0% found this document useful (0 votes)
13 views164 pages

Doca0101en 04

The MasterPact MTZ2/MTZ3 User Guide provides comprehensive information on IEC circuit breakers and switch-disconnectors ranging from 800 to 6300 A. It includes safety information, operational instructions, commissioning, and troubleshooting guidelines. Users are advised to perform risk analysis and testing for specific applications, as Schneider Electric disclaims liability for misuse of the information provided.

Uploaded by

Matias
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
13 views164 pages

Doca0101en 04

The MasterPact MTZ2/MTZ3 User Guide provides comprehensive information on IEC circuit breakers and switch-disconnectors ranging from 800 to 6300 A. It includes safety information, operational instructions, commissioning, and troubleshooting guidelines. Users are advised to perform risk analysis and testing for specific applications, as Schneider Electric disclaims liability for misuse of the information provided.

Uploaded by

Matias
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 164

MasterPact MTZ2/MTZ3

DOCA0101EN-04 07/2020

MasterPact MTZ2/MTZ3
IEC Circuit Breakers and Switch-Disconnectors
from 800 to 6300 A
User Guide
07/2020
DOCA0101EN-04

www.schneider-electric.com
The information provided in this documentation contains general descriptions and/or technical character-
istics of the performance of the products contained herein. This documentation is not intended as a
substitute for and is not to be used for determining suitability or reliability of these products for specific user
applications. It is the duty of any such user or integrator to perform the appropriate and complete risk
analysis, evaluation and testing of the products with respect to the relevant specific application or use
thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for
misuse of the information contained herein. If you have any suggestions for improvements or amendments
or have found errors in this publication, please notify us.
You agree not to reproduce, other than for your own personal, noncommercial use, all or part of this
document on any medium whatsoever without permission of Schneider Electric, given in writing. You also
agree not to establish any hypertext links to this document or its content. Schneider Electric does not grant
any right or license for the personal and noncommercial use of the document or its content, except for a
non-exclusive license to consult it on an "as is" basis, at your own risk. All other rights are reserved.
All pertinent state, regional, and local safety regulations must be observed when installing and using this
product. For reasons of safety and to help ensure compliance with documented system data, only the
manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant instructions must
be followed.
Failure to use Schneider Electric software or approved software with our hardware products may result in
injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2020 Schneider Electric. All rights reserved.

2 DOCA0101EN-04 07/2020
Table of Contents

Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Chapter 1 MasterPact MTZ2/MTZ3 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
MasterPact MTZ2/MTZ3 Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Fixed Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Drawout Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Device Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
MicroLogic X Control Unit: Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Go2SE Landing Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Operating Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Chapter 2 MasterPact MTZ2/MTZ3 Normal Operation . . . . . . . . . . . . . . . . . . . . . . . . 33
2.1 Device Operating Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Operating the Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Control Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Opening the Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Closing the Device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Resetting the Circuit Breaker. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Engaging the ERMS Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Operating Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
2.2 Drawout Device Racking Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Drawout MasterPact MTZ2/MTZ3 Device Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Disconnecting the Drawout Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Connecting the Drawout Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Removing the Drawout Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Installing the Drawout Device in the Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
2.3 Device Locking Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Locking the Pushbuttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Locking the Device in Open Position with Padlocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Locking the Device in Open Position with Keylocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Chassis Locking in Disconnected Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Chassis Locking in Any Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Locking the Safety Shutters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
2.4 Device Interlocking Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Mismatch Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
VPEC Door Interlock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
VPOC Open-door Racking Interlock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
IPA Cable-type Door Interlock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Mechanical Interlocking for Transfer Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
DAE Automatic Spring-Discharge Interlock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
IBPO Racking Interlock Between Racking Handle and Opening Pushbutton . . . . . . . . . . . . 105
Chapter 3 MasterPact MTZ Critical Cases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Finding the Cause of a Trip or an Alarm in Critical Cases. . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Resetting the Circuit Breaker After a Trip Due to an Electrical Fault . . . . . . . . . . . . . . . . . . 111
Resetting the Circuit Breaker After a Trip Due to an Incident Detected by the MicroLogic X
Self-tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Diagnosing Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Diagnosing Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124

DOCA0101EN-04 07/2020 3
Chapter 4 MasterPact MTZ Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Introduction to Commissioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Inspection and MicroLogic X Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Communication Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Final Checks and Reporting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
MasterPact MTZ Test Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Chapter 5 MasterPact MTZ Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Introduction to Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Troubleshooting: Chassis Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Troubleshooting: Unexpected Tripping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Troubleshooting: Mechanical Control Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
Troubleshooting: Electrical Control Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
Troubleshooting: Control Operations from EcoStruxure Power Device App . . . . . . . . . . . . . 149
Troubleshooting: Control Operations from IO Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Troubleshooting: Control Operations from EcoStruxure Power Commission Software . . . . . 152
Troubleshooting: Control Operations from IFE/EIFE Webpages . . . . . . . . . . . . . . . . . . . . . . 154
Troubleshooting: Control Operations from Communication Network. . . . . . . . . . . . . . . . . . . 156
Troubleshooting: Control Operations from FDM128 Display . . . . . . . . . . . . . . . . . . . . . . . . . 158
Chapter 6 Schneider Electric Green Premium™ Ecolabel . . . . . . . . . . . . . . . . . . . . . . 159
Schneider Electric Green Premium™ Ecolabel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159

4 DOCA0101EN-04 07/2020
Safety Information

Important Information

NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before
trying to install, operate, service, or maintain it. The following special messages may appear throughout
this documentation or on the equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.

PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this
material.
A qualified person is one who has skills and knowledge related to the construction and operation of
electrical equipment and its installation, and has received safety training to recognize and avoid the
hazards involved.

DOCA0101EN-04 07/2020 5
SAFETY NOTICE

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
 Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See
NFPA 70E, CSA Z462, NOM 029-STPS or local equivalent.
 This equipment must only be installed and serviced by qualified electrical personnel.
 Turn off all power supplying this equipment before working on or inside this equipment.
 Always use a properly rated voltage sensing device to confirm power is off.
 Replace all devices, doors, and covers before turning on power to this equipment.
 Beware of potential hazards, and carefully inspect the work area for tools and objects that may have
been left inside the equipment.
Failure to follow these instructions will result in death or serious injury.

CYBERSECURITY SAFETY NOTICE

WARNING
POTENTIAL COMPROMISE OF SYSTEM AVAILABILITY, INTEGRITY, AND CONFIDENTIALITY
 Change default passwords at first use to help prevent unauthorized access to device settings,
controls, and information.
 Disable unused ports/services and default accounts to help minimize pathways for malicious
attackers.
 Place networked devices behind multiple layers of cyber defenses (such as firewalls, network
segmentation, and network intrusion detection and protection).
 Use cybersecurity best practices (for example, least privilege, separation of duties) to help prevent
unauthorized exposure, loss, modification of data and logs, or interruption of services.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

6 DOCA0101EN-04 07/2020
About the Book

At a Glance

Document Scope
The aim of this guide is to provide users, installers, and maintenance personnel with technical information
needed to operate MasterPact™ MTZ2/MTZ3 circuit breakers and switch-disconnectors, in compliance
with the IEC standards.

Validity Note
This guide applies to MasterPact MTZ2/MTZ3 circuit breakers and switch-disconnectors.
This guide applies to MicroLogic™ X control units:
 With firmware version 004.000.000 or greater
 With hardware version 001.000.000 or greater

NOTE: This guide also applies to MicroLogic™ Xi control units. A MicroLogic Xi control unit is a
MicroLogic X control unit without Bluetooth low energy (BLE) communication.
The specific features of the MicroLogic Xi control units are described in the appendix in DOCA0102EN
MasterPact MTZ - MicroLogic X Control Unit - User Guide.

Online Information
The information contained in this guide is likely to be updated at any time. Schneider Electric strongly
recommends that you have the most recent and up-to-date version available on
www.se.com/ww/en/download.
The technical characteristics of the devices described in this guide also appear online. To access the
information online, go to the Schneider Electric home page at www.se.com.

Related Documents

Title of Documentation Reference Number


MasterPact MTZ - MicroLogic X Control Unit - User Guide DOCA0102EN
MasterPact MTZ - Modbus Communication Guide DOCA0105EN
MasterPact MTZ - IEC 61850 Communication Guide DOCA0162EN
MasterPact MTZ - IEC Circuit Breakers and Switch-Disconnectors - Maintenance DOCA0099EN
Guide
MasterPact MTZ Catalogue LVPED216026EN
MasterPact MTZ2/MTZ3 - Fixed IEC Circuit Breaker or Switch-Disconnector - NVE35469
Instruction Sheet
MasterPact MTZ2/MTZ3 - Drawout IEC Circuit Breaker or Switch-Disconnector - NVE35470
Instruction Sheet
Enerlin'X IO - Input/Output Application Module for One IEC Circuit Breaker - User DOCA0055EN
Guide
Enerlin'X IFE - Ethernet Switchboard Server - User Guide DOCA0084EN
Enerlin'X IFE - Ethernet Interface for One IEC Circuit Breaker - User Guide DOCA0142EN
Enerlin'X EIFE - Embedded Ethernet Interface for One MasterPact MTZ Drawout DOCA0106EN
Circuit Breaker - User Guide
Enerlin’X FDM128 - Ethernet Display for Eight Devices - User Guide DOCA0037EN
ULP System for MasterPact and ComPact (IEC Standard) - User Guide DOCA0093EN

You can download these technical publications and other technical information from our website at
https://www.se.com/ww/en/download/ .

Trademark Notice
All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.

DOCA0101EN-04 07/2020 7
8 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3
MasterPact MTZ2/MTZ3 Description
DOCA0101EN-04 07/2020

Chapter 1
MasterPact MTZ2/MTZ3 Description

MasterPact MTZ2/MTZ3 Description

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
MasterPact MTZ2/MTZ3 Range 10
Fixed Device 12
Drawout Device 16
Device Identification 23
MicroLogic X Control Unit: Description 26
Go2SE Landing Page 29
Operating Conditions 31

DOCA0101EN-04 07/2020 9
MasterPact MTZ2/MTZ3 Description

MasterPact MTZ2/MTZ3 Range

Description
The MasterPact MTZ2/MTZ3 range of circuit breakers and switch-disconnectors offers current ratings from
800 A to 6,300 A, for AC power systems up to 1,150 Vac.
The MasterPact MTZ2/MTZ3 range is available in the following frame sizes:
 MasterPact MTZ2 for current ratings from 800 A to 4,000 A
 MasterPact MTZ3 for current ratings from 4,000 A to 6,300 A

Each frame size is available in the following power systems:


 3-pole (3P)
 4-pole (4P)

Devices are available in the following installation types:


 Fixed-mounted devices
 Drawout devices

Convention
In this guide, the term MasterPact MTZ device covers circuit breakers and switch-disconnectors.

Circuit Breakers
The following performance levels are available:
 N1: standard short-circuit level (42 kA) with total selectivity
 H1: high short-circuit level (66 kA) with total selectivity
 H2: very high short-circuit level (100 kA) with very high selectivity (85 kA)
 H2V: very high short-circuit level (100 kA) with very high selectivity (100 kA) (Rated operational voltage
Ue limited to 440 Vac)
 H3: extremely high short-circuit level (150 kA) with high selectivity (66 kA)
 L1: extremely high short-circuit level (150 kA) with strong current limitation and significant selectivity
(30 kA)
NOTE: The values above correspond to a 440 Vac network, for higher voltage levels the values can be
different. Refer to LVPED216026EN MasterPact MTZ Catalogue.

Circuit breakers are fitted with a MicroLogic X control unit.


For full information about available circuit breaker models, frame sizes, interrupting ratings, sensor ratings,
and control units, refer to LVPED216026EN MasterPact MTZ Catalogue.

Switch-Disconnectors
The following performance levels are available:
 NA: Icw = 42 kA/1s
 HA: Icw = 66 kA/1s
 HF: Icw = 85 kA/1s
 HH: Icw = 100 kA/1s

For information about available switch-disconnector models and frame sizes, refer to LVPED216026EN
MasterPact MTZ Catalogue.

10 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Description

Neutral Position on 4P Devices


On 4P circuit breakers:
 For MasterPact MTZ2 N1, H3, L1, H10, the neutral position is on the left side as standard.
 For MasterPact MTZ2 H1, H2, and H2V, the neutral position is on the left side as standard. A version
with neutral position on the right side is available when ordering.
 For MasterPact MTZ3 H1, H2, the neutral position is on the left side as standard. A version with neutral
position on the right side is available when ordering.
On 4P switch-disconnectors:
 For MasterPact MTZ2 NA, HA, HF, the neutral position can be switched from the left side to the right
side using the label provided.
 For MasterPact MTZ2 HH, the neutral position is on the left side as standard. A version with neutral
position on the right side is available when ordering.
 For MasterPact MTZ3 HA, the neutral position is on the left side as standard.

DOCA0101EN-04 07/2020 11
MasterPact MTZ2/MTZ3 Description

Fixed Device

Fixed Device Description


The following image shows the standard version of the fixed device (no optional accessories).

A Mounting side plate


B Carrying grip
C Arc chute
D Blue fault-trip reset button
E Opening pushbutton
F Closing pushbutton
G Spring charging handle
H Terminal blocks for standard accessories
I Front cover
J VBP pushbutton locking cover (optional)
K Rating plate
L Spring charged and ready-to-close indicator
M Main-contact position indicator
N Window to read the (optional) CDM mechanical
operation counter
O Control unit
P Control unit transparent cover

Fixed Device Accessories Description


The following image shows the accessories available for the fixed device.

A Additional support brackets for mounting on a


backplate
B ULP port module
C Terminal blocks for optional accessories
D Four OF indication contacts (optional)
E Four OF indication contacts (delivered as
standard)
F KMT grounding kit
G MCH gear motor
H CDM mechanical operation counter
Z1, Z2 See following images

12 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Description

The following images zoom in on the accessories for the fixed device:

I Standard SDE1 fault-trip indication contact N MN undervoltage release or MX2 opening voltage release
J Optional SDE2 fault-trip indication contact or RES electrical O MX1 opening voltage release
remote reset P PF ready-to-close contact
K Microswitch Q XF closing voltage release
L M2C programmable contacts or ESM ERMS switch module R BPFE electrical closing pushbutton
M Isolation module S VCPO OFF-position locking by padlocks
T VSPO OFF-position locking by keylocks

DOCA0101EN-04 07/2020 13
MasterPact MTZ2/MTZ3 Description

Fixed Device Terminal Block Description

Terminal block supplied as standard on the circuit breaker

Terminal block for optional accessories on the circuit breaker

14 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Description

Assignment of Terminal Blocks


The following table describes the assignment and the availability of the terminal blocks for circuit breakers
and switch-disconnectors for fixed devices:
 Standard terminal blocks and the associated accessories are delivered with the device.
 Optional terminal blocks are delivered with the device only if the associated optional accessories are
installed in the device.
 N/A indicates that the terminal blocks and the associated optional accessories are not compatible with
the device.

Block Marking Description Circuit Switch-disconnector


breaker
A COM Terminal block for the external power supply Standard N/A
of the MicroLogic X control unit
or ULP port module Optional N/A
UC1 Zone selective interlocking (ZSI), Standard N/A
rectangular sensor for earth-leakage
protection, or MDGF module input
UC2 Neutral external sensor, rectangular sensor Standard N/A
for earth-leakage protection, or MDGF
module input
SDE2/RES SDE2 additional fault-trip indication contact Optional N/A on MasterPact MTZ NA,
HA, HA10
Optional on MasterPact MTZ2
HF, HH

or RES electrical remote reset N/A


UC4 External voltage connector Optional N/A
UC3 External voltage connector Optional N/A
M2C/ESM M2C programmable contacts or ESM ERMS Optional N/A
switch module
SDE1 SDE1 fault-trip indication contact Standard N/A on MasterPact MTZ NA,
HA, HA10
Standard on MasterPact MTZ2
HF, HH
B MN/MX2 MN undervoltage release Optional Optional
or MX2 opening voltage release
MX1 MX1 opening voltage release Optional Optional
XF XF closing voltage release Optional Optional
PF PF ready-to-close contact Optional Optional
MCH MCH gear motor Optional Optional
C OF21–OF24 4 OF indication contacts Optional Optional
OF11–OF14 4 OF indication contacts Optional Optional
OF1–OF4 4 OF indication contacts Standard Standard

DOCA0101EN-04 07/2020 15
MasterPact MTZ2/MTZ3 Description

Drawout Device

Definition
A drawout device is composed of the moving part (also called the device) and the fixed part (or chassis).

Drawout Device Moving Part Description


The following image shows the standard version of the moving part of a drawout device (no optional
accessories).

A Carrying grip
B Arc chute
C Blue fault-trip reset button
D Opening pushbutton
E Closing pushbutton
F Spring charging handle
G Terminal block connectors
H Front cover
I VBP pushbutton locking cover (optional)
J Rating plate
K Spring charged and ready-to-close indicator
L Main-contact position indicator
M Window to consult the (optional) CDM
mechanical operation counter
N Control unit
O Control unit transparent cover

16 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Description

Drawout Device Accessories Description


The following image shows the accessories available for the moving part of a drawout device.

A VDC mismatch protection


B Terminal block connectors for optional
accessories
C Terminal block connectors for standard
accessories
D Optional block of four OF indication contacts
or EF combined connected/closed contacts
E Four OF indication contacts (delivered as
standard)
F KMT grounding kit
G MCH gear motor
H CDM mechanical operation counter
Z1, Z2 See following images

DOCA0101EN-04 07/2020 17
MasterPact MTZ2/MTZ3 Description

The following images zoom in on the accessories for the moving part of a drawout device.

I Standard SDE1 fault-trip indication contact O MN undervoltage release or MX2 opening voltage release
J Optional SDE2 fault-trip indication contact or RES electrical P MX1 opening voltage release
remote reset Q PF ready-to-close contact
K Microswitch R XF closing voltage release
L IBPO interlock between racking handle and opening pushbutton S BPFE electrical closing pushbutton
M M2C programmable contacts or ESM ERMS switch module T VCPO OFF-position locking by padlocks
N Isolation module U VSPO OFF-position locking by keylocks

18 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Description

Chassis Description
The following image shows the standard version of the chassis (no optional accessories).

A Carrying grip K Racking handle


B ULP port module L Moving part position indicator
C Terminal blocks supplied as standard M Racking handle socket
D Terminal block identification plate N Position release button
E Top safety shutter O Chassis locking by padlocks
F Bottom safety shutter P Latch for switching chassis locking from disconnected position to
G Rail release tab any position (connected, test, disconnected)
H Drawout grip Q Shutter locking block
I Extension rail
J Racking handle storage space

DOCA0101EN-04 07/2020 19
MasterPact MTZ2/MTZ3 Description

Chassis Accessories Description


The following image shows the accessories available for the chassis.

A VDC mismatch protection G VPOC open-door racking interlock


B Drawout device position contacts H VIVC shutter position indication and locking
C Optional terminal block I IBPO interlock between racking handle and opening pushbutton
D Cord between ULP port module and EIFE interface J VSPD chassis locking by keylocks
E EIFE embedded Ethernet interface K VPEC door interlock
F Circuit breaker auxiliary terminal shield

20 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Description

Chassis Terminal Block Description

Terminal block supplied as standard on the chassis

Optional terminal block on the chassis

(1) Supplied as standard with chassis for MasterPact MTZ2/MTZ3 circuit breakers only
(2) Supplied as standard with 3P chassis only

DOCA0101EN-04 07/2020 21
MasterPact MTZ2/MTZ3 Description

Assignment of Terminal Blocks


The following table describes the assignment and the availability of the terminal blocks for circuit breakers
and switch-disconnectors for drawout devices:
 Standard terminal blocks are delivered on the chassis, even if the associated optional accessories are
not installed in the device.
 Optional terminal blocks are delivered on the chassis only if the associated optional accessories are
installed in the device.
 N/A indicates that the terminal blocks and the associated optional accessories are not compatible with
the device.

