUREMENT
67-2 SOFT/21/50
- I, U, Io, Uo, P, Q, E, pf, f
Object Ctrl 2) Ind 3)
- Limit value supervision
CB 3 - - Load profile
- Power Quality functions
DC 4 4 - RTD/mA measurements
ES - Symmetrical components
Io>>> Io> Io>> 3 3
50N/51N 51N-1 51N-2 1)
Check availability of binary inputs/outputs
from technical documentation Analog interface types 1)
2)
Control and indication function for
Io primary object Current sensor 3
3)
Status indication function for
Voltage sensor 3
primary object
Io>→ Io>>→
67N-1 67N-2 Current transformer 1
1)
Combi sensor inputs with conventional
Io input
UL1UL2UL3
ESTART
Uo ESTART
4× 3× 2× 2×
3U< Uo> U2> U1<
27 59G 47O- 47U+
3× 3× 6× OTHER FUNCTIONALITY
3U> U<RT f>/f<,
df/dt 3×
59 27RT
81 Io ARC
50L/50NL
3I
M
12×RTD 18×
4×mA REMARKS
MAP Io>R
MAP 64R
Optional 3× No. of Calculated OR Alternative
function instances value function to be
Io/Uo
defined when
ordering
88 REM620
Application Manual
1MRS757655 E REM620 default configurations
1 SIM0002
2 SIM0005
REM620 89
Application Manual
REM620 default configurations 1MRS757655 E
90 REM620
Application Manual
1MRS757655 E REM620 default configurations
REM620 91
Application Manual
REM620 default configurations 1MRS757655 E
92 REM620
Application Manual
1MRS757655 E REM620 default configurations
Additionally, all the digital inputs that are connected by default are also enabled
with the setting. Default triggering settings are selected depending on the
connected input signal type. Typically all protection START signals are selected to
trigger the disturbance recorded by default.
REM620 93
Application Manual
REM620 default configurations 1MRS757655 E
X130
1 0.2/1A
Io
2 N
X131 X131
4 7
IL1 U1
5 8
X132 X132
4 7
IL2 3I U2 3U
5 8
X133 X133
4 7
IL3 U3
5 8
The physical analog channels of all functions which require current or voltage inputs
in this configuration are listed in Table 31. Meaning of the symbols is explained in
Table 30.
Symbol Description
x The analog channel is assigned to the function by default.
C The function can be set to use residual voltage or current calculated based on
the three-phase input. Only applicable for functions which need residual voltage
or current as input.
D The analog channel is dedicated to the function. When the corresponding func-
tion is taken into use, other functions cannot use this analog channel any more.
The other functions can be set to use calculated values instead of physical meas-
ured value or select an alternative operation mode not requiring this physical
measured channel. However, some functions might not have such operation
modes and might become unusable in the configuration. All functions marked to
use the same HW channel under the same column should be checked to make
sure the functions work.
94 REM620
Application Manual
1MRS757655 E REM620 default configurations
IEC61850 3I 3U Io
Protection
PHLPTOC1 x
PHHPTOC1 x
PHHPTOC2 x
PHIPTOC1 x
DPHLPDOC1 x x
DPHHPDOC1 x x
DPHHPDOC2 x x
PHPVOC1 x x
PHPVOC2 x x
EFLPTOC1 C x
EFHPTOC1 C x
EFIPTOC1 C x
DEFLPDEF1 C x x
DEFHPDEF1 C x x
ROVPTOV1 x
ROVPTOV2 x
ROVPTOV3 x
PHPTUV1 x
PHPTUV2 x
PHPTUV3 x
PHPTUV4 x
PHPTOV1 x
PHPTOV2 x
PHPTOV3 x
PSPTUV1 x
PSPTUV2 x
NSPTOV1 x
NSPTOV2 x
FRPFRQ1 x
FRPFRQ2 x
FRPFRQ3 x
FRPFRQ4 x
FRPFRQ5 x
FRPFRQ6 x
MNSPTOC1 x
MNSPTOC2 x
LOFLPTUC1 x
LOFLPTUC2 x
JAMPTOC1 x
Table continues on the next page
REM620 95
Application Manual
REM620 default configurations 1MRS757655 E
IEC61850 3I 3U Io
STTPMSU1 x
PREVPTOC1 x
MPTTR1 x
CCBRBRF1 x x
CCBRBRF2 x x
CCBRBRF3 x x
ARCSARC1 x
ARCSARC2 x
ARCSARC3 x
CVPSOF1 x x
DQPTUV1 x x
DQPTUV2 x x
DUPPDPR1 x x
DUPPDPR2 x x
DOPPDPR1 x x
DOPPDPR2 x x
DOPPDPR3 x x
UEXPDIS1 x x
UEXPDIS2 x x
LVRTPTUV1 x
LVRTPTUV2 x
LVRTPTUV3 x
MREFPTOC1 D
Control
ESMGAPC1 x
SECRSYN1 9-2 specific func-
tion
Condition monitoring
SSCBR1 x
SSCBR2 x
SSCBR3 x
CCSPVC1 x x
SEQSPVC1 x x
Measurement
CMMXU1 x
CSMSQI1 x
RESCMMXU1 x
VMMXU1 x
VAMMXU2 9-2 specific func-
tion
VSMSQI1 x
PEMMXU1 x x
Table continues on the next page
96 REM620
Application Manual
1MRS757655 E REM620 default configurations
IEC61850 3I 3U Io
FMMXU1 x
Power quality
CMHAI1 x
VMHAI1 x
PHQVVR1 x x
VSQVUB1 x
There are 16 programmable push buttons offered in the front panel of the unit. The
relay offers six different setting groups which can be set based on individual needs.
Each group can then be activated or deactivated by using a programmable button.
In addition to this, the programmable button can also be used, for example, for the
manual trigger of disturbance recorder, enabling/disabling the autoreclosing
function, circuit breaker control interlocking bypass or master trip lockout reset.