Block Marking Description Circuit breaker Switch-disconnector


A CD1–CD3 3 CD disconnected position contacts Optional Optional
CE4–CE6 or 3 CE connected position contacts
B COM ULP port module Standard N/A
UC1 Zone selective interlocking (ZSI), rectangular Standard Standard
sensor for earth-leakage protection, or
MDGF module input
UC2 Neutral external sensor, rectangular sensor Standard Standard
for earth-leakage protection, or MDGF
module input
SDE2/RES SDE2 additional fault-trip indication contact Optional N/A on MasterPact MTZ
NA, HA, HA10
Optional on
MasterPact MTZ2 HF, HH
or RES electrical remote reset N/A
UC4 External voltage connector Optional N/A
UC3 External voltage connector Standard on Standard on 3P switch-
3P circuit disconnectors
breakers

Optional on 4P N/A on 4P switch-


circuit disconnectors
breakers
M2C/ESM M2C programmable contacts Optional N/A
or ESM ERMS switch module
SDE1 SDE1 fault-trip indication contact Standard Standard
CE1–CE3 3 CE connected position contacts Optional Optional
CT4–CT6 or 3 CT test position contacts
C MN/MX2 MN undervoltage release Standard Standard
or MX2 opening voltage release
MX1 MX1 opening voltage release Standard Standard
XF XF closing voltage release Standard Standard
PF PF ready-to-close contact Standard Standard
MCH MCH gear motor Standard Standard

D (1) OF11–OF24 8 OF indication contacts Optional Optional


EF11–EF24 or 8 EF combined connected/closed position
auxiliary contacts
OF1–OF4 4 OF indication contacts Standard Standard
CT1–CT3 3 CT test position contacts Optional Optional
CD4–CD6 or 3 CD disconnected position contacts
CE7–CE9 or 3 CE connected position contacts
D(2) OF11–OF22 6 OF indication contacts Optional N/A
EF11–EF22 or 6 EF combined connected/closed position
auxiliary contacts
OF1–OF4 4 OF indication contacts Standard Standard
EIFE EIFE embedded Ethernet interface Optional N/A
(1) Without EIFE interface
(2) With EIFE interface

22 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Description

Device Identification

Identification
The MasterPact MTZ2/MTZ3 device can be identified in the following ways:
 Rating plate on device
 QR code located:
 On the front face of the control unit of the circuit breaker
 On the front face of the switch-disconnector

 Identification labels on the device and on the chassis

A Product identification label


B Product checked label
C Accessory voltages label
D Rating plate
E QR code to access product information

DOCA0101EN-04 07/2020 23
MasterPact MTZ2/MTZ3 Description

Product Identification Label

Legend Description Explanation


A Product code The product code is a line of code representing the complete
configuration of a MasterPact circuit breaker or switch-disconnector. It is
automatically generated for each MasterPact device after completing the
configuration using the Product Selector configuration tool.
The product code appears on the invoice and on the delivery documents
as well as on the MasterPact device and packaging labels.
The product code can be entered in the Product Selector configuration
tool, which generates the complete configuration of the MasterPact
device.
B Schneider Electric internal –
identification numbers
C Description of device The description of the device, specifies the following characteristics:
 Range
 Rating
 Performance level
 Number of poles
 Control unit type

D Certification logos The logos of the mandatory certifications of the device.


E Device serial number The device serial number is coded PPYYWWDXXXX, where:
 PP: Plant code
 YY: Year of manufacture
 WW: Week of manufacture
 D: Day of the week of manufacture (Monday = 1)
 XXXX: The production number of the product on the day. Ranges from
0001 to 9999
For example, PP162330064 is the sixty fourth device manufactured at
plant PP on Wednesday, June 8, 2016.

Product Checked Label

Legend Description Explanation


F Device serial number See explanation in preceding table.
G Device test date code The device test date code is coded PPYYWWD HH:MM, where:
 PP: plant code
 YY: year of test
 WW: week of test
 D: day of the week of test (Monday = 1)
 HH:MM: the time of test in hours and minutes

Accessory Voltages Label

The accessory voltages label gives the voltage of the accessories which are installed in the device and
which need to be connected to a power supply.

24 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Description

Rating Plate
The rating plate with the device information is located on the front cover of the device.

Circuit breaker rating plate Switch-disconnector rating plate

A Device size and rated current x 100 A J Uimp: rated impulse withstand voltage
B Ui: rated insulation voltage K Icu: rated ultimate short-circuit breaking capacity
C Ue: rated operational voltage L Selectivity category as per IEC 60947-2
D Frequency M Place for sticker with IP address of the optional EIFE
E Type of device: circuit breaker or switch-disconnector, interface
suitable for insulation N Icm: rated short-circuit making capacity
F Ics: rated service short-circuit breaking capacity O Ith: conventional free air thermal current
G Icw: rated short-time withstand current P Ie: rated operational current
H Standards Q Information related to switch-disconnectors used as
I Performance level unprotected circuit breakers

QR Code
When the QR code on the front face of a MasterPact MTZ device is scanned with a smartphone running a
QR code reader and connected to the Internet, the Go2SE landing page is displayed (see page 29). The
landing page displays some information about the device and a list of menus.

DOCA0101EN-04 07/2020 25
MasterPact MTZ2/MTZ3 Description

MicroLogic X Control Unit: Description

Introduction
The MicroLogic X control unit includes:
 LEDs to monitor the status of the circuit breaker
 A local Human Machine Interface comprising a graphic display with colored backlight, contextual
buttons, and dedicated buttons
 LEDs to monitor the cause of trips and alarms

Control Unit Description

A Ready LED
B Service LED
C ERMS LED
D Graphic display screen
E NFC wireless communication zone
F Home button
G Three contextual buttons
H Escape button ESC
I Bluetooth LED
J Bluetooth activation button
K Test button for ground-fault and earth-leakage
protection (MicroLogic 6.0 X and 7.0 X)
L Test/Reset button for trip cause LEDs and alarms
M Mini USB port under rubber cover
N Overload and trip cause LEDs
O Cover for internal battery
P VPS voltage power supply module (optional)
Q VPS LED to indicate that the VPS module is
supplying the control unit
R QR code to access product information
S Control unit identification number
T Control unit type
U Sensor plug with the rated current of the circuit
breaker
V Plastic cover

Status LEDs

LED Description
Ready The Ready LED blinks slowly when the standard protection functions of the control unit are
operational.
The service LED alerts the user to the health state of the circuit breaker.
 Orange LED: medium severity detected alarm that requires non-urgent maintenance action.
 Red LED: high severity detected alarm that requires immediate maintenance action.

ERMS The ERMS (Energy Reduction Maintenance Setting) LED has the following statuses:
 Blue LED: ERMS engaged
 Off LED: ERMS disengaged

Display Screen with Contextual Buttons and Dedicated Buttons


The local HMI screen and buttons are used to:
 Navigate the menu structure.
 Display monitored values.
 Access and edit configuration settings.

26 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Description

NFC Communication Zone


The NFC communication zone is used to establish an NFC connection between a smartphone running the
EcoStruxure Power Device app and the MicroLogic X control unit. When the connection is established, the
circuit breaker operating data is automatically uploaded to the smartphone.

Bluetooth Activation Button and LED


The Bluetooth activation button is used to establish a Bluetooth low energy connection between a
smartphone running the EcoStruxure Power Device app and the MicroLogic X control unit. When the
connection is established, the circuit breaker can be monitored and controlled from the smartphone.
When the Bluetooth LED is blinking, it indicates that the MicroLogic X control unit is in communication with
a Bluetooth device.

Test Button
The test button is used to test the ground-fault protection for MicroLogic 6.0 X and the earth-leakage
protection for MicroLogic 7.0 X.

Overload and Trip Cause LEDs


The indications of the four trip cause LEDs depend on the type of MicroLogic X control unit.

LEDs Description
 MicroLogic 2.0 X, 5.0 X, 6.0 X, 7.0 X: Overload pre-alarm, the load exceeds 90%
and is lower than 105% of the Ir setting of the long-time protection.

 MicroLogic 2.0 X, 5.0 X, 6.0 X, 7.0 X: Overload alarm, the load exceeds 105% of
the Ir setting of the long-time protection.

 MicroLogic 2.0 X, 5.0 X, 6.0 X, 7.0 X: Trip due to long-time protection.

 MicroLogic 2.0 X: Trip due to instantaneous protection.


 MicroLogic 5.0 X, 6.0 X, 7.0 X: Trip due to short-time protection or instantaneous
protection.

 MicroLogic 2.0 X, 5.0 X: Not applicable.


 MicroLogic 6.0 X: Trip due to ground-fault protection.
 MicroLogic 7.0 X: Trip due to earth-leakage protection.

 MicroLogic 2.0 X, 5.0 X, 6.0 X, 7.0 X: Trip due to optional protections.

 MicroLogic 2.0 X, 5.0 X, 6.0 X, 7.0 X: MicroLogic control unit invalid result detected
during self test.

NOTE: If the MicroLogic X control unit is not powered, the trip cause LEDs go off after 4 hours. After this
period, press the Test/Reset button to light them again.

DOCA0101EN-04 07/2020 27
MasterPact MTZ2/MTZ3 Description

Test/Reset Button
The Test/Reset button performs the following functions:
 Test of the internal battery or check LED functionality: press and hold the Test/Reset button for less than
3 seconds, the four trip cause LEDs switch off for one second. One of the following results:
 The four trip cause LEDs switch on for two seconds: the battery is OK.
 The four trip cause LEDs flash sequentially for two seconds: the battery is near the end of its life.
Replace the battery.
 The four trip cause LEDs do not light: replace the battery.

NOTE: This test must be carried out immediately after the replacement of the internal battery to check
the correct functioning of the new battery. It can then be carried out at any time in the life of the internal
battery.
 Reset of the latched events: press and hold the Test/Reset button for more than 3 seconds to reset the
latched events. The trip cause LEDs and the service LED switch off.

Mini USB Port


Remove the rubber cover of the mini USB port to connect the following devices:
 A Mobile Power Pack to supply power to the MicroLogic X control unit.
 A smartphone running the EcoStruxure Power Device app through USB OTG connection.
 A PC running EcoStruxure Power Commission software.

NOTE: The MicroLogic X control unit does not support USB keys. Even if a USB key is connected using
an adapter, data is not transferred.

QR Code
When the QR code on the front face of a MicroLogic X control unit is scanned with a smartphone running
a QR code reader and connected to the Internet, the Go2SE landing page is displayed (see page 29). The
landing page displays some information about the device and a list of menus.

Control Unit Identification Number


The identification number is made up as follows:
 The serial number of the MicroLogic X control unit in the format FFFFFFYYWWDLXXXX
 The commercial reference of the control unit in the format LV8•••••

Use the identification number to register your MicroLogic X control unit through mySchneider app, the
customer care mobile application.
Registering your MicroLogic X control unit enables you to keep your records up to date and enables
traceability.

Control Unit Type


This code indicates the type of MicroLogic control unit:
 The number (for example, 6.0) defines the types of protection provided by the control unit.
 The letter (X) identifies the range of the control unit.

Internal Battery
The internal battery powers the trip cause LEDs and the main diagnostic functions in the absence of any
other power supply.

VPS Voltage Power Supply Module


The VPS module provides an internal voltage supply to the MicroLogic X control unit.
The VPS module is optional for MicroLogic 2.0 X, 5.0 X, and 6.0 X. It is installed as standard on
MicroLogic 7.0 X.

Sensor Plug
The protection ranges depend on the rated current In, defined by the sensor plug present below the
MicroLogic X control unit.

28 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Description

Go2SE Landing Page

Presentation
When the QR code on the front face of a MasterPact MTZ device is scanned with a smartphone running a
QR code reader and connected to the Internet, the Go2SE landing page is displayed.
The landing page displays information about the device and a list of menus.

Landing Page Description


The landing page is accessible from Android and iOS smartphones. It displays the same list of menus with
slight differences in presentation.
The following example shows the landing page displayed on an Android smartphone:

A Commercial reference of MicroLogic X control unit


B Type of MicroLogic X control unit
C Landing page menus. See the following menu descriptions
for details.
D Downloadable applications

Characteristics
Selecting this menu gives access to a product datasheet with detailed information about the MicroLogic X
control unit.

Documentation
Selecting this menu gives access to a sub-menu with the following options:
 Asset Life Cycle Documents: gives access to Safe Repository.
Safe Repository is a web service allowing documentation linked to assets to be consulted, stored, and
shared in a Schneider Electric environment. Access to Safe Repository is restricted to authorized users.
Safe Repository gives access to the bill of materials of the MasterPact MTZ circuit breaker.
 Technical Guidance at Glance: gives access to the MasterPact MTZ technical publications, including:
 MasterPact MTZ - MicroLogic X Control Unit - User Guide
 MasterPact MTZ1 - Circuit Breakers and Switch-Disconnectors - User Guide
 MasterPact MTZ2/MTZ3 - Circuit Breakers and Switch-Disconnectors - User Guide
 All the instruction sheets for MasterPact MTZ devices and MicroLogic X control units
 Product Documentation: gives access to the MicroLogic X technical publications

DOCA0101EN-04 07/2020 29
MasterPact MTZ2/MTZ3 Description

EcoStruxure Facility Expert App


Selecting this application gives access to the EcoStruxure Facility Expert mobile application that can be
downloaded on Android and iOS smartphones. For smartphone compatibility, check on your application
store.
EcoStruxure Facility Expert optimizes operations and maintenance, helping to ensure business continuity,
and provides insights to service providers or facility managers.
EcoStruxure Facility Expert is a real-time collaborative technology available on mobile devices and PCs
that enables managers and maintenance personnel to be connected with facilities and equipment.
Information exchange between users is simple and fast.
The QR code on MasterPact MTZ devices enables managers and maintenance personnel to access the
following automatic downloads:
 MasterPact MTZ device identifier.
 Technical documentation.
 The maintenance plan for the MasterPact MTZ device.

EcoStruxure Facility Expert enables managers and maintenance personnel to access the maintenance
plan for MasterPact MTZ devices.
EcoStruxure Facility Expert helps maintenance personnel to diagnose issues remotely and manage
maintenance efficiently by:
 Providing relevant information on critical assets.
 Sending immediate state of the equipment and detailed information helping for diagnostics.

EcoStruxure Power Device App


Selecting this application gives access to the EcoStruxure Power Device app that can be downloaded and
installed on Android and iOS smartphones. For smartphone compatibility, check on your application store.

mySchneider App
Selecting this application gives access to the Schneider Electric customer care mobile application
mySchneider app that can be downloaded on Android and iOS smartphones. For smartphone
compatibility, check on your application store. The customer care application offers self-service
instructions and easy access to expert support and information.

30 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Description

Operating Conditions

Introduction
MasterPact MTZ devices are designed and tested for operation in industrial atmospheres. It is
recommended that equipment is cooled or heated to the proper operating temperature and kept free of
excessive vibration and dust.

Ambient Temperature
MasterPact MTZ devices can operate under the following temperature conditions:
 Electrical and mechanical characteristics specified for an ambient temperature of -25 °C to +70 °C .
 Circuit-breaker closing specified down to -35 °C by manual operation with closing pushbutton.

Storage conditions are as follows:


 -40 °C to +85 °C for the device without the control unit.
 -25 °C to +85 °C for the control unit.

Extreme Atmospheric Conditions


MasterPact MTZ devices have successfully passed tests for extreme atmospheric conditions, defined by
the following standards:

Standard Title
IEC 60068-2-1 Dry cold, at -40 °C
IEC 60068-2-2 Dry heat, at +85 °C
IEC 60068-2-30 Damp heat (temperature +55 °C, relative humidity 95%)
IEC 60068-2-52 level 2 Salt mist

Industrial Environments
MasterPact MTZ devices can operate in the industrial environments defined by IEC 60947 (pollution
degree up to 3).
It is advisable to check that devices are installed in suitably cooled switchboards without excessive dust.

Conditions Standard
Corrosive industrial atmospheres Category 3C3 compliant with IEC 60721-3-3
Sea salts 0.8 to 8 mg/m² day average over the year Compliant with IEC 60721-2-5
Mechanically active substances Category 3S3 compliant with IEC 60721-3-3

Beyond these conditions, MasterPact MTZ devices must be installed inside switchboards with an IP rating
equal to or greater than IP54.

Vibration
MasterPact MTZ devices have successfully passed tests for the following vibration levels, in compliance
with IEC 60068-2-6 and IEC 60068-2-27:
 2 Hz to 13.2 Hz: amplitude +/- 1 mm.
 13.2 Hz to 100 Hz: constant acceleration of 0.7 g.

Vibration testing to these levels is required by merchant marine inspection organizations (for example,
Veritas, Lloyd’s).
MasterPact MTZ devices have also been successfully tested according to:
 Annex Q - IEC 60947-1: Special tests – damp heat, salt mist, vibration and shock
 IEC 60947-1 - Category D: Environment subject to temperature, humidity and vibration

DOCA0101EN-04 07/2020 31
MasterPact MTZ2/MTZ3 Description

Altitude
MasterPact MTZ devices are designed and tested to operate at altitudes below 2,000 m.
At altitudes above 2,000 m, the characteristics of the ambient air (electrical resistance, cooling capacity)
lower product characteristics as follows:

Characteristics Altitude
2,000 m 3,000 m 4,000 m 5,000 m
Impulse withstand voltage Uimp (kV) 12 11 10 8
Rated insulation voltage (Ui) (V) 1,000 900 780 700
Maximum rated operational MasterPact MTZ2/MTZ3 690 690 630 560
voltage 50/60 Hz Ue (V) except H10
MasterPact MTZ2/MTZ3 H10 1,000 890 795 700
Rated current (A) at 40 °C 1 x In 0.99 x In 0.96 x In 0.94 x In

NOTE: Intermediate values can be obtained by interpolation.

Electromagnetic Disturbances
MasterPact MTZ devices have protection against:
 Overvoltages caused by devices that generate electromagnetic disturbance.
 Overvoltages caused by atmospheric disturbance or by a distribution-system outage (for example, a
lighting system failure).
 Devices emitting radio waves (for example, radio transmitters, walkie-talkies, or radar).
 Electrostatic discharge produced by users.

MasterPact MTZ devices have successfully passed the electromagnetic-compatibility tests (EMC) defined
by the following international standards:
 IEC 60947-2, appendix F.
 IEC 60947-2, appendix B (control units with earth-leakage function).

The devices have passed the above tests and therefore:


 No nuisance tripping occurs.
 Tripping times are respected.

32 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3
MasterPact MTZ2/MTZ3 Normal Operation
DOCA0101EN-04 07/2020

Chapter 2
MasterPact MTZ2/MTZ3 Normal Operation

MasterPact MTZ2/MTZ3 Normal Operation

What Is in This Chapter?


This chapter contains the following sections:
Section Topic Page
2.1 Device Operating Actions 34
2.2 Drawout Device Racking Actions 60
2.3 Device Locking Actions 77
2.4 Device Interlocking Actions 93

DOCA0101EN-04 07/2020 33
MasterPact MTZ2/MTZ3 Normal Operation

Section 2.1
Device Operating Actions

Device Operating Actions

What Is in This Section?


This section contains the following topics:
Topic Page
Operating the Device 35
Control Modes 39
Opening the Device 44
Closing the Device 47
Resetting the Circuit Breaker 50
Engaging the ERMS Function 51
Operating Accessories 53

34 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

Operating the Device

Device Status
The indicators on the front of the device show the following information:
 Reset button:
 In: the device is closed or open voluntarily (not tripped)
 Out: the device has tripped

 Position indicator of main contacts: ON or OFF.


 Closing spring and ready-to-close indicator. The state can be one of the following:
 Discharged (no energy to close the circuit breaker)
 Charged not ready-to-close
 Charged ready-to-close

A Reset button
B Position indicator of main contacts
C Closing spring and ready-to-close indicator

The combination of both indicators gives the device status:

Position indicator of main Closing spring and ready- Device status description
contacts to-close indicator
Device is off (main contacts are open) and closing spring is
discharged.

Device is off (main contacts are open) and closing spring is


charged. The device is not ready-to-close because at least
one of the following conditions is true:
 The device has tripped and must be reset.
 The MX opening voltage release is energized.
 The MN undervoltage release is not energized.
 The device is mechanically locked in the open position
by using padlock or keylock or by using an interlocking
system.
Device is off (main contacts are open) and closing spring is
charged.
The device is ready-to-close.

Device is on (main contacts are closed) and closing spring


is discharged.

Device is on (main contacts are closed) and closing spring


is charged.
The device is not ready-to-close because it is already
closed.

DOCA0101EN-04 07/2020 35
MasterPact MTZ2/MTZ3 Normal Operation

Device Indication Contacts


The position of the device main contacts is indicated by OF indication contacts.