REM620 97
Application Manual
REM620 default configurations 1MRS757655 E
PROTECTION
SG_LOGIC_SEL
SG_1_ACT
BI_SG_2 SG_2_ACT
BI_SG_3 SG_3_ACT
BI_SG_4 SG_4_ACT
BI_SG_5 SG_5_ACT
BI_SG_6 SG_6_ACT
BEH_BLK
BEH_TST
SRGAPC1_S1
AND
SRGAPC1_S2
AND
FKEYGGIO1 SPCGAPC1
SRGAPC1_S3
R_TRIG
BLOCK AND
L1 K1 IN1 O1 SRGAPC1_S4 R_TRIG_Q
OR CLK Q
L2 K2 IN2 O2 AND
L3 K3 IN3 O3 SRGAPC1_S5
L4 K4 IN4 O4 AND
L5 K5 IN5 O5 SRGAPC1_S6
L6 K6 IN6 O6 AND
L7 K7 IN7 O7
L8 K8 IN8 O8 SPCGAPC1_EMERGENCY_START
L9 K9 IN9 O9 SPCGAPC1_DR_MANUAL_TRIGGER
L10 K10 IN10 O10 SPCGAPC1_LOCKOUT_RESET
L11 K11 IN11 O11 SPCGAPC1_ITL_BYPASS_ENABLE
L12 K12 IN12 O12 SPCGAPC1_RESTART_INHIBIT
L13 K13 IN13 O13
L14 K14 IN14 O14
L15 K15 IN15 O15
L16 K16 IN16 O16
SRGAPC1
S1 Q1 BI_SG_2
AND R1 Q2 BI_SG_3
SPCGAPC1_O2
S2 Q3 BI_SG_4
AND R2 Q4 BI_SG_5
SPCGAPC1_O3
S3 Q5 BI_SG_6
R_TRIG_Q
AND R3 Q6
SPCGAPC1_O4
S4 Q7
AND R4 Q8
SPCGAPC1_O5
S5
AND R5
SPCGAPC1_O6
S6
R6
S7
R7
S8
R8
98 REM620
Application Manual
1MRS757655 E REM620 default configurations
PHLPTOC1
3I>(1)
51P-1(1)
3I OPERATE
BLOCK START
ENA_MULT
PHHPTOC2
PHIPTOC1
3I>>>(1) PHHPTOC1
50P/51P(1) 3I>>(1)
51P-2(1)
DPHLPDOC1
3I>→(1)
67-1(1)
OR LED 4
3U OPERATE
3I
START
NON_DR
ENA_MULT
DPHHPDOC2
DPHHPDOC1
3I>> (1)
67-2(1)
3U OPERATE
3I
START
NON_DR
ENA_MULT
JAMPTOC1
Ist>(1)
51LR(1)
3I OPERATE
STTPMSU1_MOT_START BLOCK
Seven overcurrent stages in total are offered for overcurrent and short-circuit
protection. Three stages are for directional functionality DPHxPDOC, while the
others are only for non-directional overcurrent protection PHxPTOC.
PHLPTOC1 can be used for overcurrent protection and PHIPTOC1 for the short-
circuit protection. The operation of PHIPTOC1 is not blocked as default by any
functionality and it should be set over the motor start current level to avoid
unnecessary operation.
The motor load jam protection JAMPTOC1 is used for protecting the motor in stall
or mechanical jam situations during the running state. The motor jam protection
function JAMPTOC1 is blocked by the motor start-up protection function.
The OPERATE outputs are connected to the Master Trip. The OPERATE outputs are
also connected to the alarm LED 4, except for PHIPTOC1, which is connected to the
alarm LED 1. LED 1 is used for short-circuit protection alarm indication, and LED 4 is
used for combined protection alarm indication, including overcurrent protection,
REM620 99
Application Manual
REM620 default configurations 1MRS757655 E
EARTH-FAULT PROTECTION
EFLPTOC1
Io>(1)
51N-1(1)
Io OPERATE
BLOCK START
ENA_MULT
OR LED 2
EFHPTOC1 DEFLPDEF1
Io>>(1) Io>→ (1)
51N-2(1) 67N-1(1)
Io OPERATE
Io OPERATE Uo START
DEFHPDEF1
EFIPTOC1 Io>>→ (1)
Io>>>(1) 67N-2(1)
50N/51N(1) Io OPERATE
Uo START
BLOCK
Io OPERATE
ENA_MULT
BLOCK START
RCA_CTL
ENA_MULT
PHIPTOC1_START
100 REM620
Application Manual
1MRS757655 E REM620 default configurations
PHPTOV3
PHPTOV2
PHPTOV1
3U>(1)
59(1)
3U OPERATE TPGAPC3
BLOCK START
IN1 OUT1 X115-SO4
IN2 OUT2
PHPTUV3
OR LED 3
PHPTUV2
PHPTUV1
3U<(1)
27(1)
3U OPERATE
STTPMSU1_MOT_START
OR BLOCK START
SEQSPVC1_FUSEF_U
PSPTUV2
PSPTUV1
U1<(1)
47U+(1)
TPGAPC3
3U OPERATE
IN1 OUT1 X115-SO4
BLOCK START
IN2 OUT2
OR LED 3
NSPTOV2
NSPTOV1
U2>(1)
47O-(1)
3U OPERATE
STTPMSU1_MOT_START
OR BLOCK START
X105-BI1
Rotation Direction
REM620 101
Application Manual
REM620 default configurations 1MRS757655 E
voltage drop. Also the binary input X105-BI1, which indicates the motor rotation
direction, is used to block these functions by default.
The OPERATE outputs of voltage-sequence functions are connected to the Master
Trip and also to alarm LED 3 and also connected to output X115-SO4 via generic
timer TPGAPC3.
ROVPTOV3
ROVPTOV2
ROVPTOV1
Uo>(1)
59G(1)
Uo OPERATE LED 2
BLOCK START
102 REM620
Application Manual
1MRS757655 E REM620 default configurations
LED 10
ESMGAPC1_ST_EMERG_ENA
LED 5
ESMGAPC1 MPTTR1
ESTART(1) 3Ith>M(1)
ESTART(1) 49M(1) TPGAPC2
3I
3I ST_EMERG_ENA BLOCK OPERATE IN1 OUT1
BLOCK START_EMERG ALARM IN2 OUT2 X115-SO3
MVGAPC1 CCBRBRF1_EXE_OP
X105-BI3 I1 Q1
RESTART INHIBIT
External Restart Inhibit SPCGAPC1_O12_RESTART_INHIBIT
OR LED 6
TPSGAPC1 TRPPTRC1_TRIP
STTPMSU1_LOCK_START
TRPPTRC1_TRIP MNSPTOC1_BLK_RESTART
OR IN1 OUT1
CBXCBR1_EXE_OP MNSPTOC2_BLK_RESTART
IN2 OUT2
The emergency start function ESMGAPC1 allows motor start-ups although the
calculated thermal level or cumulative start-up time counter is blocking the restart.
The emergency start is enabled for ten minutes after the selected binary input
X105- BI2 is energized. On the rising edge of the emergency start signal, various
events occur.
• The calculated thermal level in MPTTR1 is set slightly below the restart inhibit
level to allow at least one motor start-up
• The value of the cumulative start-up time counter STTPMSU1 is set slightly below
the set restart inhibit value to allow at least one motor start-up
• Alarm LED 10 is activated
A new emergency start cannot be made until the emergency start signal has been
reset and the emergency start time of ten minutes has expired.
The thermal overload protection function MPTTR1 detects short and long term
overloads under varying load conditions. When the emergency start request is
issued for the emergency start function, it activates the corresponding input of the
thermal overload function. When the thermal overload function has issued a restart
blocking, which inhibits the closing of the breaker when the machine is overloaded,
the emergency start request removes this blocking and enables the restarting of
the motor. The OPERATE output of MPTTR1 is connected to alarm LED 5, which is
used for thermal overload protection alarm indication. The ALARM output of MPTTR1
is connected to output X115-SO3 via generic timer TPGAPC2.
The restart inhibit is activated for a set period when a circuit breaker is opened.
This is called remanence voltage protection where the motor has damping
remanence voltage after circuit breaker opening. Reclosing after a too short period
of time can lead to stress for the machine and other apparatuses. The remanence
voltage protection waiting time can be set to a timer function TPSGAPC1. The alarm
LED 6 is used for restart inhibit alarm indication.
The restart inhibit is also activated when one of the conditions is met.
• An active trip command
• Motor start-up supervision has issued lockout
REM620 103
Application Manual
REM620 default configurations 1MRS757655 E
STTPMSU1
IS²t >,n>(1)
49,66,48,51LR(1)
X115-BI1
3I OPR_IIT STTPMSU1_OPR_IIT
CB Closed Position BLOCK OPR_STALL STTPMSU1_OPR_STALL
BLK_LK_ST MOT_START STTPMSU1_MOT_START
X115-BI7 LOCK_START STTPMSU1_LOCK_START
CB_CLOSED
Speed Switch STALL_IND
ESMGAPC1_ST_EMERG_ENA ST_EMERG_ENA TPGAPC2
IN2 OUT2
MDSOPT1
OPTS(1)
OPTM(1)
X110-BI1
DC1 Closed Position AND POS_ACTIVE ALARM LED 9
With the motor start-up supervision function STTPMSU1 the starting of the motor is
supervised by monitoring three-phase currents or the status of the energizing
circuit breaker of the motor.
When the emergency start request is activated by ESMGAPC1 and STTPMSU1 is in
lockout state, the lockout LOCK_START is deactivated and emergency starting is
available. The MOT_START output of STTPMSU1 is connected to output X115-SO1 via
generic timer TPGAPC2.
The motor running time counter MDSOPT1 provides history data since last
commissioning. The counter counts the total number of motor running hours and is
incremented when the energizing circuit breaker is closed. The alarm of the runtime
counter is connected to alarm LED 9. LED 9 is used for general supervision of trip
circuit, current measurement circuit, voltage measurement circuit and motor
operation time.
104 REM620
Application Manual
1MRS757655 E REM620 default configurations
MNSPTOC2
MNSPTOC1
I2>M(1)
46M(1)
I2 OPERATE
BLOCK ALARM
BLK_RESTART
PREVPTOC1
I2>>(1)
46R(1)
LED 4
I2 OPERATE OR
CCSPVC1_FAIL
OR BLOCK START
X105-BI1
Rotation Direction
LOFLPTUC2
LOFLPTUC1
3I<(1)
37(1)
3I OPERATE
BLOCK START
REM620 105
Application Manual
REM620 default configurations 1MRS757655 E
FREQUENCY PROTECTION
FRPFRQ6
FRPFRQ5
FRPFRQ4
FRPFRQ3
FRPFRQ2
FRPFRQ1
f>/f<,df/dt(1)
81(1)
3U OPERATE LED 3
BLOCK OPR_UFRQ
OPR_OFRQ
OPR_FRG
START
ST_UFRQ
ST_OFRQ
ST_FRG
106 REM620
Application Manual
1MRS757655 E REM620 default configurations
PHLPTOC1_OPERATE
PHHPTOC1/2_OPERATE
PHIPTOC1_OPERATE CCBRBRF1
DPHLPDOC1_OPERATE 3I>/Io>BF(1)
DPHHPDOC1/2_OPERATE
51BF/51NBF(1)
EFLPTOC1_OPERATE 3I CB_FAULT_AL
DEFHPDEF1_OPERATE CB_FAULT
PREVPTOC1_OPERATE
JAMPTOC1_OPERATE
STTPMSU1_OPR_IIT
STTPMSU1_OPR_STALL
ARCSARC1/2/3_OPERATE
X115-BI1
CB Closed Position
The breaker failure protection CCBRBRF1 is initiated via the start input by a number
of different protection stages in the relay. The breaker failure protection function
offers different operating modes associated with the circuit breaker position and
the measured phase and residual currents.