Name Contact Position of indicators and contacts


number
Device status – ON OFF Tripped (by
MicroLogic X control
unit)
Position indicator of –
main contacts

Main contact position – Closed Open Open


Reset button position – IN IN OUT
OF indication contact 1–2 Open Closed Closed
position 1–4 Closed Open Open
SDE indication contact 1–2 Closed Closed Open
position
1–4 Open Open Closed

Anti-Pumping Function
MasterPact MTZ devices provide a mechanical anti-pumping function. In the event of simultaneous
maintained opening and closing orders, the standard mechanism blocks the main contacts in the open
position. After a trip due to an electrical fault or intentional opening using the manual or electrical controls,
the closing order must first be discontinued, then reactivated to close the circuit breaker. This prevents a
cycle of closing and opening.
When remote operation features are used, allow at least four seconds for the MCH gear motor to charge
the device closing spring completely before the XF closing voltage release is actuated.
To prevent the device from closing prematurely, the PF ready-to-close contact can be series connected
with the XF closing voltage release.

Charging the Closing Spring


The closing spring must be charged with sufficient energy to close the MasterPact MTZ:
 Manual charge: Charge the mechanism by pulling the spring charging handle down seven times.

 Automatic charge: If the optional MCH gear motor is installed, the spring is automatically charged after
closing.
NOTE: For drawout devices fitted with the optional DAE automatic spring-discharge before device removal
(see page 105), the closing spring is discharged when the device is moved from disconnected to
withdrawn position.

36 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

Manual Operation Cycle with the Spring Charging Handle


The following image shows an Open/Close/Open (OCO) cycle for manually charged devices without MCH
gear motor:

DOCA0101EN-04 07/2020 37
MasterPact MTZ2/MTZ3 Normal Operation

Electrical Operation Cycle with an MCH Gear Motor


The following image shows an Open/Close/Open (OCO) cycle for electrically charged devices using an
MCH gear motor:

38 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

Control Modes

Presentation
The circuit breaker control mode is a MicroLogic X setting which defines the means to control the opening
and closing functions of the circuit breaker.
Two control modes are available: Manual and Auto.
Manual control mode only accepts orders made using one of the following:
 The mechanical buttons on the front of the circuit breaker.
 The external pushbutton connected to the MN/MX/XF voltage releases.
 The BPFE electrical closing pushbutton.

Auto control mode has two settings: Local or Remote. All orders accepted in Manual control mode are
accepted in Auto control mode, as well as orders from local or remote communication as follows:
 Auto Local: the operator needs to be close to the circuit breaker to establish communication and only
orders sent from a local source through communication are accepted:
 EcoStruxure Power Commission software through USB connection
 EcoStruxure Power Device app with MasterPact Operation Assistant Digital Module through
Bluetooth or USB OTG connection
 Auto Remote: the operator does not need to be next to the circuit breaker to establish communication
and orders are accepted only when sent from a remote source through the communication network.
NOTE: EcoStruxure Power Commission software connected through the communication network can be
used to send control orders to the circuit breaker.
The control mode factory setting is Auto Remote.
NOTE: The switch-disconnector control mode corresponds to the Manual control mode of circuit breakers.
To operate a switch-disconnector through communication, it is possible to use an IO module. Refer to
DOCA0055EN Enerlin'X IO - Input/Output Application Module for One IEC Circuit Breaker - User Guide.

Operation According to Control Mode Configured


The following table summarizes the opening and closing operations available, depending on the control
mode configured:

Control mode Type of order and delivery method


Mechanical Electrical Through communication
Pushbutton BPFE Point to IO EcoStruxure Power EcoStruxure Power Communication IFE/EIFE
point module Commission software (1) Device app + network Webpages
(voltage MasterPact
release) Operation Assistant
Digital Module(2)
Manual ✔ ✔ ✔ – – – – –
Auto: Local ✔ ✔ ✔ ✔(3) ✔ ✔ – –

Auto: Remote ✔ ✔ ✔ ✔ (3) – – ✔ ✔


(1) Through USB
(2) Through Bluetooth or USB OTG
(3) According to IO input mode setting

DOCA0101EN-04 07/2020 39
MasterPact MTZ2/MTZ3 Normal Operation

Operation in Manual Control Mode

A MicroLogic X control unit


B ULP port module
C EIFE embedded Ethernet interface
D Circuit breaker mechanism

Opening and closing operations available in Manual control mode:


 0: mechanical opening pushbutton
 1: mechanical closing pushbutton
 BPFE: electrical closing pushbutton
 External pushbuttons wired by customer, and connected to:
 XF: standard or communicating and diagnostic closing voltage release
 MX: standard or communicating and diagnostic opening voltage release
 MN: standard or diagnostic undervoltage release

40 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

Operation in Auto: Local Mode

A MicroLogic X control unit


B ULP port module
C EIFE embedded Ethernet interface
D Circuit breaker mechanism
E IO input/output application module

Opening and closing operations available in Auto: Local mode:


 0: mechanical opening pushbutton
 1: mechanical closing pushbutton
 BPFE: electrical closing pushbutton
 External pushbuttons wired by customer, and connected to:
 XF: communicating and diagnostic closing voltage release
 MX: communicating and diagnostic opening voltage release
 MN: standard or diagnostic undervoltage release

 IO: with the Breaker Operation predefined application of the IO module set to local control mode
 EcoStruxure Power Commission software: command sent through USB connection
 EcoStruxure Power Device app with MasterPact Operation Assistant Digital Module:
 Through Bluetooth low energy wireless communication
 Through USB OTG connection

DOCA0101EN-04 07/2020 41
MasterPact MTZ2/MTZ3 Normal Operation

Operation in Auto: Remote Mode

A MicroLogic X control unit


B ULP port module
C EIFE embedded Ethernet interface
D Circuit breaker mechanism
E IO input/output application module

Opening and closing operations available in Auto: Remote mode:


 0: mechanical opening pushbutton
 1: mechanical closing pushbutton
 BPFE: electrical closing pushbutton
 External pushbuttons wired by customer, and connected to:
 XF: communicating and diagnostic closing voltage release
 MX: communicating and diagnostic opening voltage release
 MN: standard or diagnostic undervoltage release

 IO: with the Breaker Operation predefined application of the IO module set to remote control mode
 Communication: remote command through IFE, EIFE, or IFM interface.

Setting the Control Mode


The Auto or Manual control mode can be set as follows:
 On the MicroLogic X display screen, at Home → Configuration → Communication → Control Mode →
Mode.
 With the EcoStruxure Power Device app through Bluetooth or USB OTG connection.

The Local or Remote mode can be set as follows:


 When the IO module is used with the Breaker Operation predefined application, the local or remote
mode is defined only by the control mode selector switch wired on the digital input I1 of the IO module.
 When the IO module is not used with the Breaker Operation predefined application, the local or remote
mode can be set as follows:
 With EcoStruxure Power Commission software through USB connection
 With the EcoStruxure Power Device app through Bluetooth or USB OTG connection.

NOTE:
 The Local or Remote mode cannot be set on the MicroLogic X display screen.
 When Auto control mode is set, the control mode is Auto Local or Auto Remote, depending on the last
setting.

42 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

Displaying the Control Mode


The control mode (Manual, Auto Local, or Auto Remote) is displayed as follows:
 On the MicroLogic X display screen, at Home → Configuration → Communication → Control Mode →
Mode
 With EcoStruxure Power Commission software through USB connection
 With the EcoStruxure Power Device app through Bluetooth or USB OTG connection
 On the IFE/EIFE webpages
 By a remote controller using the communication network.

Predefined Events
Changing the control mode settings generates the following events:

Code Event History Severity


0x1002 (4098) Manual mode enabled Operation Low
0x1004 (4100) Local mode enabled Operation Low
0x0D0D (3341) Config. error IO and CU - Local/Remote mode Configuration Medium

Recommended Actions

Code Event Recommended actions


0x0D0D (3341) Config. error IO and CU - Local/Remote mode Correct the configuration error with EcoStruxure
Power Commission:
 If you want the L/R mode to be controlled by
the IO module, connect an IO module with
L/R mode assignment.
 If you do not want the L/R mode to be
controlled by the IO module, connect an IO
module without L/R mode assignment.

DOCA0101EN-04 07/2020 43
MasterPact MTZ2/MTZ3 Normal Operation

Opening the Device

Opening Conditions
To open the device, the device must be closed (I).
NOTE: An opening order always takes priority over a closing order.

Opening the Device


The following tables present the different ways to open the device in the different control modes available.
The device can be opened in the following ways in all control modes:

Opening type Control Accessories Opening action


mode
Mechanical Manual, – Press the opening
Auto: pushbutton on the front
Local, or of the device.
Auto: This opening action is
Remote possible at any time.

Automatic Manual, MN undervoltage The MN undervoltage release opens the device


Auto: release, with or without automatically in the case of voltage drop.
Local, or MN delay unit
Auto:
Remote
By external Manual,  External pushbutton Press the external pushbutton which is connected to the MX
pushbutton Auto: wired by customer opening voltage release or to the MN undervoltage release
Local, or  One of the following via the customer terminal block.
Auto: accessories: When the MN undervoltage release is connected to the MN
Remote  MX standard or delay unit, the device opens with the corresponding time
communicating delay.
opening voltage
release
 MN undervoltage
release, with or
without MN delay
unit

44 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

In addition, the circuit breaker can be opened in the following ways when Auto control mode is configured.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
 Do not operate the circuit breaker without confirming that doing so will not create a hazardous
situation.
 Do not allow any person to work on the electrical network without physically validating the successful
execution of the local or remote software actions for opening the circuit breaker or switching off the
electrical circuit.
Failure to follow these instructions will result in death or serious injury.

Opening type Control mode Accessories Opening action


Through IO module Auto: Local or  MX communicating Open the circuit breaker by using the
Auto: Remote opening voltage release predefined application 2 Breaker
 Isolation module Operation of the IO module.
 ULP port module  When the circuit breaker is set to
 IO module local control mode by the IO
module, the command to open is
issued from local pushbuttons
wired on digital inputs.
 When the circuit breaker is set to
remote control mode by the IO
module, the command to open is
issued from remote PLC outputs
wired on digital inputs.
Refer to DOCA0055EN Enerlin'X IO -
Input/Output Application Module for
One IEC Circuit Breaker - User
Guide.
Through EcoStruxure Auto: Local  MX communicating Send a command to open the circuit
Power Commission opening voltage release breaker from EcoStruxure Power
software  Isolation module Commission software running on a
PC connected locally to the device
through the mini USB port on the
MicroLogic X control unit.
This opening action is password-
protected.
Refer to EcoStruxure Power
Commission Online Help.
Through EcoStruxure Auto: Local  MX communicating Send a command to open the circuit
Power Device app opening voltage release breaker from the EcoStruxure Power
 Isolation module Device app with MasterPact
 MasterPact Operation Operation Assistant Digital Module,
Assistant Digital Module through Bluetooth wireless
communication or USB OTG
connection. The opening action is
password-protected.
Through Modbus Auto: Remote  MX communicating Send a command to open the circuit
communication opening voltage release breaker through the Modbus
 Isolation module communication network.
 ULP port module This opening action is password-
 IFE, EIFE, or IFM interface, protected.
or IFE server Refer to DOCA0105EN
MasterPact MTZ - Modbus
Communication Guide.
NOTE: EcoStruxure Power
Commission software running on a
PC connected to the device through
the communication network can be
used to send commands to open.

DOCA0101EN-04 07/2020 45
MasterPact MTZ2/MTZ3 Normal Operation

Opening type Control mode Accessories Opening action


Through IEC 61850 Auto: Remote  MX communicating Send a command to open the circuit
communication opening voltage release breaker through the IEC 61850
 Isolation module communication network.
 ULP port module This opening action is password-
 IFE or EIFE interface protected.
 IEC 61850 for MasterPact Refer to DOCA0162EN MasterPact
MTZ Digital Module MTZ - IEC 61850 Communication
Guide.
Through IFE/EIFE Auto: Remote  MX communicating Send a command to open the circuit
webpages opening voltage release breaker from the IFE/EIFE control
 Isolation module webpage.
 ULP port module This opening action is password-
 IFE or EIFE interface, or protected.
IFE server Refer to the relevant document:
 DOCA0084EN Enerlin'X IFE -
Ethernet Switchboard Server -
User Guide
 DOCA0142EN Enerlin'X IFE -
Ethernet Interface for One IEC
Circuit Breaker - User Guide
 DOCA0106EN Enerlin'X EIFE -
Embedded Ethernet Interface for
One MasterPact MTZ Drawout
Circuit Breaker - User Guide

If the device does not open, refer to the troubleshooting chapter (see page 142).

46 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

Closing the Device

Closing Conditions
To close the device, the following conditions must be met:
 Device is open (O).
 Closing spring is charged.
 The device is ready to close, OK is displayed.

NOTE: An opening order always takes priority over a closing order. The device cannot be closed while an
opening order is being received. If OK is crossed-out on the ready-to-close indicator, an order to open is
being received (either electrically or mechanically) and must be ended before OK can be displayed.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not re-close the device on an electrical fault.
First inspect and, if necessary, repair the downstream equipment.
Failure to follow these instructions will result in death or serious injury.

Closing the Device


The following tables present the different ways to close the device in the different control modes available.
The device can be closed in the following ways in all control modes:

Closing type Control Accessories Closing action


mode
Mechanical Manual, – Press the closing
Auto: Local, pushbutton on the front of
or Auto: the device.
Remote The closing action is
possible when the closing
conditions are met.

Electrical with Manual,  BPFE electrical Press the BPFE electrical


BPFE Auto: Local, closing pushbutton closing pushbutton,
or Auto:  XF communicating mounted on the front cover.
Remote closing voltage The closing action takes
release into account internal closing
 Isolation module conditions of the device and
the external conditions that
are part of the control and
monitoring system of the
installation.
External Manual,  External pushbutton Press the external pushbutton, which is connected to the XF
pushbutton Auto: Local, wired by customer closing voltage release through the customer terminal block.
or Auto:  XF standard or
Remote communicating
closing voltage
release
 Isolation module
 MCH gear motor

DOCA0101EN-04 07/2020 47
MasterPact MTZ2/MTZ3 Normal Operation

In addition, the circuit breaker can be closed in the following ways when Auto control mode is configured.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
 Do not operate the circuit breaker without confirming that doing so will not create a hazardous
situation.
 Do not allow any person to work on the electrical network without physically validating the successful
execution of the local or remote software actions for closing the circuit breaker or switching on the
electrical circuit.
Failure to follow these instructions will result in death or serious injury.

Closing type Control Accessories Closing action


mode
Through IO module Auto: Local  XF communicating Close the circuit breaker by using the predefined
or Auto: closing voltage application 2 Breaker Operation of the IO module:
Remote release  When the circuit breaker is set to local control mode by
 Isolation module the IO module, the command to close is issued from
 MCH gear motor local pushbuttons wired on digital inputs.
 ULP port module  When the circuit breaker is set to remote control mode
 IO module by the IO module, the command to close is issued
from remote PLC outputs wired on digital inputs.
Refer to DOCA0055EN Enerlin'X IO - Input/Output
Application Module for One IEC Circuit Breaker - User
Guide.
Through Auto: Local  XF communicating Send a command to close the circuit breaker from
EcoStruxure Power closing voltage EcoStruxure Power Commission software running on a
Commission release PC connected locally to the circuit breaker through the
software  Isolation module mini USB port on the MicroLogic X control unit.
 MCH gear motor The closing action is password-protected.
Refer to EcoStruxure Power Commission Online Help.
Through Auto: Local  XF communicating Send a command to close the circuit breaker from the
EcoStruxure Power closing voltage EcoStruxure Power Device app with MasterPact
Device app release Operation Assistant Digital Module, through Bluetooth
 Isolation module wireless communication or USB OTG connection.
 MCH gear motor The closing action is password-protected.
 MasterPact
Operation Assistant
Digital Module
Through Modbus Auto:  XF communicating Send a command to close the circuit breaker through the
communication Remote closing voltage Modbus communication network.
release The closing action is password-protected.
 Isolation module Refer to DOCA0105EN MasterPact MTZ - Modbus
 MCH gear motor Communication Guide.
 ULP port module NOTE: EcoStruxure Power Commission software
 IFE, EIFE, or IFM running on a PC connected to the circuit breaker through
interface, or IFE the communication network can be used to send
server commands to close.

48 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

Closing type Control Accessories Closing action


mode
Through Auto:  XF communicating Send a command to close the circuit breaker through the
IEC 61850 Remote closing voltage IEC 61850 communication network.
communication release This closing action is password-protected.
 Isolation module Refer to DOCA0162EN MasterPact MTZ - IEC 61850
 MCH gear motor Communication Guide.
 ULP port module
 IFE or EIFE
interface
 IEC 61850 for
MasterPact MTZ
Digital Module
Through IFE/EIFE Auto:  XF communicating Send a command to close the circuit breaker from the
webpages Remote closing voltage IFE/EIFE control webpage.
release The closing action is password-protected.
 Isolation module Refer to the relevant document:
 MCH gear motor  DOCA0084EN Enerlin'X IFE - Ethernet Switchboard
 ULP port module Server - User Guide
 IFE or EIFE  DOCA0142EN Enerlin'X IFE - Ethernet Interface for
interface, or IFE One IEC Circuit Breaker - User Guide
server  DOCA0106EN Enerlin'X EIFE - Embedded Ethernet
Interface for One MasterPact MTZ Drawout Circuit
Breaker - User Guide

If the device does not close, refer to the troubleshooting chapter (see page 142).

Inhibiting the Closing Function


The closing function can be inhibited by sending a command through:
 The communication network or EcoStruxure Power Commission software
 The IO module

NOTE: Using EcoStruxure Power Commission software, you can determine whether the closing inhibition
can be controlled using the IO module. For more information, refer to EcoStruxure Power Commission
Online Help.

WARNING
RESTRICTED CLOSING INHIBITION
Do not use the inhibit closing order to lock the circuit breaker in open position.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

The inhibit close order inhibits only the closing orders allowed in Auto control mode. The closing orders
issued from the mechanical closing pushbutton or BPFE, or from the pushbutton directly connected to the
XF voltage release are not inhibited.

DOCA0101EN-04 07/2020 49
MasterPact MTZ2/MTZ3 Normal Operation

Resetting the Circuit Breaker

Resetting Conditions
After a trip, the circuit breaker must be reset before closing it.
Resetting is possible in all control modes.

Resetting the Circuit Breaker


The circuit breaker can be reset in different ways, according to the circuit breaker configuration and its
accessories:

Type of resetting Accessories Resetting action


Mechanical with – Push in the blue fault-trip reset
the blue fault-trip button on the front of the circuit
reset button breaker. This resetting action is
always possible. Pushing in the
blue fault-trip reset button
resets the SDE fault-trip
indication contact, and allows
the circuit breaker to be closed.

Automatic (RAR  XF communicating or After a trip, RAR automatic reset allows the circuit breaker to be
automatic reset standard closing voltage closed without the blue fault-trip reset button being pushed in. The
option) release use of XF closing voltage release is compulsory with this option.
 Isolation module The mechanical indicator and the SDE fault-trip indication contact
 MCH gear motor remain in detected fault position.
To reset the SDE fault-trip indication contact and the mechanical
indicator, push in the blue fault-trip reset button.
Electrical with  External pushbutton Press the external pushbutton which is connected to the RES
external wired by customer electrical remote reset via the customer terminal block.
pushbutton  RES electrical remote The use of XF closing voltage release is compulsory with this option.
reset The RES electrical remote reset resets the SDE fault-trip indication
 XF communicating or contact and the mechanical indicator, and allows the circuit breaker
standard closing voltage to be closed.
release NOTE: The RES electrical remote reset is not compatible with the
 Isolation module SDE2 option.
 MCH gear motor

50 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

Engaging the ERMS Function

Presentation
Engage the ERMS function to reduce protection settings so that the circuit breaker trips as soon as
possible when an internal arc fault occurs. Minimizing the time between fault and trip helps to reduce the
risk of injury when qualified electrical personnel are near energized equipment.

Conditions for Engaging the ERMS Function


The ERMS function is available when the Energy Reduction Maintenance Settings Digital Module is
purchased and installed on the MicroLogic X control unit.

Operating Principle

The ERMS function can be engaged as follows:


 With the EcoStruxure Power Device app
(password-protected).
There is a digital lock between a smartphone
running the EcoStruxure Power Device app and
the MicroLogic X control unit.
 By using an external selector switch connected
to the optional ESM ERMS switch module.
The ESM module is installed in the circuit
breaker and is connected to an external selector
switch, which can be padlocked. The ERMS
function is engaged by turning the external
selector switch.

The ERMS function can be engaged with both the EcoStruxure Power Device app (password-protected)
and an external selector switch.
The ERMS function must be disengaged by the interface that engaged it:
 If it is engaged on a smartphone, it must be disengaged by the same smartphone.
 If it is engaged by the external ERMS switch connected to the ESM module, it must be disengaged by
the ERMS switch.
 If it is engaged by both smartphone and ERMS switch, it must be disengaged by both smartphone and
ERMS switch.

While the ERMS function is engaged:


 A blue ERMS LED (A) is lit on the front face of the MicroLogic X
control unit
 Quick View scrolling is interrupted and the ERMS engaged message
is displayed with a blue backlight
 All screens, except pop-up messages, are displayed with a blue
backlight

For more information, refer to DOCA0102EN MasterPact MTZ - MicroLogic X Control Unit - User Guide.

DOCA0101EN-04 07/2020 51
MasterPact MTZ2/MTZ3 Normal Operation

Engaging the ERMS Function

NOTICE
HAZARD OF LOSS OF POWER
Ensure that the ERMS protection settings are properly configured prior to engagement.
Failure to follow these instructions can result in loss of service due to power loss.

The ERMS can be engaged in different ways, according to the circuit breaker configuration and its
accessories:

Type Accessories Action


Through EcoStruxure Power Device – Send a command from the
app EcoStruxure Power Device app to
engage the ERMS function, through
Bluetooth wireless communication or
USB OTG connection. The action is
password-protected.
Through an external selector switch  ESM ERMS switch module Turn the external selector switch to
connected to the ESM module  External selector switch the Engaged position

Disengaging the ERMS Function

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Prior to disengaging ERMS:
 Carefully inspect your work area, and remove any tools and objects left inside the equipment.
 Ensure that all personnel are away from the equipment, and devices, doors, and covers are in place.

Failure to follow these instructions will result in death or serious injury.

A digital lock function establishes a digital lock between a smartphone running the EcoStruxure Power
Device app and the MicroLogic X control unit when ERMS is engaged by the smartphone. The digital lock
function ensures that when the ERMS function is engaged by a smartphone, it must be disengaged by the
same smartphone.
The way to disengage the ERMS function depends on how it was engaged:

Type Accessories Action


Through EcoStruxure Power Device – Disengage the ERMS function on the
app same smartphone that engaged it
Through an external selector switch  ESM ERMS switch module Turn the external selector switch to
 External selector switch the Disengaged position
Through EcoStruxure Power Device  ESM ERMS switch module  Disengage the ERMS function on
app and an external selector switch  External selector switch the same smartphone that
engaged it
 Turn the external selector switch to
the Disengaged position

52 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

Operating Accessories

XF, MX, and MN Voltage Releases


XF, MX, and MN voltage releases are optional accessories mounted inside the device. They can be of
standard type or diagnostic and communicating type (standard or with diagnostic function for MN
undervoltage release).
The standard voltage releases are designed to receive either pulse-type or maintained voltage operating
orders.

XF Closing Voltage Release (Standard or With Diagnostic and Communicating Function)


The XF closing voltage release closes the circuit breaker instantaneously when powered if the spring
mechanism is charged. The minimum duration of the pulse operating order must be 200 ms.

For information on installation, consult the instruction sheet on the Schneider Electric website:
 XF standard closing voltage release: NVE40749
 XF communicating closing voltage release: NVE40766

MX Opening Voltage Release (Standard or With Diagnostic and Communicating Function)


The MX opening voltage release opens the circuit breaker instantaneously when powered. The minimum
duration of the pulse operating order must be 200 ms. The MX standard opening voltage release locks the
circuit breaker in OFF position if the command is maintained.

For information on installation, consult the instruction sheet on the Schneider Electric website:
 MX standard opening voltage release: NVE40749
 MX communicating opening voltage release: NVE40766

DOCA0101EN-04 07/2020 53
MasterPact MTZ2/MTZ3 Normal Operation

MN Undervoltage Release (Standard or With Diagnostic Function)


The MN undervoltage release instantaneously opens the circuit breaker when its supply voltage drops to
a value between 35% and 70% of its rated voltage. If there is no supply to the release, it is impossible to
close the circuit breaker, either manually or electrically. Any attempt to close the circuit breaker has no
effect on the main contacts. Circuit breaker closing is enabled again when the supply voltage of the release
returns to 85% of its rated value.

For information on installation, consult the instruction sheet on the Schneider Electric website:
 MN standard undervoltage release: NVE40749
 MN undervoltage release with diagnostic function: NVE40766

Isolation Module for Communicating Voltage Releases


The internal isolation module for MicroLogic X control units provides double insulation in compliance with
IEC 60664-1 (up to 12 kV). It also provides insulation between the XF, MX, and MN types of voltage
release.

For information on installation, consult the instruction sheet on the Schneider Electric website: NVE40748.

BPFE Electrical Closing Pushbutton


This is an optional accessory that is mounted on the front cover of the device.
The BPFE electrical closing pushbutton carries out electrical closing of the circuit breaker. It takes into
account the internal closing conditions of the device and the external conditions that are part of the control
and monitoring system of the installation. It connects to the XF standard or communicating closing voltage
release.
If BPFE is being used, it is recommended to lock access to the closing pushbutton using the VBP
accessory because the closing pushbutton does not take into account internal and external conditions.

For information on installation, consult the instruction sheet on the Schneider Electric website: NVE40773.

54 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

PF Ready-to-close Contact
This is an optional accessory that is mounted inside the device.
The PF ready-to-close contact delivers remotely, the indication delivered locally by the ready-to-close
indicator.
It consists of a changeover contact indicating remotely that the circuit breaker is ready to close, that is:
 The circuit breaker is in the open position.
 The spring mechanism is charged.
 There is no maintained opening order.

For information on installation, consult the instruction sheet on the Schneider Electric website: NVE35466.

MCH Gear Motor


This is an optional accessory that is mounted inside the device.
The MCH gear motor automatically charges the spring mechanism when the device is closed, allowing
instantaneous closing of the device following opening.

For information on installation, consult the instruction sheet on the Schneider Electric website: NVE35483.

RES Electrical Remote Reset


This is an optional accessory that is mounted inside the device.
Following tripping, this function resets the SDE fault-trip indication contact, and the mechanical indicator
and enables circuit breaker closing.
The use of an XF closing release is compulsory with this option.
The RES electrical remote reset is not compatible with the SDE2 additional fault-trip indication contact
because they are installed in the same physical place.

For information on installation, consult the instruction sheet on the Schneider Electric website: NVE35503.

DOCA0101EN-04 07/2020 55
MasterPact MTZ2/MTZ3 Normal Operation

ESM ERMS Switch Module


This is an optional accessory that is mounted inside the device.
The ESM ERMS switch module is used to engage ERMS protection settings.The ESM module works in
conjunction with the ERMS Digital Module, which must also be installed.
The ESM ERMS switch module is not compatible with M2C programmable contacts because they are
installed in the same physical place.

For installation of the ESM ERMS switch module, contact your Schneider Electric field service
representative.

KMT Grounding Kit


This is an optional accessory that is mounted inside the device.
This option allows the device mechanism to be grounded when the front cover is removed. The grounding
is made through the chassis for the drawout version and through the mounting side plate for the fixed
version.

For information on installation, consult the instruction sheet on the Schneider Electric website: NVE35480.

CDM Mechanical Operation Counter


This is an optional accessory that is mounted inside the device.
The CDM mechanical operation counter counts the number of operating cycles and is visible on the front
panel. It is compatible with manual and electrical control functions.
This option is compulsory for all source-changeover systems.

For information on installation, consult the instruction sheet on the Schneider Electric website: NVE35485.

56 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

ULP Port Module


The ULP port module is optional on the fixed circuit breaker and standard on the drawout circuit breaker.
It is mounted with the terminal blocks of the circuit breaker.
The ULP port module:
 Supplies the MicroLogic X control unit.
 Integrates the ULP termination.
 Allows the connection to external ULP modules, like the IO module or the IFE Ethernet interface.

Fixed circuit breaker: Drawout circuit breaker:

For information on installation, consult the instruction sheet on the Schneider Electric website:
 ULP port module for fixed MasterPact MTZ2/MTZ3: NVE40791
 ULP port module for drawout MasterPact MTZ2/MTZ3: NVE40797

EIFE Embedded Ethernet Interface


This is an optional accessory that is mounted on the chassis of the drawout circuit breaker.
The EIFE embedded Ethernet interface enables drawout MasterPact MTZ circuit breakers to be connected
to an Ethernet network with the following protocols:
 Modbus TCP/IP
 IEC 61850 with addition of the IEC 61850 for MasterPact MTZ Digital Module

It provides digital access to all the data delivered by the MicroLogic X control unit. In addition, it monitors
the position of the device in the chassis: connected, test, and disconnected.

For information on installation, consult the instruction sheet on the Schneider Electric website: NVE23550.
For information on usage, refer to DOCA0106EN Enerlin'X EIFE - Embedded Ethernet Interface for One
MasterPact MTZ Drawout Circuit Breaker - User Guide.

DOCA0101EN-04 07/2020 57
MasterPact MTZ2/MTZ3 Normal Operation

IFE Ethernet Interface for One Circuit Breaker


The IFE Ethernet interface provides an Ethernet access to a single circuit breaker with the following
protocols:
 Modbus TCP/IP
 IEC 61850 with addition of the IEC 61850 for MasterPact MTZ Digital Module

The circuit breaker is connected to the IFE interface through the ULP port module and a prefabricated ULP
cord.

For information on installation, consult the instruction sheet on the Schneider Electric website: HRB49218.
For information on usage, refer to DOCA0142EN Enerlin'X IFE - Ethernet Interface for One IEC Circuit
Breaker - User Guide.

IFE Ethernet Switchboard Server


The IFE Ethernet switchboard server provides an Ethernet access to one or several circuit breakers with
the Modbus TCP/IP protocol. It allows the following communication architectures:
 One single circuit breaker connected to the IFE server through the ULP port module.
 Up to 11 circuit breakers through IFM Modbus-SL interfaces stacked to the IFE server.

For information on installation, consult the instruction sheet on the Schneider Electric website: HRB49218.
For information on usage, refer to DOCA0084EN Enerlin'X IFE - Ethernet Switchboard Server - User
Guide.

IFM Modbus-SL Interface for One Circuit Breaker


The IFM Modbus-SL interface provides an access to a Modbus serial line communication network to a
single device. The device is connected to the IFM interface through the ULP port module and a
prefabricated ULP cord.

For information on installation, consult the instruction sheet on the Schneider Electric website: NVE85393.

58 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

IO Input/Output Application Module for One Circuit Breaker


The IO input/output application module for one circuit breaker is one of the components of the ULP
architecture.
The IO application module enhances control and monitoring functions, thanks to its built-in applications. Its
resources are:
 Six digital inputs that are self-powered for either NO and NC dry contact or pulse counter.
 Three digital outputs that are bistable relay (5 A maximum).
 One analog input for Pt100 temperature sensor.

For information on installation, consult the instruction sheet on the Schneider Electric website: HRB49217.
For information on usage, refer to DOCA0055EN Enerlin'X IO - Input/Output Application Module for One
IEC Circuit Breaker - User Guide.

DOCA0101EN-04 07/2020 59
MasterPact MTZ2/MTZ3 Normal Operation

Section 2.2
Drawout Device Racking Actions

Drawout Device Racking Actions

What Is in This Section?


This section contains the following topics:
Topic Page
Drawout MasterPact MTZ2/MTZ3 Device Status 61
Disconnecting the Drawout Device 65
Connecting the Drawout Device 68
Removing the Drawout Device 71
Installing the Drawout Device in the Chassis 74

60 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

Drawout MasterPact MTZ2/MTZ3 Device Status

Drawout Device Handling Conditions


Connection or disconnection of the drawout device requires insertion of the racking handle. When
interlocks, padlocks, or an open door lock are in place, the racking handle cannot be inserted.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
 Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See
NFPA 70E or CSA Z462 or local equivalent.
 This equipment must only be installed and serviced by qualified electrical personnel.
Failure to follow these instructions will result in death or serious injury.

Drawout Device Positions


The indicator located on the front of the chassis locally signals the position of the device in the chassis.

Device Position indicator and Connector position Device status


position position contact state
Connected  Can be operated.
 Ready for service.

 Disconnecting contact clusters: engaged


 Control: engaged

Test  Can be operated.


 Can have
operation and
control systems
tested.

 Disconnecting contact clusters: disengaged -


the minimum distance between the device
racking terminals and the chassis clusters is
reached.
 Control: engaged

DOCA0101EN-04 07/2020 61
MasterPact MTZ2/MTZ3 Normal Operation

Device Position indicator and Connector position Device status


position position contact state
Disconnected  Can be operated.
 Can be removed
from chassis.

 Disconnecting contact clusters: disengaged


 Control: disengaged

Withdrawn Removed from


chassis.

 Disconnecting contact clusters: disengaged


 Control: disengaged

62 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

Drawout Device Position Contacts


The position of the device in the chassis is indicated remotely by the following position contacts:
 CE: connected position.
 CT: test position.
 CD: disconnected position.

The state of the position contacts changes according to the device position during racking-in and racking-
out operations, as shown in the diagram below.

A Device in connected position


B Separation of the main circuits Position contact is open
C Device in test position
D Separation of auxiliary circuits Position contact is closed
E Device in disconnected position

Drawout Device Position Contacts Without EIFE Ethernet Interface


Without EIFE Ethernet interface, the standard configuration of the position contacts is the following:
 3 CD disconnected position contacts
 3 CE connected position contacts
 3 CT test position contacts

The following optional configurations are available:


 6 CE + 3 CT
 3 CD + 6 CE
 6 CD + 3 CE
 9 CE

DOCA0101EN-04 07/2020 63
MasterPact MTZ2/MTZ3 Normal Operation

Drawout Device Position Contacts With EIFE Ethernet Interface


With EIFE Ethernet interface, the standard configuration of the position contacts is the following:
 3 CD disconnected position contacts
 3 CE connected position contacts

The following optional configurations are available:


 3 CE + 3 CT
 3 CD + 3 CT
 6 CE

Chassis Management Function


The chassis management function is used to:
 Record and check the position of the moving part of the drawout device in the chassis
 Provide information about preventive maintenance actions
 Notify the remote controller about the position of the drawout device

The chassis management function is performed by:


 The EIFE Ethernet interface, refer to DOCA0106EN Enerlin'X EIFE - Embedded Ethernet Interface for
One MasterPact MTZ Drawout Circuit Breaker - User Guide.
 The IO module, refer to DOCA0055EN Enerlin'X IO - Input/Output Application Module for One IEC
Circuit Breaker - User Guide.

64 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

Disconnecting the Drawout Device

Drawout Device Handling Conditions


Connection or disconnection of the drawout device requires insertion of the racking handle. When chassis
locking by keylocks, padlocks, or an open door lock are in place, the racking handle cannot be inserted.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
 Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See
NFPA 70E or CSA Z462 or local equivalent.
 This equipment must only be installed and serviced by qualified electrical personnel.
Failure to follow these instructions will result in death or serious injury.

NOTICE
HAZARD OF EQUIPMENT DAMAGE
 Use the provided racking handle to rack the device into or out of chassis.
 Do not use power tools for racking.
 Do not turn the handle after position release button has popped out.
Failure to follow these instructions can result in equipment damage.

Racking-out a Drawout Device Demonstration Video


To access a demonstration video about racking-out a drawout device, you can click the image, scan the
QR code, or copy and paste the link to your Web browser:

The video also includes demonstration of:


 Racking-in a drawout device
 Removing a drawout from the chassis
 Installing a drawout in the chassis

DOCA0101EN-04 07/2020 65
MasterPact MTZ2/MTZ3 Normal Operation

Racking-out the Device from Connected to Test Position

Step Action
1 Press the opening pushbutton to open
the device.
2 Remove the racking handle from its
storage space.
3 Insert the racking handle into the
racking handle socket.
NOTE: If the IBPO racking interlock
option is installed, press the opening
pushbutton to allow insertion of the
racking handle (see page 105).

4 Push in the position release button.


5 Turn the racking handle
counterclockwise.
Result: The device moves forward in
the chassis.
6 When the test position is reached, the
position release button pops out and the
mechanism blocks the racking handle.
Result: The device is in the test
position.

66 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

Racking-out the Device from Test to Disconnected Position

Step Action
1 Push in the position release button.
2 Turn the racking handle
counterclockwise.
Result: The device moves forward in
the chassis.
3 When the disconnected position is
reached, the position release button
pops out and the mechanism blocks the
racking handle.
Result: The device is in the
disconnected position.

4 Remove the racking handle from the


racking socket.
5 Put the racking handle back into its
storage space.

DOCA0101EN-04 07/2020 67
MasterPact MTZ2/MTZ3 Normal Operation

Connecting the Drawout Device

Drawout Device Handling Conditions


Connection or disconnection of the drawout device requires insertion of the racking handle. When chassis
locking by keylocks, padlocks, or an open door lock are in place, the racking handle cannot be inserted.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
 Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See
NFPA 70E or CSA Z462 or local equivalent.
 This equipment must only be installed and serviced by qualified electrical personnel.
Failure to follow these instructions will result in death or serious injury.

NOTICE
HAZARD OF EQUIPMENT DAMAGE
 Use the provided racking handle to rack the device into or out of chassis.
 Do not use power tools for racking.
 Do not turn the handle after position release button has popped out.
Failure to follow these instructions can result in equipment damage.

Racking-in a Drawout Device Demonstration Video


To access a demonstration video about racking-in a drawout device, you can click the image, scan the QR
code, or copy and paste the link to your Web browser:

The video also includes demonstration of:


 Racking-out a drawout device
 Removing a drawout device from the chassis
 Installing a drawout device in the chassis

68 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

Racking-in the Device from Disconnected to Test Position

Step Action
1 Remove the racking handle from its
storage space.
2 Insert the racking handle into the
racking handle socket.
NOTE: If the IBPO racking interlock
option is installed, press the opening
pushbutton to allow insertion of the
racking handle (see page 105).

3 Push the position release button.


4 Turn the racking handle clockwise.
Result: The device moves back in the
chassis.
5 When the test position is reached, the
position release button pops out and the
mechanism blocks the racking handle.
Result: The device is in the test
position.

DOCA0101EN-04 07/2020 69
MasterPact MTZ2/MTZ3 Normal Operation

Racking-in the Device from Test to Connected Position

Step Action
1 Push the position release button.
2 Turn the racking handle clockwise.
Result: The device moves back in the
chassis.
3 When the connected position is
reached, the position release button
pops out and the mechanism blocks the
racking handle.
Result: The device is in the connected
position.

4 Remove the racking handle from the


racking socket.
5 Put the racking handle back into its
storage space.

70 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

Removing the Drawout Device

Removing a Drawout Device Demonstration Video


To access a demonstration video about removing a drawout device, you can click the image, scan the QR
code, or copy and paste the link to your Web browser:

The video also includes demonstration of:


 Racking-out a drawout device
 Racking-in a drawout device
 Installing a drawout device in the chassis

DOCA0101EN-04 07/2020 71
MasterPact MTZ2/MTZ3 Normal Operation

Device Removal

NOTICE
HAZARD OF EQUIPMENT DAMAGE
The chassis must be securely fastened when installing or removing the device.
Failure to follow these instructions can result in equipment damage.

Step Action
1 With the device in the disconnected
position (see page 84), discharge the
closing spring by pressing the closing
pushbutton.
If the closing spring is charged, the device
closes.
NOTE: For drawout devices fitted with the
optional DAE automatic spring-discharge
interlock (see page 105), the closing spring
is discharged when the device is moved
from disconnected to withdrawn position.
2 Press the opening pushbutton to open the
device.

3 Press and hold the rail release tabs


towards the back.
4 Pull out the rails to the maximum by pulling
on the drawout grips.
Result: The device is supported on the
rails, clear of the chassis and ready to be
lifted.

72 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

Lifting the Device


Both the device and chassis have a carrying grip for lifting. To lift the device, use an overhead lifting device
attached to the carrying grip, following the directions given in this section.

DANGER
HAZARD OF DEVICE FALLING
 Be sure that lifting equipment has lifting capacity for the device being lifted.
 Follow manufacturer’s instructions for use of lifting equipment.
 Wear hard hat, safety shoes, and heavy gloves.
Failure to follow these instructions will result in death or serious injury.

Lift the device from the chassis rails by using the carrying grip located on the sides of the device.

Device Weights
The following table shows the weights of the different devices available.