The breaker failure protection has two operating outputs: TRRET and TRBU. The
TRRET output is used for retripping its own breaker through the Master Trip 1. The
TRBU output is used to give a back-up trip to the breaker feeding upstream. For this
purpose, the TRBU output signal is connected to the output X100-PO2 and alarm
LED 7. LED 7 is used for back-up TRBU operate indication.
REM620 107
Application Manual
REM620 default configurations 1MRS757655 E
ARC PROTECTION
ARCSARC3
ARCSARC2
ARCSARC1
ARC(1)
50L/50NL(1)
3I OPERATE LED 11
Io FLT_ARC_DET
BLOCK
REM_FLT_ARC
OPR_MODE
108 REM620
Application Manual
1MRS757655 E REM620 default configurations
DISTURBANCE RECORDER
RDRE1
PHLPTOC1_OPERATE
PHHPTOC1/2_OPERATE
PHIPTOC1_OPERATE OR PHLPTOC1_START C1 TRIGGERED
DPHLPDOC1_OPERATE PHHPTOC1_START C2
DPHHPDOC1/2_OPERATE PHHPTOC2_START C3
PHIPTOC1_START C4
EFLPTOC1_OPERATE DPHLPDOC1_START C5
EFHPTOC1_OPERATE DPHHPDOC1_START C6
EFIPTOC1_OPERATE OR DPHHPDOC2_START C7
DEFLPDEF1_OPERATE C8
DEFHPDEF1_OPERATE EFLPTOC1_START C9
EFHPTOC1_START C10
EFIPTOC1_START C11
DEFLPDEF1_START C12
DEFHPDEF1_START C13
C14
ROVPTOV1/2/3_START C15
ROVPTOV1/2/3_OPERATE C16
PHPTUV1/2/3_START C17
PHPTOV1/2/3_START C18
OR
PSPTUV1/2_START FRPFRQ1/2/3/4/5/6_START C19
NSPTOV1/2_START FRPFRQ1/2/3/4/5/6_OPERATE C20
MNSPTOC1_START C21
MNSPTOC2_START C22
PHPTUV1/2/3_OPERATE MNSPTOC1/2_BLK_RESTART C23
PHPTO V1/2/3_OPERATE MNSPTOC1/2_OPERATE C24
OR
PSPTUV1/2_OPERATE LOFLPTUC1_START C25
NSPTOV1/2_OPERATE LOFLPTUC1_START C26
LOFLPTUC1/2_OPERATE C27
MPTTR1_ALARM C28
MPTTR1_BLK_RESTART C29
MPTTR1_OPERATE C30
PREVPTOC1_START C31
PREVPTOC1_OPERATE C32
ESMGAPC1_ST_EMERG_ENA C33
C34
C35
C36
C37
JAMPTOC1_OPERATE C38
STTPMSU1_MOT_START C39
STTPMSU1_LOCK_START C40
STTPMSU1_OPR_IIT C41
STTPMSU1_OPR_STALL C42
ARCSARC1/23_ARC_FLT_DET C43
ARCSARC1_OPERATE C44
ARCSARC2_OPERATE C45
ARCSARC3_OPERATE C46
SEQSPVC1_FUSEF_3PH C47
SEQSPVC1_FUSEF_U C48
CCSPVC1_FAIL C49
CCBRBRF1_TRRET C50
CCBRBRF1_TRBU C51
X115_BI1_CB_CLOSED C52
X115_BI2_CB_OPEN C53
X105_BI2_EMERGENCY_START_ENABLE C54
C55
C56
X105_BI3_EXTERNAL_RESTART_INHIBIT C57
X115_BI7_SPEED_SWITCH C58
MDSOPT1_ALARM C59
C60
C61
C62
C63
SPCGAPC1_O9_DR_MANUAL_TRIGGER C64
All START and OPERATE outputs from the protection stages are routed to trigger the
disturbance recorder or, alternatively, only to be recorded by the disturbance
recorder depending on the parameter settings. Additionally, some selected signals
from different functions and five binary inputs totally from X105 and X115 are also
connected.
The manual trigger signal from push button is used to trigger disturbance recorder
manually as needed.
REM620 109
Application Manual
REM620 default configurations 1MRS757655 E
TCSSCBR1
TCS(1)
TCM(1)
TRPPTRC1_TRIP
OR BLOCK ALARM
X115-BI2
CB Open Position
CCSPVC1
MCS 3I(1)
CSM 3I(1)
3I FAIL
Io ALARM
BLOCK
OR LED 9
SEQSPVC1
FUSEF(1)
60(1)
3I FUSEF_3PH
3U FUSEF_U
BLOCK
X115-BI1 CB_CLOSED
CB Closed Position DISCON_OPEN
MINCB_OPEN
One trip circuit supervision function is used by default, TCSSCBR1 for X100-PO3.
Both functions are blocked by the Master Trip TRPPTRC1 and the circuit breaker
open signal. The ALARM output indication is connected to the LED 9.
It is assumed that there is no external resistor in the circuit breaker
tripping coil circuit connected parallel with circuit breaker normally open
auxiliary contact.
110 REM620
Application Manual
1MRS757655 E REM620 default configurations
MASTER TRIP
PHLPTOC1_OPERATE
PHHPTOC1/2_OPERATE
PHIPTOC1_OPERATE
DPHLPDOC1_OPERATE
DPHHPDOC1/2_OPERATE
EFLPTOC1_OPERATE
EFHPTOC1_OPERATE
EFIPTOC1_OPERATE
DEFLPDEF1_OPERATE X115-SO2
TRPPTRC1
DEFHPDEF1_OPERATE
ROVPTOV1/2/3_OPERATE Master Trip(1)
PHPTOV1/2/3_OPERATE 94/86(1)
PHPTUV1/2/3_OPERATE
OR OPERATE
PSPTUV1/2_OPERATE TRIP
NSPTO V1/2_OPERATE
BLOCK CL_LKOUT
FRPFRQ1/2/3/4/5/6_OPERATE
MNSPTOC1/2_OPERATE RST_LKOUT
LOFLPTUC1/2_OPERATE
STTPMSU1_OPR_IIT
STTPMSU1_OPR_STALL
JAMPTOC1_OPERATE
MPTTR1_OPERATE OR X100-PO3
PREVPTOC1_OPERATE CBXCBR1_EXE_OP
MVGAPC1 ARCSARC1/2/3_OPERATE
CCBRBRF1_TRRET
X105-BI4 I4 Q4
External Trip
SPCGAPC1_O10_LO CKOUT_RESET
The operate signals from the protections, and an external trip X105-BI4 via
MVGAPC1 are connected to the output X115-SO2 and the trip output contact X100-
PO3 via the corresponding Master Trip TRPPTRC1. Open control commands to the
circuit breaker from the local or remote CBXCBR1_EXE_OP are connected directly to
the output X100-PO3.