Number of poles Device MTZ2 MTZ3


3P Moving part (Drawout) 50 kg 120 kg
Chassis 40 kg 105 kg
Fixed Device 50 kg 120 kg
4P Moving part (Drawout) 65 kg 160 kg
Chassis 55 kg 140 kg
Fixed Device 65 kg 160 kg

DOCA0101EN-04 07/2020 73
MasterPact MTZ2/MTZ3 Normal Operation

Installing the Drawout Device in the Chassis

Drawout Device Handling Conditions


Connection or disconnection of the drawout device requires insertion of the racking handle. When chassis
locking by keylocks, padlocks, or an open door lock is in place, the racking handle cannot be inserted.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
 Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See
NFPA 70E or CSA Z462 or local equivalent.
 This equipment must only be installed and serviced by qualified electrical personnel.
Failure to follow these instructions will result in death or serious injury.

NOTICE
HAZARD OF EQUIPMENT DAMAGE
 Use the provided racking handle to rack the device into or out of chassis.
 Do not use power tools for racking.
 Do not turn the handle after position release button has popped out.
Failure to follow these instructions can result in equipment damage.

Optional Mismatch Protection


Mismatch protection (see page 94) allows the installation of a drawout device only in a chassis with
compatible characteristics.

Installing a Drawout Device Demonstration Video


To access a demonstration video about installing a drawout device, you can click the image, scan the QR
code, or copy and paste the link to your Web browser:

The video also includes demonstration of:


 Racking-out a drawout device
 Racking-in a drawout device
 Removing a drawout device from the chassis

74 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

Installing the Device

DANGER
HAZARD OF DEVICE FALLING
 Be sure that lifting equipment has lifting capacity for the device being lifted.
 Follow manufacturer’s instructions for use of lifting equipment.
 Wear hard hat, safety shoes, and heavy gloves.
Failure to follow these instructions will result in death or serious injury.

NOTICE
HAZARD OF EQUIPMENT DAMAGE
 Chassis must be securely fastened when installing or removing the device.
 Before mounting the device, make sure that it matches the chassis.
Failure to follow these instructions can result in equipment damage.

Step Action
1 If the chassis is not installed yet in a switchboard or panelboard, securely fasten the chassis on a pallet.
2 Remove the racking handle from its storage space.
3 Check that the chassis indicator is in the disconnected position:

If the chassis indicator is not in the disconnected position, follow the steps on disconnecting the drawout
device (see page 67).
4 Press the rail release tabs.

5 Pull out the drawout grips until the


extension rails are fully extended.
NOTE: The right-hand rail cannot be
extended if the racking handle has not
been removed.

DOCA0101EN-04 07/2020 75
MasterPact MTZ2/MTZ3 Normal Operation

Step Action
6 Install the device on the extension rails
by using appropriate lifting equipment.
Check that the slots on the device are
correctly aligned with the guides on the
rails while bringing the device down.
7 Detach the lifting equipment.

8 Check that the device is in the open


position.

9 Using both hands, push in the device


so that the rails are inserted to the
maximum in the chassis. Take care not
to push the control unit.

10 Check that the rail release tabs are in


the correct position.
Result: The device is in the
disconnected position.

76 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

Section 2.3
Device Locking Actions

Device Locking Actions

About Locking Actions


A locking action is a manual locking operation made by the user. A number of optional locking accessories
are available for the MasterPact MTZ2/MTZ3 device and chassis. For a complete listing of available locks,
refer to LVPED216026EN MasterPact MTZ Catalogue.

What Is in This Section?


This section contains the following topics:
Topic Page
Locking the Pushbuttons 78
Locking the Device in Open Position with Padlocks 80
Locking the Device in Open Position with Keylocks 82
Chassis Locking in Disconnected Position 84
Chassis Locking in Any Position 88
Locking the Safety Shutters 90

DOCA0101EN-04 07/2020 77
MasterPact MTZ2/MTZ3 Normal Operation

Locking the Pushbuttons

Description
The pushbutton locking cover is an optional accessory for the MasterPact MTZ2/MTZ3 device that forbids
access to the closing and opening pushbuttons:
 Together or separately.
 By using a padlock (shackle diameter 5–8 mm).
 By using a lead seal.
 By using screws.

VBP Pushbutton Locking Accessory


The pushbutton locking accessory is an optional transparent cover, mounted on the front cover of the
device, which covers the closing and opening pushbuttons.

For information on the accessory installation, consult the instruction sheet on the Schneider Electric
website: NVE16147.

78 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

Locking the Pushbuttons

Step Action
1 Close the transparent covers of the locking
accessory.
NOTE: One or both transparent covers of
the locking accessory can be closed and
locked.

2 Lock the transparent covers in place by Padlock


using a padlock, lead seal, or screws.

Lead seal

Screws

DOCA0101EN-04 07/2020 79
MasterPact MTZ2/MTZ3 Normal Operation

Locking the Device in Open Position with Padlocks

Description
Optional padlocks can be used to lock the MasterPact MTZ2/MTZ3 in the open position. When locked the
device cannot be closed either locally with the closing pushbutton or remotely.
To use padlocks to lock the device in the open position, an optional OFF-position locking accessory is
necessary. This accessory allows the use of up to three padlocks with shackle diameter 5–8 mm.

VCPO OFF-Position Locking Accessory


The off-position locking accessory is an optional accessory that is mounted on the front face of the device.

For information on the accessory installation, consult the instruction sheet on the Schneider Electric
website: NVE16146.

Locking the Device in the Open Position

Step Action
1 Press and hold down the opening pushbutton.
2 With the opening button pressed, pull out the tab of the
off-position locking accessory.

3 Insert the padlock in the tab and close the padlock.


Release the opening pushbutton.

80 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

Unlocking the Device

Step Action
1 Remove the padlock.

2 The tab of the OFF-position locking accessory


retracts.

3 Press the closing pushbutton to close the device.

DOCA0101EN-04 07/2020 81
MasterPact MTZ2/MTZ3 Normal Operation

Locking the Device in Open Position with Keylocks

Description
Optional keylocks can be used:
 To lock one MasterPact MTZ2/MTZ3 in the open position. When locked the device cannot be closed
either locally with the closing pushbutton or remotely.
 To interlock several MasterPact MTZ2/MTZ3 devices locked with the same key.

To use keylocks to lock the device in the open position, an optional OFF-position locking accessory is
necessary.
The keylocks can be used in addition to padlocks.

VSPO OFF-Position Locking Accessory


The OFF-position locking accessory is an optional accessory that is mounted on the front of the device.

The OFF-position locking accessory can be fitted with either:


 One keylock.
 Two keylocks with identical keys or different keys.

The following types of keylocks can be fitted:

Ronis keylock Profalux keylock Castell keylock (keylock not Kirk keylock (keylock not
provided) provided)

For information on the accessory installation, consult the instruction sheet on the Schneider Electric
website: NVE16146.

82 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

Locking the Device in the Open Position


For devices equipped with two keylocks, locking with one key is sufficient to lock the device in the open
position.

Step Action
1 Press and hold the opening pushbutton.
2 With the opening pushbutton pressed, turn the key
counterclockwise to lock the device.

3 Remove the key.


4 Release the opening pushbutton.

5 Check that the device is locked in the open position


and cannot be closed either locally with the closing
pushbutton or remotely.

Unlocking the Device


For devices equipped with two keylocks, both keys must be inserted in the keylocks to unlock the device.

Step Action
1 Put the key in the keylock.

2 Turn the key clockwise to unlock the device.

3 Press the closing pushbutton to close the device.


NOTE: The key remains captive in the keylock.

DOCA0101EN-04 07/2020 83
MasterPact MTZ2/MTZ3 Normal Operation

Chassis Locking in Disconnected Position

Description
The chassis can be locked in the disconnected position. When the chassis is locked in the disconnected
position, the racking handle cannot be inserted.
The chassis can be locked in the disconnected position:
 By up to three padlocks with shackle diameter 5–8 mm.
 By optional keylocks.

Keylocks can be used in addition to padlocks.


Chassis locking by padlock is always possible and does not require any accessory.

VSPD Chassis Locking by Keylock Accessory


The chassis locking by keylock accessory can be fitted with either:
 One keylock.
 Two keylocks with identical keys or different keys.

The following types of keylocks can be fitted:

Ronis keylock Profalux keylock Castell keylock (keylock not Kirk keylock (keylock not
provided) provided)

For information on the accessory installation, consult the instruction sheet on the Schneider Electric
website: NVE16142.

84 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

Chassis Locking with Padlocks

Step Action
1 Check that the chassis indicator is in the
disconnected position.

2 Pull out the padlocking tab.

3 Insert the padlocks in the tab and close


the padlocks.

4 Check that the racking handle cannot be


inserted into the racking handle socket.

Chassis Unlocking with Padlocks

Step Action
1 Remove the padlocks.
The tab retracts.

2 Check that the racking handle can be


inserted into the racking handle
socket.

DOCA0101EN-04 07/2020 85
MasterPact MTZ2/MTZ3 Normal Operation

Chassis Locking with Keylocks


For chassis equipped with two keylocks, locking with one key is sufficient to lock the chassis in the
disconnected position.

Step Action
1 Check that the chassis indicator is in
the disconnected position.

2 Turn the key counterclockwise to


lock the chassis.

3 Remove the key.

4 Check that the racking handle


cannot be inserted into the racking
handle socket.

86 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

Chassis Unlocking with Keylocks


For chassis equipped with two keylocks, both keys must be inserted in the keylocks to unlock the chassis.

Step Action
1 Put the key in the lock.

2 Turn the key clockwise to unlock the


chassis.
NOTE: The key remains captive in
the keylock.

3 Check that the racking handle can


be inserted into the racking handle
socket.

DOCA0101EN-04 07/2020 87
MasterPact MTZ2/MTZ3 Normal Operation

Chassis Locking in Any Position

Description
The chassis can be locked in any position (connected, test, or disconnected position).
This locking function requires a mechanical adaptation of the chassis, explained in the following procedure.
When the chassis is locked, the racking handle cannot be inserted in the racking handle socket.
The chassis can be locked in any position:
 By up to three padlocks with shackle diameter 5–8 mm as standard.
 By one or two optional keylocks.

Keylocks can be used in addition to padlocks.

VSPD Chassis Locking by Keylock Accessory


The chassis locking by keylock accessory and the locking and unlocking procedures are the same as for
chassis locking in disconnected position (see page 84).

Adapting the Chassis

DANGER
HAZARD OF DEVICE FALLING
 Be sure that lifting equipment has lifting capacity for the device being lifted.
 Follow manufacturer’s instructions for use of lifting equipment.
 Wear hard hat, safety shoes, and heavy gloves.
Failure to follow these instructions will result in death or serious injury.

NOTICE
HAZARD OF EQUIPMENT DAMAGE
The chassis must be securely fastened when installing or removing the device.
Failure to follow these instructions can result in equipment damage.

Follow this procedure to adapt the chassis locking mechanism so that the chassis can be locked in any
position.

Step Action
1 Make sure that chassis indicator is
in the disconnected position.

2 Remove the device from the chassis


(see page 71).

88 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

Step Action
3 Insert the racking handle into the
racking handle socket.

4 Rotate the latch to the front.


The chassis can now be locked in
any position.

NOTE: To return the chassis to locking only in the disconnected position, rotate the latch to its original
position at the rear.

Latch position for locking in disconnected position. Latch position for locking in any position.

DOCA0101EN-04 07/2020 89
MasterPact MTZ2/MTZ3 Normal Operation

Locking the Safety Shutters

Description
A shutter lock locks the safety shutter in closed position so that the moving part of a
MasterPact MTZ2/MTZ3 device cannot be connected in its chassis.
The top and bottom safety shutters can be locked independently.
The safety shutters can be locked by padlocks either inside the chassis or on the front of the chassis.
The safety shutters can be locked by optional accessories:
 VIVC shutter position indication and locking accessory
 Shutter locking blocks

The accessories can be locked with one padlock with maximum shackle diameter 5–8 mm.

VIVC Shutter Position Indication and Locking Accessory


Use the shutter position indication and locking accessory to perform the following functions:
 Indicate the position of each safety shutter: open or closed.
 Padlock either or both of the safety shutters in closed position with the moving part in test or
disconnected position.

For information on the accessory installation, consult the instruction sheet on the Schneider Electric
website: NVE35478.

Shutter Locking Blocks


The shutter locking blocks allow the locking of the safety shutters inside the chassis. Shutter locking blocks
are delivered with each chassis as standard, and can be stored in the chassis:
 Two shutter locking blocks on a MasterPact MTZ2
 Four shutter locking blocks on a MasterPact MTZ3

90 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

Locking the Safety Shutters by Using Shutter Position Indication and Locking Accessory

Step Action
1 The shutter indicator arms can be
locked individually or together:
 To lock the top safety shutter, pull
the left shutter indicator arm tab out
of the slot.
 To lock the bottom safety shutter,
pull the right shutter indicator arm
tab out of the slot.
2 Insert the padlock in the padlock tab
and close the padlock.

3 Check that the bottom safety shutters


do not open when the actuator on the
right is pressed.

DOCA0101EN-04 07/2020 91
MasterPact MTZ2/MTZ3 Normal Operation

Locking the Safety Shutters by Using Shutter Locking Blocks

Step Action
1 Remove the shutter locking blocks
stored in the chassis.

2 Place the shutter locking blocks in


the appropriate guides:
 To lock the top safety shutter,
install a shutter locking block on
the shutter mechanism on the left.
 To lock the bottom safety shutter,
install a shutter locking block on
the shutter mechanism on the
right.

3 Insert a padlock in each shutter


locking block tab and close the
padlock.

92 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

Section 2.4
Device Interlocking Actions

Device Interlocking Actions

About Interlocking Actions


An interlocking action is an automatic locking operation provided by interlocking accessories added to the
MasterPact MTZ2/MTZ3 device or chassis.
A number of optional interlocking accessories are available for the MasterPact MTZ2/MTZ3 device and
chassis. For a complete listing of available interlocks, refer to LVPED216026EN MasterPact MTZ
Catalogue.
For detailed installation instructions on field-installable interlocks, refer to the installation instructions
shipped with these accessories.

What Is in This Section?


This section contains the following topics:
Topic Page
Mismatch Protection 94
VPEC Door Interlock 96
VPOC Open-door Racking Interlock 99
IPA Cable-type Door Interlock 102
Mechanical Interlocking for Transfer Switches 103
DAE Automatic Spring-Discharge Interlock 105
IBPO Racking Interlock Between Racking Handle and Opening Pushbutton 105

DOCA0101EN-04 07/2020 93
MasterPact MTZ2/MTZ3 Normal Operation

Mismatch Protection

Description
Mismatch protection allows the installation of a MasterPact MTZ2/MTZ3 device only in a chassis with
compatible characteristics.
Mismatch protection offers 35 different combinations that can be selected so that a device can only be
mounted on a chassis with the matching combination.

Accessory
The use of mismatch protection is optional. One mismatch protection accessory is required for each
device.

For information on the accessory installation, consult the instruction sheet on the Schneider Electric
website: NVE35465.

Pin Location of Mismatch Protection


The following illustration shows the pin location on the chassis and device, respectively.

The pin combination selected on the chassis must correspond to the pin combination selected on the
device (see following table). For example, the combination ABCD on the chassis corresponds to the
combination 567 on the device.
Pins on the chassis are labeled A, B, C, D, E, F, G.
Pins on the device are labeled 1, 2, 3, 4, 5, 6, 7.

94 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

Recommended Pin Combinations


The following are the recommended pin combinations:

Pins on chassis Pins on device Pins on chassis Pins on device


ABCD 567 BCDE 167
ABCE 467 BCDF 157
ABCF 457 BCDG 156
ABCG 456 BCEF 147
ABDE 367 BCEG 146
ABDF 357 BCFG 145
ABDG 356 BDEF 137
ABEF 347 BDEG 136
ABEG 346 BDFG 135
ABFG 345 BEFG 134
ACDE 267 CDEF 127
ACDF 257 CDEG 126
ACDG 256 CDFG 125
ACEF 247 CEFG 124
ACEG 246 DEFG 123
ACFG 245
ADEF 237
ADEG 236
ADFG 235
AEFG 234

DOCA0101EN-04 07/2020 95
MasterPact MTZ2/MTZ3 Normal Operation

VPEC Door Interlock

Description
With the door interlock:
 The equipment door is locked and cannot be opened when the drawout device is in connected or test
position.
 The equipment door can be opened when the drawout device is in disconnected position.
 The equipment door can be closed with the drawout device in any position.

Accessory
The VPEC door interlock accessory is an optional accessory that is mounted on the left side or on the right
side of the chassis. One door interlock is necessary for each chassis.

For information on the accessory installation, consult the instruction sheet on the Schneider Electric
website: NVE35493.

96 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

Locking the Equipment Door

Step Action
1 Close the equipment door.

2 Put the device into the test or


connected position
(see page 68).

3 Check that the equipment door


is locked.

DOCA0101EN-04 07/2020 97
MasterPact MTZ2/MTZ3 Normal Operation

Unlocking the Equipment Door

Step Action
1 Put the device into the disconnected position
(see page 65).

2 Check that the equipment door is unlocked.

98 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 Normal Operation

VPOC Open-door Racking Interlock

Description
With the racking interlock installed, a drawout MasterPact MTZ2/MTZ3 device cannot be racked in or out
when the equipment door is open because the racking handle cannot be inserted.

Accessory
The optional VPOC racking interlock can be installed on the right side of the chassis.

For information on the accessory installation, consult the instruction sheet on the Schneider Electric
website: NVE35494.

DOCA0101EN-04 07/2020 99
MasterPact MTZ2/MTZ3 Normal Operation

Activating the Racking Interlock

Step Action
1 Insert the racking interlock.

2 Check that the racking


handle cannot be inserted
into the racking handle
socket when the equipment
door is open.

3 Check that the racking


handle can be inserted into
the racking handle socket
when the equipment door is
closed.

100 DOCA0101EN-04 07/2020


MasterPact MTZ2/MTZ3 Normal Operation

Deactivating the Racking Interlock

Step Action
1 Pull out the racking interlock.

2 Check that the racking handle


can be inserted into the racking
handle socket when the
equipment door is open or
closed.

DOCA0101EN-04 07/2020 101


MasterPact MTZ2/MTZ3 Normal Operation

IPA Cable-type Door Interlock

Description
When the cable-type door interlock is installed, the door cannot be opened when the device is closed and
the device cannot be closed when the door is open.
The cable-type door interlock comprises a plate, a lock and a cable. It is mounted on the right-hand side
of the device.
When the interlock is installed, the mechanical interlock for transfer switches cannot be implemented.

Accessory
The IPA cable-type door interlock is an optional accessory.

For information on the accessory installation, consult the instruction sheet on the Schneider Electric
website: NVE35495.

102 DOCA0101EN-04 07/2020


MasterPact MTZ2/MTZ3 Normal Operation

Mechanical Interlocking for Transfer Switches

Description
The mechanical interlocking for transfer switches between MasterPact MTZ devices prevents the
interlocked devices from closing at the same time. The following interlocking functions are available:
 Interlocking between two devices
 Interlocking between three devices:
 Three incomers
 Two incomers and one coupling
 Two incomers and one replacement

Mechanical Interlocking Between Two Devices


Two devices can be mechanically interlocked by cables or by rods so that both devices cannot be closed
at the same time.

For information on the accessory installation, consult the instruction sheet on the Schneider Electric
website:
 For Interlocking by cables:NVE35496
 For Interlocking by rods: NVE35497

Mechanical Interlocking Between Three Incomers


Mechanical interlocking is between three main devices connected to different power sources.
Only one of the three devices can be in the closed position at a time. The other two devices are held in the
locked open position.

For information on the accessory installation, consult the instruction sheet on the Schneider Electric
website: NVE35498

DOCA0101EN-04 07/2020 103


MasterPact MTZ2/MTZ3 Normal Operation

Mechanical Interlocking Between Two Incomers and One Coupling


Mechanical interlocking is between two main devices connected to different power sources and one tie
device.
Two of the three devices can be in the closed position at any time.

(1) Possible by forcing operation

For information on the accessory installation, consult the instruction sheet on the Schneider Electric
website: NVE35500

Mechanical Interlocking Between Two Incomers and One Replacement


Mechanical interlocking is between two main devices connected to the same power source and a third
device connected to a generator power source.
The generator device is locked open when either or both of the main devices are closed.

For information on the accessory installation, consult the instruction sheet on the Schneider Electric
website: NVE35499

IVE Electrical Interlocking Unit


Electrical interlocking between MasterPact MTZ devices can be done using the IVE electrical interlocking
unit or by using dedicated wiring. The IVE unit is suitable for two devices only. For three devices, dedicated
wiring is required to perform the electrical interlocking.

For information on the accessory installation, consult the instruction sheet on the Schneider Electric
website: 51201201AA

104 DOCA0101EN-04 07/2020


MasterPact MTZ2/MTZ3 Normal Operation

DAE Automatic Spring-Discharge Interlock

Description
The DAE automatic spring-discharge interlock releases the closing spring energy when a drawout
MasterPact MTZ2/MTZ3 device is moved from the disconnected position to the withdrawn position.
The DAE interlock is an optional interlock mounted inside the device. It is factory-installed. To install it on
site, contact your field service representative.

IBPO Racking Interlock Between Racking Handle and Opening Pushbutton

Description
With the IBPO racking interlock installed a drawout MasterPact MTZ2/MTZ3 device cannot be
disconnected in the closed position.
Insertion of the racking handle for connection or disconnection of the drawout device is only possible when
the opening pushbutton is pressed.
The IBPO racking interlock is an optional interlock mounted inside the device. It is factory-installed. To
install it on site, contact your field service representative.

Inserting the Racking Handle With the IBPO Racking Interlock Installed

Step Action
1 Press and hold the opening pushbutton.

2 Insert the racking handle.

DOCA0101EN-04 07/2020 105


MasterPact MTZ2/MTZ3 Normal Operation

106 DOCA0101EN-04 07/2020


MasterPact MTZ2/MTZ3
MasterPact MTZ Critical Cases
DOCA0101EN-04 07/2020

Chapter 3
MasterPact MTZ Critical Cases

MasterPact MTZ Critical Cases

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Finding the Cause of a Trip or an Alarm in Critical Cases 108
Resetting the Circuit Breaker After a Trip Due to an Electrical Fault 111
Resetting the Circuit Breaker After a Trip Due to an Incident Detected by the MicroLogic X Self-tests 114
Diagnosing Alarms 116
Diagnosing Error Messages 124

DOCA0101EN-04 07/2020 107


MasterPact MTZ Critical Cases

Finding the Cause of a Trip or an Alarm in Critical Cases

Definitions
While operating the device, the user may face two critical cases:
 The circuit breaker has tripped automatically, interrupting the power supply.
 The circuit breaker has not tripped, but the MicroLogic X control unit has detected an alarm:
 For a high severity alarm, the service LED is red, indicating that urgent corrective action is required.
 For a medium severity alarm, the service LED is orange, indicating that corrective action needs to be
scheduled.

Notification of a Trip or Alarm


A trip or alarm event is signaled:
 On the MicroLogic X control unit HMI, by the trip cause LEDs or the service LED. When the control unit
is powered, a red or orange pop-up message is displayed on the screen.
 By the SDE fault-trip indication contact

Depending on the options installed, a trip or alarm can also be signaled:


 By an additional SDE2 fault-trip indication contact
 By the outputs of the M2C programmable contacts
 By the outputs of an IO application module
 By an email sent through IFE or EIFE Ethernet interface
 On a remote controller connected to the communication network (application customized by user)
 On the FDM128 display

Active alarms can also be consulted in the following ways:


 On a smartphone with EcoStruxure Power Device app connected to the MicroLogic X control unit:
 Through Bluetooth
 Through USB OTG connection

 On EcoStruxure Power Commission software connected to the MicroLogic X control unit:


 Through USB connection
 Through IFE or EIFE Ethernet interface
 Through IFM Modbus-SL interface

108 DOCA0101EN-04 07/2020


MasterPact MTZ Critical Cases

A Com’X energy server


B FDM128 Ethernet display for eight devices
C Ethernet switch
D EIFE embedded Ethernet interface for one MasterPact MTZ drawout circuit breaker
E IFE Ethernet interface for one MasterPact MTZ circuit breaker
F IO input/output application module for one circuit breaker
G IO module outputs used for event notification
H ULP port module
I One or two SDE fault-trip indication contacts
J Two optional M2C programmable contacts
K MicroLogic X control unit
L Drawout MasterPact MTZ circuit breaker
M Fixed MasterPact MTZ circuit breaker

Identifying the Cause of a Trip or Alarm Using the MicroLogic X Control Unit
In critical situations, the cause of a trip or an alarm can be identified locally by using one of the following:
 The blue fault-trip reset button on the circuit breaker (A). When the trip button is popped out, the trip has
occurred.
 The indicators on the MicroLogic X control unit (see page 110):
 The Ready LED (B)
 The service LED (C)
 The MicroLogic X display screen (D)
 The trip cause LEDs (E)

 A smartphone with EcoStruxure Power Device app installed to get the trip cause, the trip or alarm
context, and the device ID:
 Through NFC
 Through Bluetooth
 Through USB OTG connection

A Blue fault-trip reset button


B Ready LED
C Service LED
D MicroLogic X display screen
E Trip cause LEDs

NOTE: The optional Power Restoration Assistant Digital Module provides assistance with restoring power
after a trip. For more information, refer to DOCA0102EN MasterPact MTZ - MicroLogic X Control Unit -
User Guide.

Availability of Diagnostic Data After a Trip


The diagnostic data is available when the MicroLogic X control unit is powered.
If the MicroLogic X control unit is not permanently powered by an external 24 Vdc power source, connect
the MicroLogic X control unit to an external power supply, for example, the Mobile Power Pack, through
the mini USB port to have access to the diagnostic data.
When the MicroLogic X control unit is powered externally, the availability of diagnostic data depends on
the MicroLogic X state:
 If the MicroLogic X control unit is operative, all diagnostic data is available.
 If the MicroLogic X control unit is inoperative, no data is directly available. However, some data can be
extracted using the NFC function with the EcoStruxure Power Device app.
The trip cause LEDs and the red service LED are powered by the MicroLogic X internal lithium battery and
remain on for 4 hours when there is no other power to the control unit. To switch on the trip cause LEDs
or the red service LED again after 4 hours, press the Test/Reset button.

DOCA0101EN-04 07/2020 109


MasterPact MTZ Critical Cases

Using the Display Screen and LEDs to Find the Cause of a Trip
The circuit breaker has tripped automatically, interrupting the power supply, and the blue fault-trip reset
button has popped out.

Ready LED Service LED MicroLogic X Trip cause LEDs Description


display screen
Ready LED Service LED off. One of the trip cause LEDs is on Electrical fault on the
flashing green. red. network (see page 111)

Ready LED off. Service LED on All LEDs are on. Major MicroLogic X
red. control unit incident
detected during self-test
(see page 114)

Using the Display Screen and LEDs to Find the Cause of an Alarm
The circuit breaker has not tripped, but the MicroLogic X control unit service LED is on.

Ready LED Service LED MicroLogic X Trip cause LEDs Description


display screen
Ready LED flashing Service LED on All LEDs are off or all LEDs are High severity alarm
green or Ready LED red. on. (see page 117)
off.

Ready LED flashing Service LED on All LEDs are off. Medium severity alarm
green. orange. (see page 118)

110 DOCA0101EN-04 07/2020


MasterPact MTZ Critical Cases

Resetting the Circuit Breaker After a Trip Due to an Electrical Fault

Reset Sequence

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not re-close the device on an electrical fault.
First inspect and, if necessary, repair the downstream equipment.
Failure to follow these instructions will result in death or serious injury.

The table shows the sequence of actions to follow after a trip due to an electrical fault. Further explanation
of each action is given in the following paragraphs.

Step Action
1 Identify the trip cause.
2 Press OK to view details of the trip cause on the display screen.
3 Consult the two trip cause context screens:
 Screen 1: Name and settings of the tripping protection, date and time of the trip.
 Screen 2: Current values recorded before the trip.

4 Clear the electrical fault on the network.


5 Inspect the circuit breaker and switchboard after a short circuit.
6 Press OK to acknowledge the trip cause and return to the Home menu.
NOTE: If the trip cause is not acknowledged within the event timeout, the pop-up is displayed again.
7 Reset the circuit breaker (see page 50).
8 Press the Test/Reset button for 3 seconds to reset the latched events and switch off the trip cause
LEDs.
9 When the circuit breaker is ready-to-close, re-close it (see page 47).

NOTE: You may use the EcoStruxure Power Device app with the Power Restoration Assistant Digital
Module to get support while resetting after a trip due to an electrical fault.

DOCA0101EN-04 07/2020 111


MasterPact MTZ Critical Cases

Identifying the Trip Cause

Ready LED Service LED MicroLogic X display Trip cause LEDs Description
screen
Ready LED Service LED  MicroLogic 2.0 X,
flashing green. off. 5.0 X, 6.0 X, 7.0 X:
trip due to the long-
time protection.

 MicroLogic 2.0 X: trip


due to the
instantaneous
protection.
 MicroLogic 5.0 X,
6.0 X, 7.0 X: trip due
to the short-time
protection or
instantaneous
protection.
 MicroLogic 2.0 X,
5.0 X: not used.
 MicroLogic 6.0 X: trip
due to the ground-
fault protection.
 MicroLogic 7.0 X: trip
due to the earth-
leakage protection.
 MicroLogic 2.0 X,
5.0 X, 6.0 X, 7.0 X:
trip due to optional
protections.

NOTE: Diagnostic assistance can be obtained by using a smartphone running the EcoStruxure Power
Device app.

112 DOCA0101EN-04 07/2020


MasterPact MTZ Critical Cases

Clearing the Electrical Fault

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
 Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See
NFPA 70E or CSA Z462 or local equivalent.
 This equipment must be installed and serviced by qualified electrical personnel.
 Turn off all power supplying this equipment before performing maintenance inspections.
Assume that all circuits are live until they are de-energized, tested, grounded, and tagged. Consider
all sources of power, including the possibility of backfeeding and control power.
 Always use a properly rated voltage sensing device to confirm that power is off.
 Replace all devices, doors, and covers before turning on power to this equipment.
 Beware of potential hazards and carefully inspect the work area for tools and objects that may have
been left inside the equipment.
Failure to follow these instructions will result in death or serious injury.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not re-close the device on an electrical fault.
First inspect and, if necessary, repair the downstream equipment.
Failure to follow these instructions will result in death or serious injury.

The feed must be isolated before inspecting the electrical equipment downstream of the protection.
The fact that a circuit breaker has tripped does not remedy the cause of the electrical fault detected on the
downstream electrical equipment.

Inspecting the Circuit Breaker and Switchboard After a Trip on Short Circuit
After a trip on short circuit due to short-time or instantaneous protection, the circuit breaker and
switchboard must be inspected for smoke deposits or cracks in the device casing.
Refer to DOCA0099EN MasterPact MTZ - IEC Circuit Breakers and Switch-Disconnectors - Maintenance
Guide and contact your field service representative.

DOCA0101EN-04 07/2020 113


MasterPact MTZ Critical Cases

Resetting the Circuit Breaker After a Trip Due to an Incident Detected by the MicroLogic X Self-tests

Reset Sequence
The following table shows the sequence of actions to take after a trip due to an incident detected by the
MicroLogic X control unit. Further explanation of each action is given in the following paragraphs.

Step Action
1 Identify the trip cause.
2 Press OK to view details of the trip cause on the display screen:
 A code that identifies the trip cause.
 A trip message describing the cause of the incident.
 The date and time that the incident occurred.

3 Consult the list of possible detected incidents (see page 115) and perform the actions recommended to
restart after the trip.
4 Press OK to acknowledge the trip and return to the Home menu.
5 Reset the circuit breaker (see page 50).
6 Press the Test/Reset button for 3 seconds to reset the latched events and switch off the trip cause LEDs
and the service LED.
7 When the circuit breaker is ready to close, re-close it (see page 47).

Identifying the Trip Cause

Ready LED Service LED MicroLogic X Trip cause LEDs Description


display screen
Ready LED off. Service LED on red. All LEDs are on. Major MicroLogic X
control unit incident
detected during self-
test (see page 115).

Ready LED Service LED off. Op. LED is on. Circuit breaker
flashing green. incident detected
during self-test
(see page 115).

114 DOCA0101EN-04 07/2020


MasterPact MTZ Critical Cases

Recommended Actions After a Trip Due to a MicroLogic X Incident


The following table indicates what action to perform according to the trip message.
For more information, refer to the event messages in DOCA0102EN MasterPact MTZ - MicroLogic X
Control Unit - User Guide.

Code Trip message Description Recommended action


0x1400 Control unit self test The control unit self test detected a Plan to replace the MicroLogic X
0x1404 major malfunction major malfunction in the control unit control unit.
0x1405 operation.
0x1406
NOTE: The malfunction trips or does
0x1416
not trip the circuit breaker, depending on
the malfunction detected.
0x1402 Internal current The control unit self test detected the Plan to replace the MicroLogic X
sensor disconnection of an internal sensor of control unit.
disconnected the circuit breaker.
0x1403 External neutral The control unit self-test detected the Check connection of the External
current sensor disconnection of the external neutral Neutral Current Sensor (ENCT).
disconnected current sensor of the circuit breaker.
0x6407 Self diagnostic trip The circuit breaker tripped following a Plan to replace the MicroLogic X
control unit microprocessor (Asic) control unit.
invalid result.
0x641F Replace Circuit The circuit breaker tripped following a Replace the circuit breaker.
Breaker. Self major malfunction of one or two internal
Diagnostic current power supply sensors of the
circuit breaker.

DOCA0101EN-04 07/2020 115


MasterPact MTZ Critical Cases

Diagnosing Alarms

Diagnosis Sequence
The following table shows the sequence of actions to take after an alarm is detected by the MicroLogic X
control unit. Further explanation of each action is given in the following paragraphs.

Step Action
1 Identify the alarm detected.
2 Press OK to view details of the alarm detected on the display screen:
 An alarm message.
 The date and time that the alarm occurred.

3 Consult the list of alarm messages in the following tables and perform the actions recommended.
4 Press OK to acknowledge the alarm and return to the Home menu.
5 Press the Test/Reset button for 3 seconds to reset the latched events and switch off the trip cause LEDs
and the service LED.

Identifying the Alarm Detected


The MicroLogic X control unit indicates alarms with:
 The Ready LED (flashing green or off)
 The service LED (red or orange)
 A pop-up alarm screen (red or orange)

Two levels of alarm are detected and indicated by the color of the service LED:
 Red for high-severity detected alarms.
 Orange for medium-severity detected alarms.

Ready LED Service LED MicroLogic X Trip cause LEDs Description


display screen
Ready LED Service LED on All LEDs are off or all LEDs are High severity alarm
flashing green or red. on. (see page 117)
Ready LED off.

Ready LED Service LED on All LEDs are off. Medium severity alarm
flashing green. orange. (see page 118)

116 DOCA0101EN-04 07/2020


MasterPact MTZ Critical Cases

Recommended Action After Detection of High Severity Alarms


The following table indicates what action to perform according to the alarm message.
For more information, refer to the event messages in DOCA0102EN MasterPact MTZ - MicroLogic X
Control Unit - User Guide.

Code Alarm message Alarm description Recommended action


0x1400 Control unit self test major The control unit self test detected a Plan to replace the MicroLogic X
0x1404 malfunction major malfunction in the control unit control unit.
0x1405 operation.
0x1406
NOTE: The malfunction trips or
0x1416
does not trip the device, depending
on the malfunction detected.
0x1408 Earth leakage (Vigi) sensor The control unit self test detected Check the connection of the
disconnected the disconnection of an earth external earth leakage (Vigi)
leakage (Vigi) sensor. sensor.
0x1409 Unable to read sensor plug The control unit is unable to read the Check connection of the sensor
value of the sensor plug. plug and performer plugs. If the
connection is good but it fails
again, replace the sensor plug or
the control unit.
0x1413 I∆n/Ig test - no trip The earth-leakage (I∆n)/ground (Ig) Restart the test. If it fails again,
did not trip. replace the control unit.
0x1430 Protection settings reset to If switched off, the control unit will be Update the MicroLogic X control
factory values reset at next reboot to the default unit firmware with EcoStruxure
values of the protection settings, Power Commission software.
due to a control unit incident. Otherwise, plan to replace the
MicroLogic X control unit
0x1442 Contact wear > 100%. Replace The contact wear indicator reached Replace the circuit breaker.
CB the threshold of 100%. Consult contact wear
interpretation on EcoStruxure
Power Device app in order to
estimate the circuit breaker ability
to isolate, withstand rated duty,
operate, trip.
0x1444 CB has reached the max The circuit breaker reached the Replace the circuit breaker.
number of operations maximum number of operations.
0x1446 MicroLogic control unit has MicroLogic control unit reached 15 Replace the MicroLogic X control
reached the max service life years of service life. unit.
0x1451 MCH has reached the max The MCH gear motor reached the Replace the MCH.
number of operations maximum number of operations.
0x1453 MX1 voltage release has The MX1 voltage release reached Replace the MX1 voltage
reached the max number of the maximum number of operations. release.
operations
0x1455 XF voltage release has reached The XF voltage release reached the Replace the XF voltage release.
the max number of operations maximum number of operations.
0x1457 MN undervoltage release has The MN undervoltage release Replace the MN undervoltage
reached the max number of reached the maximum number of release.
operations operations.
0x1459 MX2 voltage release has The MX2 voltage release reached Replace the MX2 voltage
reached the max number of the maximum number of operations. release.
operations
0x150F Replace Circuit Breaker. The control unit self test detected Replace the circuit breaker.
the malfunction of all internal current
power supply sensors of the circuit
breaker.
0x1510 Replace Circuit Breaker. Tsd The control unit self test detected Replace the circuit breaker.
forced to 0. the malfunction of all internal current
power supply sensors of the circuit
breaker and Tsd is forced to 0.

DOCA0101EN-04 07/2020 117


MasterPact MTZ Critical Cases

Code Alarm message Alarm description Recommended action


0x1511 Plan to Replace Circuit Breaker. The control unit self test detected Plan to replace the circuit
the malfunction of one or two breaker.
internal current power supply
sensors of the circuit breaker.
0x1512 Replace Circuit Breaker. The control unit self test detected Replace the circuit breaker.
the major malfunction of one or two
internal current power supply
sensors of the circuit breaker.

For more information about the maximum number of operations for individual parts, refer to DOCA0099EN
MasterPact MTZ - IEC Circuit Breakers and Switch-Disconnectors - Maintenance Guide.
Contact your Schneider Electric field service representative for more information about who can carry out
the recommended actions.

Recommended Action After Medium Severity Alarms


The following table indicates what action to perform according to the alarm message.
For more information, refer to the event messages in DOCA0102EN MasterPact MTZ - MicroLogic X
Control Unit - User Guide.

Code Alarm message Alarm description Recommended action


0x03F5 Ir prealarm (I > 90% Ir) The long time protection prealarm Check the load.
started: at least one of the phase or
neutral currents is above the 90% Ir
threshold. The circuit breaker is
operating close to Ir threshold.
0x0D00 Critical hardware modules There is a major hardware Check which module is in critical
discrepancy discrepancy between the installed hardware discrepancy with the
modules that prevents them from EcoStruxure Power Commission
operating. software Firmware menu.
Replace the module.
0x0D01 Critical firmware modules There is a major software discrepancy Check which module is in critical
discrepancy between the installed ULP modules firmware discrepancy with the
that prevents them from operating. EcoStruxure Power Commission
software. Update the module.
0x0D02 Non-critical hardware There is a minor hardware Check which module is in non-
modules discrepancy discrepancy between the installed critical hardware discrepancy with
modules that prevents them from the EcoStruxure Power
operating correctly. Commission software Firmware
menu. Plan to replace the
module.
0x0D03 Non-critical firmware There is a minor software discrepancy Check which module is in non-
modules discrepancy between the installed modules that critical firmware discrepancy with
prevents them from operating the EcoStruxure Power
correctly. Commission software. Plan to
update the module.
0x0D06 Config. error - dual settings or There is a declaration error between Correct the configuration error
inhibit close order the IO module and the control unit. with EcoStruxure Power
Commission software:
 Dual settings configuration
error:
1. Set Switch mode to IO -
1 Wire or IO - 2 Wires.
2. Set IO module with dual
setting assignment.
 Inhibit close order
configuration error:
1. Set Allow control by digital
input under breaker close
as enabled.
2. Set IO module with
Enable/Inhibit close order
assignment.