TRPPTRC1 provides the lockout/latching function, event generation and the trip
signal duration setting. If the lockout operation mode is selected, one binary input
can be reassigned to the RST_LKOUT input of the Master Trip to enable external
reset with a push button.
REM620 111
Application Manual
REM620 default configurations 1MRS757655 E
DCSXSWI1
DCS(1)
X110-BI2
DCS(1)
DC1 Open Position
POSOPEN OPENPOS
POSCLOSE CLOSEPOS
X110-BI1
OKPOS
DC1 Closed Position AND
X115-BI2
DCS(2)
X110-BI4
DCS(2) AND
X115-BI1
DC2 Open Position CB Closed Position
CBXCBR1
PO SOPEN OPENPOS
PO SCLOSE CLOSEPOS
X110-BI3
OKPOS
OR I↔O CB(1)
DC2 Closed Position I↔O CB(1) CB_OPEN_COMMAND
TRPPTRC1_TRIP POSOPEN SELECTED
AND POSCLOSE EXE_OP CBXCBR1_EXE_OP
ENA_OPEN EXE_CL CB_CLOSE_COMMAND
ENA_CLOSE OPENPOS
ESSXSWI1 BLK_OPEN CLOSEPOS
ESS(1) RESTART INHIBIT BLK_CLOSE OKPOS
X100-PO4
X115-BI6
ESS(1) AU_OPEN OPEN_ENAD
ES Open Position
POSOPEN OPENPOS AU_CLOSE CLOSE_ENAD X100-PO1
X115-BI5 POSCLOSE CLOSEPOS TRIP
OKPOS SYNC_OK
ES Closed Position
SPCGAPC1_O11_ITL_BYPASS_ENABLE SYNC_ITL_BYP
X115-BI4
SSCBR1
CBCM(1)
CB Spring Charged
52CM(1)
X115-BI3 TRV_T_OP_ALM
3I
Gas Pressure Alarm BLOCK TRV_T_CL_ALM
POSOPEN SPR_CHR_ALM
POSCLOSE OPR_ALM
CB_OPEN_COMMAND OPEN_CB_EXE
OPR_LO OR LED 8
IPOW_ALM
CB_CLOSE_COMMAND CLOSE_CB_EXE IPOW_LO
PRES_ALM_IN CB_LIFE_ALM
MVGAPC1 PRES_LO_IN
SPR_CHR_ST
MON_ALM
PRES_ALM
X105-BI6
SPR_CHR PRES_LO
Emergency Stop RST_IPOW OPENPOS
I2 Q2 RST_CB_WEAR INVALIDPOS
RST_TRV_T CLOSEPOS
X105-BI5 I3 Q3 RST_SPR_T
OR
Emergency Start
SPCGAPC1_O8_EMERGENCY_START
There are two types of disconnector and earthing switch blocks available.
DCSXSWI1...4 and ESSXSWI1...3 are status only type, and DCXSWI1...4 and ESXSWI1…
3 are controllable type. By default, the status only blocks are connected in standard
configuration logic. If controllable operation is preferred, the controllable type of
disconnector and earthing switch blocks can be used instead of the status only
type. The connection and configuration of the control blocks can be done using
PCM600.
The binary inputs 1 and 2 of the card X130 are used for busbar disconnector 1
DCSXSWI1 position indication. The binary inputs 3 and 4 of the card X130 are used
for busbar disconnector 2 DCSXSWI2 position indication.
The binary inputs 7 and 8 of card X110 are designed for the position indication of
the earthing switch.
112 REM620
Application Manual
1MRS757655 E REM620 default configurations
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The
input can be activated by the configuration logic, which is a combination of the
position statuses of related primary equipment (disconnector and earthing switch),
the condition of the circuit breaker (CB gas pressure alarm, CB spring charged), and
the Master Trip logics. The OKPOS output from the DCSXSWI block defines if the
disconnector is definitely either open or close. This, together with non-active trip
signal activates the ENA_CLOSE signal to the circuit breaker control function block.
The open operation is always enabled.
The circuit breaker closing is blocked when the BKL_CLOSE input is activated, which
is connected to motor restart inhibit logic. When all conditions of the circuit breaker
closing are fulfilled, the CLOSE_ENAD output of the CBXCBR1 is activated and PO1
output X100-PO1 is closed.
Emergency stop signal to AU_OPEN input of CBXCBR1 via MVGAPC1 is used to open
the breaker by one push button through SPCGAPC1_O8 or by a binary input X105-
BI5. Emergency start signal to AU_CLOSE input of CBXCBR1 via MVGAPC1 is used to
close the breaker by one push button through SPCGAPC1_O16 or by a binary input
X105-BI6.
One push button can be used through SPCGAPC1_O11, which is connected to
SYNC_ITL_BYP input of CBXCBR1, to ignore the status of ENA_CLOSE input.
However, the BLK_CLOSE input signals is not bypassed with the interlocking bypass
functionality as they always have the higher priority.
If the ENA_CLOSE signal is completely removed from the breaker control
function block CBXCBR1 with PCM600, the function assumes that the
breaker close commands are allowed continuously.