118 DOCA0101EN-04 07/2020


MasterPact MTZ Critical Cases

Code Alarm message Alarm description Recommended action


0x0D08 Address conflict between The control unit self-test detected the If two IO modules are installed in
modules unexpected presence of IO2 module the system, make sure one is
when IO1 is not present. configured as IO#1, the other as
IO#2.
0x0D09 Firmware discrepancy within The control unit self-test detected a Check the firmware version of the
CU discrepancy between the firmware MicroLogic X control unit with
versions of control unit processors. EcoStruxure Power Commission
software. If not latest, update the
firmware of the MicroLogic X
control unit.
0x0D0C Config error IO/CU: optional There is a declaration error between Correct the configuration error
protection Inhibit the IO module and the control unit for with EcoStruxure Power
inhibition of optional protection Commission software:
functions.  If you want optional protection
inhibition to be controlled by
IO module, connect an IO
module with inhibit optional
protection assignment.
 If you do not want optional
protection inhibition to be
controlled by IO module,
connect an IO module without
inhibit optional protection
assignment.
0x0D0D Config. error IO and CU - There is a declaration error between Correct the configuration error
Local/Remote mode the IO module and the control unit for with EcoStruxure Power
local/remote mode assignment. Commission software:
 If you want the L/R mode to be
controlled by the IO module,
connect an IO module with L/R
mode assignment.
 If you do not want the L/R
mode to be controlled by the
IO module, connect an IO
module without L/R mode
assignment.
0x0D0E Discrepancy between The control unit self-test detected a Replace the embedded display
Display and MicroLogic discrepancy between the hardware screen.
version of the embedded display
screen and the firmware version of the
control unit.
0x1108 Protection changed by The protection parameters were No action required, for
communication changed by communication from information only.
remote controller, EcoStruxure Power
Commission software, or EcoStruxure
Power Device app.
0x1120 Communication lost with The control unit lost communication Check the power supply of the
IO#1 module with the IO1 module. IO1 module. Check the ULP
cable connection.
0x1121 Communication lost with The control unit lost communication Check the power supply of the
IO#2 module with the IO2 module. IO2 module. Check the ULP
cable connection.
0x1122 Communication lost with The control unit lost communication Check the power supply of the
EIFE or IFE module with the EIFE or IFE module. EIFE or IFE module. Check the
ULP cable connection.
0x1123 Communication lost with IFM The control unit lost communication Check the power supply of the
module with the IFM module. IFM module. Check the ULP
cable connection.
0x112C Control unit firmware update The firmware update of the control Restart the update procedure. If
unsuccessful unit was unsuccessful. the message is displayed again,
plan to replace the MicroLogic X
control unit.
0x1471 Control unit self test The control unit self-test detected an Plan to replace the MicroLogic X
0x1472 invalid result with minor impact. control unit.

DOCA0101EN-04 07/2020 119


MasterPact MTZ Critical Cases

Code Alarm message Alarm description Recommended action


0x147A Invalid display screen or The control unit self-test detected an Plan to replace the embedded
0x147B wireless communication invalid display screen or wireless display screen, which contains
communication. the wireless antenna.
0x1411 Invalid measurement and The control unit self-test detected an Plan to replace the MicroLogic X
optional protection #1 invalid result with minor impact in the control unit.
metering and other protection
functions of the control unit.
0x1414 NFC invalid communication The control unit self-test detected an Plan to replace the embedded
0x1415 invalid NFC connection. display screen, which contains
the wireless antenna.
0x1422 Invalid Bluetooth The control unit self-test detected the Plan to replace the embedded
communication absence of Bluetooth communication. display screen.
0x1433 Replace internal battery The lithium battery is under 3 V and Replace internal battery.
needs to be replaced soon.
0x1434 Self diagnostic test - firmware The control unit self-test detected a Update the firmware of the
firmware internal incident. MicroLogic X control unit with
EcoStruxure Power Commission
software.
0x1438 Main voltage loss and Circuit The circuit breaker is closed but no Check main voltage on the
Breaker is closed voltage is detected. busbar.
0x1440 Contact wear > 60%. Check The contact wear indicator reached or Inspect visually the arc chute and
contacts is above the threshold of 60%. main contacts at the next
scheduled maintenance. Consult
contact wear interpretation on
EcoStruxure Power Device app in
order to estimate the circuit
breaker ability to isolate,
withstand rated duty, operate,
trip.
0x1441 Contact wear > 95%. Plan for The contact wear indicator reached or Plan to replace the circuit
replacement is above the threshold of 95%. breaker. Consult contact wear
interpretation on EcoStruxure
Power Device app in order to
estimate the circuit breaker ability
to isolate, withstand rated duty,
operate, trip.
0x1443 Remaining service life of CB The circuit breaker reached 80% of Plan to replace the circuit
is below alarm threshold the maximum number of operations. breaker. To refine this theoretical
alarm by taking in account
environmental parameters, you
may ask for aging diagnostic. If
the device is cloud connected,
use EcoStruxure asset advisor for
remote aging diagnostic.
Otherwise, contact Schneider
Electric services for a local aging
diagnostic.
0x1445 Remaining service life of The control unit reached 12 years of Plan to replace the MicroLogic X
MicroLogic is below alarm service life. control unit. To refine this
threshold theoretical alarm by taking in
account environmental
parameters, you may ask for
aging diagnostic. If the Device is
cloud connected, use
EcoStruxure asset advisor for
remote aging diagnostic.
Otherwise, contact Schneider
Electric services for a local aging
diagnostic.
0x1450 MCH charging operation The MCH gear motor reached 80% of Plan to replace the MCH. Consult
counter is above alarm the maximum number of operations. the predicted date of replacement
threshold on EcoStruxure Power Device
app.

120 DOCA0101EN-04 07/2020


MasterPact MTZ Critical Cases

Code Alarm message Alarm description Recommended action


0x1452 MX1 voltage release The MX1 voltage release reached Plan to replace the MX1 voltage
operation counter is above 80% of the maximum number of release. Consult the predicted
alarm threshold operations. date of replacement on
EcoStruxure Power Device app.
0x1454 XF voltage release operation The XF voltage release reached 80% Plan to replace the XF voltage
counter is above alarm of the maximum number of release. Consult the predicted
threshold operations. date of replacement on
EcoStruxure Power Device app.
0x1456 MN undervoltage release The MN undervoltage release Plan to replace the MN
operation counter is above reached 80% of the maximum undervoltage release. Consult the
alarm threshold number of operations. predicted date of replacement on
EcoStruxure Power Device app.
0x1458 MX2 voltage release The MX2 voltage release reached Plan to replace the MX2 voltage
operation counter is above 80% of the maximum number of release. Consult the predicted
alarm threshold operations. date of replacement on
EcoStruxure Power Device app.
0x1460 Invalid self test - MX1 voltage The control unit self-test of the MX1 Plan to replace the MX1 voltage
release voltage release detected an invalid release.
result with minor impact.
0x1461 MX1 voltage release not The control unit self-test detected the Check the connection of the MX1
detected unexpected absence of the MX1 voltage release.
voltage release.
0x1462 Invalid self test - XF voltage The control unit self-test of the XF Plan to replace the XF voltage
release voltage release detected an invalid release.
result with minor impact.
0x1463 XF voltage release not The control unit self-test detected the Check the connection of the XF
detected unexpected absence of the XF voltage release.
voltage release.
0x1464 Invalid self test - MN The control unit self-test of the MN Plan to replace the MN
undervoltage release undervoltage release detected an undervoltage release.
invalid result with minor impact.
0x1465 MN undervoltage release not The control unit self-test detected the Check the connection of the MN
detected unexpected absence of the MN undervoltage release.
undervoltage release.
0x1466 Voltage loss on MN The circuit breaker opened because Check the control voltage.
undervoltage release there is no control voltage on the MN
undervoltage release.
0x1467 Communication loss on MN The control unit lost communication Check the internal connection of
undervoltage release with the MN undervoltage release. MN undervoltage release.
0x1468 Invalid self test - MX2 voltage The control unit self-test of the MX2 Plan to replace the MX2 voltage
release voltage release detected an invalid release.
result with minor impact.
0x1469 MX2 voltage release not The control unit self-test detected the Check the connection of the MX2
detected unexpected absence of the MX2 voltage release.
voltage release.
0x140F Protection settings no The control unit cannot access the Plan to replace the MicroLogic X
0x1474 accessible protection settings. control unit.
0x1475
0x1476
0x1477
0x1479 Invalid measurement and The control unit self-test detected an Plan to replace the MicroLogic X
optional protection invalid measurement or an invalid control unit.
optional protection function of the
control unit.
0x6200 Ir start (I > 105% Ir) The long time protection started: at No action required, for
least one of the phase or neutral information only.
currents is above the Ir threshold. The
circuit breaker will trip at the end of
time delay.
0x6300 Ir operate The long time protection operated: at No action required, for
least one of the phase or neutral information only.
currents is above the Ir threshold and
the tr time delay is elapsed.

DOCA0101EN-04 07/2020 121


MasterPact MTZ Critical Cases

Code Alarm message Alarm description Recommended action


0x6301 Isd operate The short time protection operated: at No action required, for
least one of the phase or neutral information only.
currents is above the Isd threshold
and the tsd time delay is elapsed.
0x6302 Ii operate The instantaneous protection No action required, for
operated: at least one of the phase or information only.
neutral currents is above the Ii
threshold (no time delay).
0x050C Ig alarm The ground fault alarm operated: the Check insulation between
ground fault current is above the Ig phase/neutral and ground (earth).
alarm threshold and the tg time delay
alarm is elapsed.
0x6303 Ig operate The ground fault protection operated: No action required, for
the ground fault current is above the information only.
Ig threshold and the tg time delay is
elapsed.
0x050D I∆n alarm The earth leakage alarm operated: Check insulation between
the earth leakage current is above the phase/neutral and ground (earth).
I∆n alarm threshold and the t∆n time
delay alarm is elapsed.
0x6304 I∆n operate The earth leakage (I∆n) protection No action required, for
started: the earth leakage current is information only.
above the I∆n threshold and the t∆n
time delay is elapsed.
0x6310 Undervoltage on 1 phase Undervoltage protection on one No action required, for
operate phase operated: one of the three information only.
monitored voltages is below the
Vmin1 threshold.
0x632A Undervoltage on all 3 phases Undervoltage protection on all three No action required, for
operate phases operated: the three monitored information only.
voltages are below the Vmin2
threshold.
0x6311 Overvoltage on 1 phase Overvoltage protection on one phase No action required, for
operate operated: one of the three monitored information only.
voltages is above the Vmax1
threshold.
0x632B Overvoltage on all 3 phases Overvoltage protection on all three No action required, for
operate phases operated: the three monitored information only.
voltages are above the Vmax2
threshold.
0x6315 Underfrequency operate The underfrequency protection No action required, for
operated: the frequency is below the information only.
Fmin threshold.
0x6316 Overfrequency operate The overfrequency protection No action required, for
operated: the frequency is above the information only.
Fmax threshold.
0x6314 Reverse power operate The reverse power protection No action required, for
operated: the reverse power is above information only.
the Rp threshold and the tRp time
delay is elapsed.
0x6321 IDMTL long-time operate The IDMTL long-time protection No action required, for
operated: at least one of the phase or information only.
neutral currents is above the IDMTL Ir
threshold and the IDMTL tr time delay
is elapsed.
0x6323 Forward directional The forward directional overcurrent No action required, for
overcurrent operate protection operated: the forward information only.
directional overcurrent is above the
Ifw threshold and the tfw time delay is
elapsed.

122 DOCA0101EN-04 07/2020


MasterPact MTZ Critical Cases

Code Alarm message Alarm description Recommended action


0x6324 Reverse directional The reverse directional overcurrent No action required, for
overcurrent operate protection operated: the reverse information only.
directional overcurrent is above the
Irv threshold and the trv time delay is
elapsed.
0x0C04 ESM (ERMS switch module) The ESM self-test detected an invalid Plan to replace the ESM (ERMS
self diagnostic alarm result with minor impact. switch module).
0x0C05 Communication lost with The control unit lost communication Plan to replace the ESM (ERMS
ESM (ERMS switch module) with ESM module (ERSM switch switch module).
module).
0x142C Ig protection configured in The Ig protection (IEC version) is No action required, for
OFF mode disabled. information only.
0x142F Last modification of The control unit did not apply the last Apply again the protection
protection settings has not modification. settings.
been completely applied
0x147C Invalid optional protection self The control unit self-test of optional Plan to replace the MicroLogic X
test protections detected an invalid result control unit.
with minor impact.
0x6306 Ultimate self-protection The integrated instantaneous No action required, for
(SELLIM) operate protection (SELLIM) operates: at least information only.
one of the phase or neutral currents is
above the SELLIM threshold (no time
delay).
0x631D Ultimate self-protection The integrated instantaneous No action required, for
(DIN/DINF) operate protection (DIN/DINF) operates: at information only.
least one of the phase or neutral
currents is above the DIN/DINF
threshold (no time delay).
0x1480 Schedule basic maintenance A basic maintenance program should Plan to schedule the basic
within one month be performed within one month. preventive maintenance program
within one month. To plan, edit
report and track maintenance
intervention, you may use
EcoStruxure Facility Expert app.
0x1481 Schedule standard A standard maintenance program Plan to schedule the basic
maintenance within one should be performed within one preventive maintenance program
month month. within one month. To plan, edit
report and track maintenance
intervention, you may use
EcoStruxure Facility Expert app.
0x1482 Schedule manufacturer A manufacturer maintenance Plan to schedule the
maintenance within three program should be performed within manufacturer preventive
months three months. maintenance program within
three months. To plan, edit report
and track maintenance
intervention, you may use
EcoStruxure Facility Expert app.

DOCA0101EN-04 07/2020 123


MasterPact MTZ Critical Cases

Diagnosing Error Messages

Diagnosis Sequence
The following table shows the sequence of actions to take after an error is detected by the MicroLogic X
control unit. Further explanation of each action is given in the following paragraphs.

Step Action
1 Identify the error detected.
2 Consult the list of error messages (see page 125) and perform the actions recommended.
3 Press OK to acknowledge the error and return to the Home menu.
4 Press the Test/Reset button for 3 seconds to reset the latched events.

Identifying the Error Detected


An error message is displayed when the MicroLogic X control unit detects an internal error.
Example of error screen:

124 DOCA0101EN-04 07/2020


MasterPact MTZ Critical Cases

Recommended Action After Detection of Errors


The following table indicates what action to perform according to the error message.

Code Error message Error description Recommended action


1 to 24 Service not performed - The requested action has failed due to Repeat the action that caused the
157 internal error an internal error error. If the message is displayed
190 again, switch off the 24 Vdc of the
MicroLogic X control unit and
switch it on again. If the problem
persists, call Schneider Electric
field service.
158 Command rejected, The MicroLogic X control unit has Repeat the command.
already in progress detected simultaneous orders (for
example between IO and control unit).
169 Command rejected, The MicroLogic X control unit is Check that the MicroLogic X
already in asked state. already in the requested state. control unit is in the required state.
If it is not, repeat the command.
174 Session Key is invalid The request action has failed because Repeat the action that caused the
the session key is not valid. error. If the message is displayed
again, switch off the 24 Vdc of the
MicroLogic X control unit and
switch it on again. If the problem
persists, call Schneider Electric
field service.
175 Out of session scope The requested action has failed Repeat the action that caused the
because it is not within the session error. If the message is displayed
scope. again, switch off the 24 Vdc of the
MicroLogic X control unit and
switch it on again. If the problem
persists, call Schneider Electric
field service.
176 Session is already opened The MicroLogic X control unit has Press OK to clear the message
detected simultaneous settings and then repeat the command.
sessions (for example, EcoStruxure
Power Commission and control unit).
177 No session is open Submit/apply operations have not Start a new session, re-enter the
been performed within five minutes. settings, then submit and apply
them.
180 Bluetooth disabled! To Bluetooth communication has not been Enable Bluetooth communication
enable go to Configuration enabled for the MicroLogic X control from the MicroLogic X control unit
menu. unit. menu > Configuration >
Communication > Bluetooth.

Contact your Schneider Electric field service representative for more information about who can carry out
the recommended actions.

DOCA0101EN-04 07/2020 125


MasterPact MTZ Critical Cases

126 DOCA0101EN-04 07/2020


MasterPact MTZ2/MTZ3
MasterPact MTZ Commissioning
DOCA0101EN-04 07/2020

Chapter 4
MasterPact MTZ Commissioning

MasterPact MTZ Commissioning

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Introduction to Commissioning 128
Inspection and MicroLogic X Settings 130
Tests 132
Communication Tests 135
Final Checks and Reporting 136
MasterPact MTZ Test Form 137

DOCA0101EN-04 07/2020 127


MasterPact MTZ Commissioning

Introduction to Commissioning

Overview

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
 Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See
NFPA 70E, CSA Z462, NOM 029-STPS, or local equivalent.
 This equipment must only be installed and serviced by qualified electrical personnel.
 Unless specified otherwise in the commissioning procedures, all operations (inspection, test, and
preventive maintenance) must be carried out with the device, the chassis, and the auxiliary circuits de-
energized.
 Check that the device and the chassis are de-energized on the upstream and downstream terminals.
 Always use a properly rated voltage sensing device to confirm that the device, the chassis, and the
auxiliary circuits are de-energized.
 Install safety barriers and display a danger sign.
 During the tests, it is strictly forbidden for anyone to touch the device, the chassis, or the conductors
while voltage is applied.
 Before putting the equipment back into operation, it is mandatory to check that all connections are
made with the correct tightening torque, there are no tools or objects inside the equipment, all devices,
doors, and protective covers are in position, and the device is off (open position).
Failure to follow these instructions will result in death or serious injury.

This chapter details the testing and commissioning procedure for MasterPact MTZ devices that must be
done before the device can be accepted as fit for service and connected to a power supply.
The commissioning procedure must be done by an authorized commissioning engineer with appropriate
training and experience:
 Only qualified electrical personnel with training and experience on low voltage circuits must perform the
work described in this chapter.
Personnel must understand the hazards involved in working with or near low-voltage equipment. Such
work must be performed only after reading the complete set of instructions.
 Some inspections or procedures require that certain parts of the electrical system remain energized at
hazardous voltage during the procedure. Observe all safety messages (Danger, Warning, Caution)
throughout this chapter and the corresponding instruction notices.
 Wear personal protective equipment, recognize potential hazards, and take adequate safety
precautions when performing the procedures outlined in this chapter and the corresponding instruction
notices.
The commissioning procedure assumes that the following conditions are met at the start of the procedure:
 The device is not connected to a power system or a control system.
 A drawout device is in the disconnected position.
 The device is not connected to a communication network.

The results of all observations, tests, adjustments, together with any relevant comments must be recorded
on the appropriate form, if applicable.
Wherever possible, testing must be done without disconnecting or disturbing existing wiring.

Scope
The commissioning procedure applies to the MasterPact MTZ intelligent modular unit (IMU), made up of:
 MasterPact MTZ circuit breaker with its MicroLogic X control unit and optional ULP modules:
 One IFE, EIFE, or IFM communication interface
 One or two IO modules

 MasterPact MTZ switch-disconnector


The associated information, which must be read with this procedure, includes specific schematic diagrams,
connections, and trip levels for the devices covered by this document.

128 DOCA0101EN-04 07/2020


MasterPact MTZ Commissioning

Equipment
The following equipment is required to do the tests detailed in the commissioning procedure:
 Insulation resistance tester
 Multimeter
 A PC equipped with the latest version of EcoStruxure Power Commission software
 A USB to mini USB cable (LV850067SP) to connect the PC to the MicroLogic X control unit

Test Form
A test form (see page 137) is proposed to guide you through the commissioning procedure and to record
the results of the commissioning tests. Each test is described in detail in the Commissioning chapter.
Only do the tests required, depending on the MasterPact MTZ type and the functions in use.

DOCA0101EN-04 07/2020 129


MasterPact MTZ Commissioning

Inspection and MicroLogic X Settings

Visual Inspection

Step Action
1 Record the equipment identification, including substation name, switchboard name, MasterPact MTZ
device type, MicroLogic X model type and serial number, MicroLogic X type, and protection settings.
2 Check that the device is undamaged, correctly mounted, and securely fastened in the switchboard.
3 Check the 3-phase clearance at terminal blocks.
4 Check that there is no debris remaining at the back of the device housing/enclosure.
5 Check that the ground terminals of the device are securely connected with the correct grounding cables.
6 Check that all external surfaces are undamaged.
7 Rectify any non-conformities, if possible. All equipment non-conformities must be referred to asset
management.

Condition of Connections and Auxiliaries


Check device mounting in the switchboard and the tightness of all connections (main connection and
auxiliary wiring).
Check that all auxiliaries and accessories are correctly installed:
 Electrical auxiliaries
 Terminal blocks
 Connections of auxiliary circuits

Check Firmware Compatibility


By using the latest version of EcoStruxure Power Commission software, check that the firmware of the
MicroLogic X control unit and ULP modules in the intelligent modular unit (IMU) are up-to-date, compatible
with each other, and are compatible with the Digital Modules that are installed. The ULP modules are EIFE,
IFE, or IFM communication interfaces, and IO module.