The circuit breaker condition monitoring function SSCBR1 supervises the circuit
breaker status based on the binary input information connected and measured
current levels. The function introduces various supervision methods. The
corresponding supervision alarm signals are routed to LED 8.
REM620 113
Application Manual
REM620 default configurations 1MRS757655 E
PHLPTOC1_START
PHHPTOC1/2_START COMMON ALARM INDICATION 1 & 2
PHIPTOC1_START
DPHLPDOC1_START
DPHHPDOC1/2_START
EFLPTOC1_START
EFHPTOC1_START
EFIPTOC1_START
DEFLPDEF1_START
DEFHPDEF1_START
ROVPTOV1/2/3_START
OR
PHPTOV1/2/3_START
PHPTUV1/2/3_START
PSPTUV1/2_START
NSPTOV1/2_START
FRPFRQ1/2/3/4/5/6_START
MNSPTOC1/2_START
LOFLPTUC1/2_START
STTPMSU1_MOT_STARTUP
STTPMSU1_LOCK_START
PREVPTOC1_START TPGAPC1
X100-SO1
IN1 OUT1
IN2 OUT2
PHLPTOC1_OPERATE
X100-SO2
PHHPTOC1/2_OPERATE
PHIPTOC1_OPERATE
DPHLPDO C1_OPERATE
DPHHPDOC1/2_OPERATE
EFLPTOC1_OPERATE
EFHPTOC1_OPERATE
EFIPTOC1_OPERATE
DEFLPDEF1_OPERATE
DEFHPDEF1_OPERATE
ROVPTOV1/2/3_OPERATE
PHPTOV1/2/3_OPERATE
OR
PHPTUV1/2/3_OPERATE
PSPTUV1/2_OPERATE
NSPTO V1/2_OPERATE
FRPFRQ1/2/3/4/5/6_OPERATE
MNSPTOC1/2_OPERATE
LOFLPTUC1/2_OPERATE
STTPMSU1_OPR_IIT
STTPMSU1_OPR_STALL
JAMPTOC1_OPERATE
PREVPTOC1_OPERATE
ARCSARC1/2/3_OPERATE
MPTTR1_OPERATE
The signal outputs from the relay are connected to give dedicated information.
• Start of any protection function X100-SO1
• Operate of any protection function X100-SO2
TPGAPC are timers and used for setting the minimum pulse length for the outputs.
There are four generic timers TPGAPC1…4 available in the relay. The remaining ones
not described in the functional diagram are available in PCM600 for connection
where applicable.
114 REM620
Application Manual
1MRS757655 E REM620 default configurations
POWER QUALITY
CMHAI1
PQM3I(1)
PQM3I(1)
BLOCK ALARM
VMHAI1
PQM3U(1)
PQM3V(1)
BLOCK ALARM
PHQVVR1
PQMU(1)
PQMV(1)
BLOCK ALARM
OPERATE
START
SWELLST
DIPST
INTST
VSQVUB1
PQUUB(1)
PQVUB(1)
BLOCK MN_UNB_AL
PCT_UNB_AL
OBS_PR_ACT
The power quality function CMHAI1 is used to measure the harmonic contents of
the phase current.
The power quality function VMHAI1 is used to measure the harmonic contents of the
phase voltages.
REM620 115
Application Manual
REM620 default configurations 1MRS757655 E
The power quality function PHQVVR1 is used to measure the voltage variation, that
is, sags and swells.
The voltage unbalance power quality function VSQVUB1 monitors the voltage
unbalance conditions in power networks. It is used to monitor the commitment of
power supply utility of providing a balanced voltage supply on a continuous basis.
VSQVUB provides statistics which can be used to verify the compliance of the
power quality.
The above functions are included in default configuration for demonstration
purposes only, but not configured by default. The functions can be configured as
needed.
MEASUREMENT FUNCTION
LOW_ALARM LOW_ALARM
LO W_WARN LOW_WARN
PEMMXU1
P, E (1)
P, E (1)
RSTACM
CSMSQI1 VSMSQI1
I1, I2, I0 (1) U1, U2, U0 (1)
I1, I2, I0 (1) V1, V2, V0 (1)
LDPRLRC1
LOADPROF (1)
RESCMMXU1 LOADPROF (1)
Io (1) RSTMEM MEM_WARN
In (1) MEM_ALARM
BLOCK HIGH_ALARM
HIGH_WARN
FLTRFRC1
FAULTREC (1)
FAULTREC (1)
BLOCK
CB_CLRD
The phase current inputs to the relay are measured by the three-phase current
measurement function CMMXU1. The three-phase current input is connected to the
X131, X132 and X133 card in the back panel for three phases. The sequence current
measurement CSMSQI1 measures the sequence current and the residual current
measurement RESCMMXU1 measures the residual current. Residual current input is
connected to the X130 card in the back panel.
The three-phase bus side phase voltage inputs to the relay are measured by three-
phase voltage measurement VMMXU1. The three-phase current input is connected
to the X131, X132 and X133 card in the back panel for three phases. The sequence
voltage measurement VSMSQI1 measures the sequence voltage.
The measurements can be seen in the LHMI and they are available under the
measurement option in the menu selection. Based on the settings, function blocks
can generate low alarm or warning and high alarm or warning signals for the
measured current values.
116 REM620
Application Manual
1MRS757655 E REM620 default configurations
The frequency measurement FMMXU1 of the power system and the three-phase
power and energy measurement PEMMXU1 are available. Load profile record
LDPRLRC1 is included in the measurements sheet. LDPRLRC1 offers the ability to
observe the loading history of the corresponding bay. FLTRFRC1 is used to record
the monitor data during the fault condition. The records enable the analysis of
recent power system events.
MREFPTOC1
Io>R(1)
64R(1)
Io OPERATE
BLOCK START
ALARM
REM620 117
Application Manual
REM620 default configurations 1MRS757655 E
INTERCONNECTION FUNCTIONS
DQPTUV2
DQPTUV1
Q> -> ,3U< (1)
32Q, 27 (1)
3U OPERATE
BLOCK START
LVRTPTUV3
LVRTPTUV2
LVRTPTUV1
U<RT (1)
27RT (1)
3U OPERATE
BLOCK START
118 REM620
Application Manual
1MRS757655 E REM620 default configurations
DUPPDPR2
DUPPDPR1
P< (1)
32U (1)
3U OPERATE
3I START
DISABLE
BLOCK
DOPPDPR3
DOPPDPR2
DOPPDPR1
P>/Q> (1)
32R/32O (1)
3U OPERATE
3I START
BLOCK
REM620 119
Application Manual
REM620 default configurations 1MRS757655 E
THREE-PHASE UNDEREXCITATION
PROTECTION
UEXPDIS2
UEXPDIS1
X< (1)
40 (1)
3U OPERATE
3I START
EXT_LOS_DET
BLOCK
This configuration includes two TVTR function blocks. If no SMV receiver is defined,
ULTVTR1 receives three phase voltage inputs from the sensor and provides the
value to different functions. ULTVTR2 is dedicated for IEC 61850-9-2 LE receiving
only. SECRSYN1 and VAMMXU2 cannot be used if a IEC 61850-9-2 LE sample value is
not configured to be received by ULTVTR2.
120 REM620
Application Manual
1MRS757655 E REM620 default configurations
X131
4
5
IL1
7
8
U1 3U-U1
PHPTOV1
X132
4
5
IL2
7
8
U2 3U-U2 ULTVTR1 ROVPTOV1
*Calculated Uo
X133
4
5
IL3
7
8
U3 3U-U3
SECRSYN1
ULTVTR2
VAMMXU2
REM620 121
Application Manual
REM620 default configurations 1MRS757655 E
X131
4
5
IL1
7
8
U1
PHPTOV1
X132
4
IL2 9-2
5 LE
7
8
U2 ULTVTR1 ROVPTOV1
*Calculated Uo
X133
4
5
IL3
7
8
U3
SECRSYN1
ULTVTR2
VAMMXU2
Figure 84: ULTVTR1 uses three phase voltages from received IEC 61850-9-2 LE
sample value
122 REM620
Application Manual
1MRS757655 E REM620 default configurations
X131
4
5
IL1
7
8
U1 3U-U1
PHPTOV1
X132
4
5
IL2
7
8
U2 3U-U2 ULTVTR1 ROVPTOV1
*Calculated Uo
X133
4
5
IL3
7
8
U3 3U-U3
SECRSYN1
9-2
LE
ULTVTR2
VAMMXU2
Figure 86: ULTVTR2 uses UL1 voltage from received IEC 61850-9-2 LE sample value
REM620 123
Application Manual
IED physical connections 1MRS757655 E
4.1 Inputs
Terminal Description
X120:1-2 IL1_N
X120:3-4 IL2_N
X120:5-6 IL3_N
X120:7-8 IL1
X120:9-10 IL2
X120:11-12 IL3
Terminal Description
X120:13-14 Io
Terminal Description
X130:1-2 Io
124 REM620
Application Manual
1MRS757655 E IED physical connections
Terminal Description
X130:11-12 U1
X130:13-14 U2
X130:15-16 U3
Terminal Description
X130:9-10 U_SYN
Terminal Description
X130:17-18 Uo
Terminal Description
X131:4-5 IL1
X131:7-8 U1
X132:4-5 IL2
X132:7-8 U2
X133:4-5 IL3
X133:7-8 U3
Terminal Description
REM620 125
Application Manual
IED physical connections 1MRS757655 E
Terminal Description
X110:5-6 mA1 (AI1), +
mA1 (AI1), -
X110:7-8 mA2 (AI2), +
mA2 (AI2), -
X110:9-10 RTD1 (AI3), +
RTD1 (AI3), -
X110:11-12 RTD2 (AI4), +
RTD2 (AI4), -
X110:13-14 RTD3 (AI5), +
RTD3 (AI5), -
X110:15 Common 1
X110:16 Common 2
X110:17-18 RTD4 (AI6), +
RTD4 (AI6), -
X110:19-20 RTD5 (AI7), +
RTD5 (AI7), -
X110:21-22 RTD6 (AI8), +
RTD6 (AI8), -
Terminal Description
X105:5-6 mA1 (AI1), +
mA1 (AI1), -
X105:7-8 mA2 (AI2), +
mA2 (AI2), -
X105:9-10 RTD1 (AI3), +
RTD1 (AI3), -
X105:11-12 RTD2 (AI4), +
RTD2 (AI4), -
X105:13-14 RTD3 (AI5), +
RTD3 (AI5), -
X105:15 Common 3
X105:16 Common 4
Table continues on the next page
126 REM620
Application Manual
1MRS757655 E IED physical connections
Terminal Description
X105:17-18 RTD4 (AI6), + RTD4 (AI6), -
Terminal Description
X100:1 + Input
X100:2 - Input
Terminal Description
X110:1 BI1, +
X110:2 BI1, -
X110:3 BI2, +
X110:4 BI2, -
X110:5 BI3, +
X110:6 BI3, -
X110:6 BI4, -
X110:7 BI4, +
X110:8 BI5, +
X110:9 BI5, -
X110:9 BI6, -
X110:10 BI6, +
X110:11 BI7, +
X110:12 BI7, -
Table continues on the next page
REM620 127
Application Manual
IED physical connections 1MRS757655 E
Terminal Description
X110:12 BI8, -
X110:13 BI8, +
Terminal Description
X115:1 BI1,+
X115:2 BI1,-
X115:3 BI2,+
X115:4 BI2,-
X115:5 BI3,+
X115:6 BI3,-
X115:6 BI4,-
X115:7 BI4,+
X115:8 BI5,+
X115:9 BI5,-
X115:9 BI6,-
X115:10 BI6,+
X115:11 BI7,+
X115:12 BI7,-
X115:12 BI8,-
X115:13 BI8,+
Terminal Description
X130:1 BI1, +
X130:2 BI1, -
X130:3 BI2, +
X130:4 BI2, -
X130:5 BI3, +
X130:6 BI3, -
X130:7 BI4, +
X130:8 BI4, -
Binary inputs of slot X105 are optional for configurations A and B. One option is to
use BIO0005 and the other one is to use BIO0007.
128 REM620
Application Manual
1MRS757655 E IED physical connections
Terminal Description
X105:1 BI1,+
X105:2 BI1,-
X105:3 BI2,+
X105:4 BI2,-
X105:5 BI3,+
X105:6 BI3,-
X105:6 BI4,-
X105:7 BI4,+
X105:8 BI5,+
X105:9 BI5,-
X105:9 BI6,-
X105:10 BI6,+
X105:11 BI7,+
X105:12 BI7,-
X105:12 BI8,-
X105:13 BI8,+
Terminal Description
X105:1 BI1,+
X105:5 BI1,-
X105:2 BI2,+
X105:5 BI2,-
X105:3 BI3,+
X105:5 BI3,-
X105:4 BI4,-
X105:5 BI4,+
X105:6 BI5,+
X105:10 BI5,-
X105:7 BI6,-
X105:10 BI6,+
X105:8 BI7,+
X105:10 BI7,-
X105:9 BI8,-
X105:10 BI8,+
REM620 129
Application Manual
IED physical connections 1MRS757655 E
The protection relay is provided with connection sockets X13, X14 and
X15 only if the optional communication module with light sensor inputs
has been installed. If the arc protection option is selected when ordering
a protection relay, the light sensor inputs are included in the
communication module.
Terminal Description
X13 Input Light sensor 1
X14 Input Light sensor 2
X15 Input Light sensor 3
4.2 Outputs
Terminal Description
X100:6 PO1, NO
X100:7 PO1, NO
X100:8 PO2, NO
X100:9 PO2, NO
X100:15 PO3, NO (TCS resistor)
X100:16 PO3, NO
X100:17 PO3, NO
X100:18 PO3 (TCS1 input), NO
X100:19 PO3 (TCS1 input), NO
X100:20 PO4, NO (TCS resistor)
X100:21 PO4, NO
X100:22 PO4, NO
X100:23 PO4 (TCS2 input), NO
X100:24 PO4 (TCS2 input), NO
130 REM620
Application Manual
1MRS757655 E IED physical connections
Terminal Description
X100:10 SO1, common
X100:11 SO1, NC
X100:12 SO1, NO
X100:13 SO2, NO
X100:14 SO2, NO
Terminal Description
X110:14 SO1, common
X110:15 SO1, NO
X110:16 SO1, NC
X110:17 SO2, common
X110:18 SO2, NO
X110:19 SO2, NC
X110:20 SO3, common
X110:21 SO3, NO
X110:22 SO3, NC
X110:23 SO4, common
X110:24 SO4, NO
Terminal Description
X115:14 SO1,common
X115:15 SO1,NO
X115:16 SO1,NC
X115:17 SO2,common
X115:18 SO2,common
X115:19 SO2,common
X115:20 SO3,common
X115:21 SO3,NO
X115:22 SO3,NC
X115:23 SO4,common
X115:24 SO4,NO
Output contacts of X105 are optional for configurations A and B. One option is to
use BIO0005 and the other one is to use BIO0007.
REM620 131
Application Manual
IED physical connections 1MRS757655 E
Terminal Description
X105:14 SO1,common
X105:15 SO1,NO
X105:16 SO1,NC
X105:17 SO2,common
X105:18 SO2,NO
X105:19 SO2,NC
X105:20 SO3,common
X105:21 SO3,NO
X105:22 SO3,NC
X105:23 SO4,common
X105:24 SO4,NO
Terminal Description
X105:15 HSO1,NO
X105:16 HSO1,NO
X105:19 HSO2,NO
X105:20 HSO2,NO
X105:23 HSO3,NO
X105:24 HSO3,NO
4.2.3 IRF
The IRF contact functions as an output contact for the self-supervision system of
the protection relay. Under normal operating conditions, the protection relay is
energized and the contact is closed (X100:3-5). When a fault is detected by the self-
supervision system or the auxiliary voltage is disconnected, the contact X100:3-5
drops off and the contact X100:3-4 closes.
Terminal Description
X100:3 IRF, common
X100:4 Closed; IRF, or Uaux disconnected
X100:5 Closed; no IRF, and Uaux connected
132 REM620
Application Manual
1MRS757655 E Glossary
5 Glossary
100BASE-FX A physical medium defined in the IEEE 802.3 Ethernet standard for local
area networks (LANs) that uses fiber optic cabling
100BASE-TX A physical medium defined in the IEEE 802.3 Ethernet standard for local
area networks (LANs) that uses twisted-pair cabling category 5 or higher
with RJ-45 connectors
620 series Series of numerical protection and control relays for high-end protection
and supervision applications of utility substations, and industrial switch-
gear and equipment
AC Alternating current
ANSI American National Standards Institute
AR Autoreclosing
ASCII American Standard Code for Information Interchange
BI Binary input
BI/O Binary input/output
BO Binary output
CT Current transformer
DAN Doubly attached node
DC 1. Direct current
2. Disconnector
3. Double command
REM620 133
Application Manual
Glossary 1MRS757655 E
134 REM620
Application Manual
1MRS757655 E Glossary
Single-line dia- Simplified notation for representing a three-phase power system. In-
gram stead of representing each of three phases with a separate line or termi-
nal, only one conductor is represented.
SMV Sampled measured values
SNTP Simple Network Time Protocol
SO Signal output
TCS Trip-circuit supervision
VT Voltage transformer
WAN Wide area network
WHMI Web human-machine interface
REM620 135
Application Manual
—
ABB Distribution Solutions
Digital Substation Products
P.O. Box 699
FI-65101 VAASA, Finland
Phone +358 10 22 11
www.abb.com/mediumvoltage
www.abb.com/relion
www.abb.com/substationautomation
1MRS757655 E