Step Action
1 Connect a PC running EcoStruxure Power Commission software by using a cable connected to the mini
USB port on the front face of the MicroLogic X control unit.
2 Establish a connection. EcoStruxure Power Commission software reads the parameters of the control
unit.
3 On EcoStruxure Power Commission, use the Overall System firmware status/compatibility matrix to
display:
 The installed firmware version of the IMU devices (MicroLogic X control unit and ULP modules).
 The latest firmware version of the devices that are available on the Schneider Electric System
Updates Internet site.
 The recommended actions to get a compatible system.

For more information, refer to EcoStruxure Power Commission Online Help.


4 Follow the recommended actions to get a compatible system.

130 DOCA0101EN-04 07/2020


MasterPact MTZ Commissioning

MicroLogic X Settings

NOTICE
RISK OF UNINTENDED OPERATION
 The device must only be configured and set by qualified personnel, using the results of the installation
protection system study.
 During commissioning of the installation and following any modification, check that the MicroLogic X
configuration and protection function settings are consistent with the results of this study.
 MicroLogic X protection functions are set by default to the minimum value, except for the long time
protection function which is set to the maximum value, by default.
Failure to follow these instructions can result in equipment damage.

Check the settings with EcoStruxure Power Commission software connected to the MicroLogic X control
unit.

Step Action
1 Connect a PC running EcoStruxure Power Commission software by using a cable connected to the mini
USB port on the front face of the MicroLogic X control unit.
2 Establish a connection. EcoStruxure Power Commission software reads the parameters of the control
unit.
3 Check that the settings read in the control unit match the requirements of the application. If necessary,
correct the settings with EcoStruxure Power Commission software:
 The protection settings must be defined according to the installation protection system study.
 Other settings must be defined according to the application.

4 Complete the project and device data.


5 Generate the project report with EcoStruxure Power Commission software, and save or print the project
report as needed.

NOTE: The protection functions available depend on the type of MicroLogic X control unit and its
associated optional Digital Modules.

DOCA0101EN-04 07/2020 131


MasterPact MTZ Commissioning

Tests

Overview
The tests to do while commissioning an MTZ device are described in this section:
 Functional checks
 Check of MCH gear motor (if fitted)
 Check of M2C programmable contacts and IO module (if fitted)
 Check of ESM ERMS switch module (if fitted)
 Check of electrical continuity
 Check of high-voltage insulation
 Check of MicroLogic X Ready LED status
 Test of the tripping mechanism with EcoStruxure Power Commission software
 Test of the tripping mechanism with the test button (MicroLogic 6.0 X or 7.0 X control units)

Only do the tests required, depending on the MasterPact MTZ type and the functions in use, and record
the results on the test form (see page 137). In the event of non-conformance, the result must be recorded
and the MasterPact MTZ device must not be accepted into service.

Functional Checks
Follow this procedure to check the operation of the MasterPact MTZ device and record the results on the
test form.

Step Action
1 Manually charge the mechanism by pulling the spring charging handle down.
2 Close the device. Check the closing of the device in the different control modes and means designed for
the application.
3 Open the device. Check the opening of the device in the different control modes and means designed for
the application.

Check of MCH Gear Motor (If Fitted)


Follow this procedure to check the operation of the MCH gear motor and record the results on the test form.

Step Action
1 Remove the MCH gear motor power supply.
2 Do an opening/closing/opening cycle to discharge the mechanism.
3 With the device in the open position and the mechanism discharged, check electrical continuity between
terminals B1 and B2, and electrical non-continuity between terminals B1 and B3.
4 Manually charge the mechanism.
5 Reconnect the MCH gear motor power supply. The device closes and the mechanism is automatically
charged.
6 Check electrical continuity between terminals B1 and B3.
7 Operate the device several times to check that the spring mechanism automatically recharges after every
closing operation.

Check of M2C Programmable Contacts and IO Module (If Fitted)


Follow this procedure to check the operation of inputs and outputs, and record the results on the test form.

Step Action
1 Connect a PC running EcoStruxure Power Commission software by using a cable to the mini USB port
on the front face of the MicroLogic X control unit.
2 Force the state of both inputs of the M2C programmable contacts and check that the operation is
correct.
3 Force the state of the six digital inputs and three outputs of the one or two IO modules in the IMU to
check the wiring to the circuit breaker. Check that the operation is correct.

132 DOCA0101EN-04 07/2020


MasterPact MTZ Commissioning

Check of ESM ERMS Switch Module (if Fitted)


Follow this procedure to check the operation of the ESM ERMS switch module, and record the results on
the test form.

Step Action
1 Make sure that the MicroLogic X control unit is powered permanently with a 24 Vdc power supply.
2 Connect the ESM ERMS switch module to an external switch with a 24 Vdc or 24—120 Vac power
supply.
3 Activate the ERMS function by moving the external switch to the Engage position. Check that:
 The ERMS LED on the front face of the MicroLogic X control unit lights blue.
 The MicroLogic X control unit display screen is lit with a blue backlight.
 The message ERMS Engaged is displayed on the MicroLogic X control unit display screen.

4 Disengage the ERMS function by moving the external switch to the Disengage position, and check after
3 s that the MicroLogic X control unit returns to its original state.

Check of Electrical Continuity


Follow this procedure to check electrical continuity using a multimeter or continuity checker and record the
results on the test form.

Step Action
1 Close the device.
2 Check electrical continuity, for each of the phases, between the upper and lower power terminals:
 For fixed device: on the power terminals
 For the drawout device: on the chassis power terminals, with the device in the connected position

Check of High-Voltage Insulation


Dielectric tests (high potential and insulation resistance tests) are used to check the insulation between
phases, and insulation between each phase and ground. The equipment used to conduct these tests
creates a high potential voltage (thousands of volts) to check dielectric or insulation integrity.
If included in the MicroLogic X control unit, the voltage power supply (VPS) module connects and
disconnects the control unit with the voltage connections in the circuit breaker.
Before conducting any high-voltage insulation tests, move the VPS module to the disconnected position
and unplug any cables from the mini USB port on the front face of the MicroLogic X control unit. For
information on VPS disconnection, consult the instruction sheet on the Schneider Electric website:
NVE40741.

CAUTION
DETERIORATION OF VPS MODULE
Disconnect the VPS module by pulling it out to the disconnected position before running a dielectric test
on the equipment.
Failure to follow these instructions can result in injury or equipment damage.

Follow this procedure to check insulation resistance and record the results on the test form.

Step Action
1 Disconnect the VPS module and unplug any cables from the mini USB port on the front face of the
MicroLogic X control unit.
2 Close the MasterPact MTZ device.
3 Measure the insulation resistance using a 500 Vdc insulation resistance tester between one of the
phases and the other two phases grounded. Repeat for each phase.
4 Open the MasterPact MTZ device by pressing the opening pushbutton.
5 Measure the insulation resistance using a 500 Vdc insulation resistance tester between one of the
phases and ground, with all other phases grounded. Repeat for each phase.
6 Check that the insulation resistance is above 5 MΩ in each case. If this result is not obtained, contact
your field service representative.

DOCA0101EN-04 07/2020 133


MasterPact MTZ Commissioning

Check of MicroLogic X Ready LED Status


Follow this procedure to check the functioning of the MicroLogic X control unit and record the results on
the test form.

Step Action
1 Provide power to the MicroLogic X control unit, for example, by connecting a PC or Mobile Power Pack
to the mini USB port on the front face.
2 Check that the MicroLogic X Ready LED is flashing green.
The Ready LED flashes green to indicate that:
 The sensors are correctly wired.
 The tripping mechanism is functioning correctly.
 The MicroLogic X control unit is functioning correctly.

3 If the Ready LED is not flashing green, refer to chapter Critical Cases (see page 107).

Test of the Tripping Mechanism With EcoStruxure Power Commission Software


Follow this procedure to test the tripping mechanism of the circuit breaker and record the results on the
test form.

Step Action
1 Close the circuit breaker.
2 Connect a PC running EcoStruxure Power Commission software by using a cable to the mini USB port
on the front face of the MicroLogic X control unit.
3 On EcoStruxure Power Commission software, select the circuit breaker and connect to it.
4 Force the circuit breaker to trip by clicking the Force Trip button on the EcoStruxure Power Commission
screen. This action is password-protected.
5 Check that the circuit breaker is open.
6 Check that the blue fault-trip reset button has popped out.
7 Check that the Isd/Ii LED is on.
8 Check that the SDE contacts have switched.
9 After the test, reset the circuit breaker.

Test of the Tripping Mechanism with the Test Button (MicroLogic 6.0 X and 7.0 X Control Units)
Follow this procedure to test the tripping mechanism of the circuit breaker when fitted with a
MicroLogic 6.0 X or 7.0 X control unit, and record the results on the test form.

Step Action
1 Close the circuit breaker.
2 Use a thin screwdriver to briefly push in (<1 s) the test button on the control unit.
3 Check that the circuit breaker is open.
4 Check that the blue fault-trip reset button has popped out.
5 Check that the Ig/IΔn LED is on.
6 Check that the SDE contacts have switched.
7 After the test, reset the circuit breaker.

134 DOCA0101EN-04 07/2020


MasterPact MTZ Commissioning

Communication Tests

Communication Network Test


EcoStruxure Power Commission software can be used to test the communication network between all the
communicating devices of the project:
 Circuit breakers connected to the Ethernet network through an IFE or EIFE Ethernet interface.
 Circuit breakers connected to a Modbus serial line network through an IFM interface stacked to an IFE
Ethernet server.
 Circuit breakers connected to a Modbus serial line network from an IFM interface.

Step Action
1 Connect a PC running EcoStruxure Power Commission software by using an RJ45 cable to a
communication network, on the IFE or EIFE Ethernet interface, or IFM interface, for example.
2 In EcoStruxure Power Commission software, at Create report → Communication test & report, select
devices to be tested from the list of communicating devices defined in the project.
3 Click Run test. All selected devices are tested.
4 Results are displayed at the end of the test.
5 Generate the communication test report with EcoStruxure Power Commission software, and save or
print the project report as needed.

Remote Control Tests


If the MasterPact MTZ circuit breakers can be opened and closed remotely through the communication
network, use the following tests to check for the correct operation of remote control:

Step Action
1 Connect a PC running EcoStruxure Power Commission software by using an RJ45 cable to a
communication network, on the IFE or EIFE Ethernet interface, or IFM interface, for example.
2 Check that the control mode is set to Auto: Remote.
3 In EcoStruxure Power Commission software, select the circuit breaker and connect to it.
4 Click the Device tab to access the Open and Close buttons.
5 Check that it is possible to open and close the MasterPact MTZ device remotely. These actions are
password-protected.

DOCA0101EN-04 07/2020 135


MasterPact MTZ Commissioning

Final Checks and Reporting

Final Checks
After completing the commissioning tests, check the following:

Step Action
1 Check that connections are made with the correct tightening torque, that there are no tools or objects
inside the equipment, and that all devices, doors, and protective covers are in position.
2 Check that the device is off (open position) and the closing spring is charged.

Project Report Generated by EcoStruxure Power Commission Software


EcoStruxure Power Commission software generates a project report with a list of the circuit breakers for
that project. For each MasterPact MTZ circuit breaker it provides the following information:
 The circuit breaker identification data
 The MicroLogic X identification data, including the list of Digital Modules installed
 The list of accessories including internal accessories (for example, M2C programmable contacts), and
external modules (for example, IO module)
 The protection settings for the MicroLogic X control unit
 The alarm settings
 The IFE, EIFE, or IFM communication interface settings

Communication Test Report Generated by EcoStruxure Power Commission Software


EcoStruxure Power Commission software performs a communication test and generates a report of the
test. For each communicating device it provides the following information:
 The name and type of the device
 The type of communication
 The address of the device
 The status of the connection

136 DOCA0101EN-04 07/2020


MasterPact MTZ Commissioning

MasterPact MTZ Test Form

How to Use the Test Form


Print this test form to record the results of the commissioning tests.
Check the box (✔) when the test has been made and is conclusive.
This test form, the project report, and the communication test report should be left on-site in a plastic wallet
and in an easily accessible, safe place.
Each test is described in detail in the Commissioning chapter.
Only do the tests required, depending on the MasterPact MTZ type and the functions in use.
When all the tests have been satisfactorily completed, sign and date the test form.

Identification

Workstation Tests conducted on: By:

Signature:

Substation name Comments:


Substation number
Switchboard name
Voltage

MasterPact MTZ device


Manufacturer Schneider Electric
Type of MasterPact MTZ device
Serial number
Hardware version

MicroLogic X control unit


MicroLogic X type CT ratio
Firmware version

Preliminary Checks

Type of check (✔)


Visual inspection satisfactory (for example, no visible signs of damage).
Grounding satisfactory.
Connection tightness checked.
Firmware compatibility satisfactory.
MicroLogic X settings applied.
Project report generated.

DOCA0101EN-04 07/2020 137


MasterPact MTZ Commissioning

Functional and Interlock Checks

Type of check (✔)


Mechanism charges when spring charging handle is pulled.
MasterPact MTZ device closes.
MasterPact MTZ device opens.
Mechanism charges automatically after closing when the device is fitted with an MCH gear motor.
M2C programmable contacts function correctly.
IO module functions correctly.
ESM ERMS switch module functions correctly.
Interlocking systems of the circuit breaker function correctly.
Interlocking systems between two or three circuit breakers function correctly.

Electrical Continuity Check

MasterPact MTZ device Tested terminals Electrical continuity


status Incoming side Outgoing side
Closed L1 L1 Ω
Closed L2 L2 Ω
Closed L3 L3 Ω

MasterPact MTZ Insulation Test

MasterPact MTZ device Terminals under test Voltage Insulation resistance


status
Closed L1, with L2 and L3 grounded 500 Vdc MΩ
Closed L2, with L1 and L3 grounded 500 Vdc MΩ
Closed L3, with L1 and L2 grounded 500 Vdc MΩ
Open L1, with L1, L2, L3 grounded on the other side 500 Vdc MΩ
Open L2, with L1, L2, L3 grounded on the other side 500 Vdc MΩ
Open L3, with L1, L2, L3 grounded on the other side 500 Vdc MΩ

Check of MicroLogic X Ready LED

Type of check (✔)


MicroLogic X Ready LED flashes green.

Test of the Tripping Mechanism for MicroLogic X Control Units

Type of check (✔)


With the circuit breaker closed, force the circuit breaker to trip using EcoStruxure Power Commission software.
Check that the circuit breaker is open.
Check that the blue fault-trip reset button has popped out.
Check that the Isd/Ii LED is on.
Check that the SDE contacts have switched.

Test of the Tripping Mechanism for MicroLogic 6.0 X and 7.0 X Control Units

Type of check (✔)


With the circuit breaker closed, briefly press (<1 s) the test button on the front face of the control unit.
Check that the circuit breaker is open.
Check that the blue fault-trip reset button has popped out.
Check that the Ig/IΔn LED is on.
Check that the SDE contacts have switched.

138 DOCA0101EN-04 07/2020


MasterPact MTZ Commissioning

Communication Tests

Type of check (✔)


Communication network tested.
Communication test report generated.
Remote opening and closing tested.

Final Checks

Type of check (✔)


All doors and protected covers are in position.
The device is off (open position) and the closing spring is charged.

DOCA0101EN-04 07/2020 139


MasterPact MTZ Commissioning

140 DOCA0101EN-04 07/2020


MasterPact MTZ2/MTZ3
MasterPact MTZ Troubleshooting
DOCA0101EN-04 07/2020

Chapter 5
MasterPact MTZ Troubleshooting

MasterPact MTZ Troubleshooting

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Introduction to Troubleshooting 142
Troubleshooting: Chassis Operation 144
Troubleshooting: Unexpected Tripping 145
Troubleshooting: Mechanical Control Operations 146
Troubleshooting: Electrical Control Operations 147
Troubleshooting: Control Operations from EcoStruxure Power Device App 149
Troubleshooting: Control Operations from IO Module 151
Troubleshooting: Control Operations from EcoStruxure Power Commission Software 152
Troubleshooting: Control Operations from IFE/EIFE Webpages 154
Troubleshooting: Control Operations from Communication Network 156
Troubleshooting: Control Operations from FDM128 Display 158

DOCA0101EN-04 07/2020 141


MasterPact MTZ Troubleshooting

Introduction to Troubleshooting

Presentation
This chapter contains information for troubleshooting problems in a working system. It assumes that the
system is correctly installed and that all the commissioning tests (see page 127) have been completed
successfully. The troubleshooting operations are described under the following headings:
 Chassis operation
 Unexpected tripping
 Mechanical control operations
 Electrical control operations
 Control operations from EcoStruxure Power Device app
 Control operations from IO module
 Control operations from EcoStruxure Power Commission software
 Control operations from IFE/EIFE webpages
 Control operations from communication network
 Control operations from FDM128 display

Layer Model
When troubleshooting the device, it is useful to consider a layer model. There are four layers:
 Communication network
 Direct connection
 Electrical
 Mechanical

The following diagram shows the layers in the device:

Communication network

Direct communication

Electrical

Mechanical

If the troubleshooting actions for a layer are not successful, go to the next layer until you reach the
Mechanical layer. If you cannot solve the problem after troubleshooting the Mechanical layer, contact your
field service representative.

142 DOCA0101EN-04 07/2020


MasterPact MTZ Troubleshooting

Troubleshooting with Assistance


Assistance for troubleshooting is provided by the MasterPact Operation Assistant Digital Module.
The MasterPact Operation Assistant Digital Module helps to close a circuit breaker after a trip or an
opening.
The following features are available:
 Ready-to-close status
 Reset (if applicable)
 Spring charging (if applicable)
 Diagnostics on related reclosing information, for example, no power supply to MX opening voltage
release, MN undervoltage release, or MCH gear motor
Refer to DOCA0102EN MasterPact MTZ - MicroLogic X Control Unit - User Guide for more information
about downloading Digital Modules.

Maintenance of the Device


Schneider Electric recommends a preventive maintenance program to ensure that devices retain the
operating and technical characteristics specified in the catalogs during their service life. Maintenance must
be carried out by trained and qualified personnel.
For information about the preventive maintenance program and maintenance procedures, refer to
DOCA0099EN MasterPact MTZ - IEC Circuit Breakers and Switch-Disconnectors - Maintenance Guide.

DOCA0101EN-04 07/2020 143


MasterPact MTZ Troubleshooting

Troubleshooting: Chassis Operation

Definition
Chassis operation includes the following:
 Racking in and racking out the drawout device
 Locking and unlocking the chassis

Troubleshooting

Problem description Probable causes Solutions


Impossible to insert the A padlock or keylock is present on the Disable the locking function.
racking handle in connected, chassis or a door interlock is present.
test, or disconnected
position.
Impossible to turn the The position release button is not pushed Push the position release button.
racking handle. in and so the racking handle cannot be
rotated.
Device cannot be removed Device is not in the disconnected position. Turn the racking handle until the device is
from chassis. in the disconnected position and the
position release button pops out.
Rails are not completely extended. Pull out the rails of the chassis.
Device cannot be connected Chassis and device do not match Check that the chassis corresponds with
(racked in). (mismatch protection). the device.
Safety shutters are locked. Remove the locks.
Disconnecting contact clusters are Reposition the disconnecting contact
incorrectly positioned. clusters.
Chassis is locked in the disconnected Disable the chassis locking function.
position.
The position release button is not pushed Push the position release button.
in and so the racking handle cannot be
rotated.
Device has not been sufficiently inserted Insert the device completely so that it is
in the chassis. engaged in the racking mechanism.
Device cannot be locked in Device is not in the correct position. Check the device position by checking that
the disconnected position. the position release button is popped out.
Racking handle is still in the chassis. Remove the racking handle and store it.
Device cannot be locked in Locking in any position is not enabled. Adapt the chassis locking mechanism so
the connected, test, or that the chassis can be locked in any
disconnected position. position (see page 88).
Device is not in the correct position. Check the device position by checking that
the position release button is out.
Racking handle is still in the chassis. Remove the racking handle and store it.
The racking handle cannot Rails are not completely in. Push the rails all the way in.
be inserted to connect or
disconnected the device.
The right-hand rail (chassis Racking handle is still in the chassis. Remove the racking handle and store it.
alone) or the device cannot
be drawn out.

144 DOCA0101EN-04 07/2020


MasterPact MTZ Troubleshooting

Troubleshooting: Unexpected Tripping

Definition
Unexpected tripping is tripping that is not caused by a protection function during normal operation or by
tests.

Troubleshooting

Problem description Symptom Probable causes Solutions


Device opened The blue fault-trip Drop in voltage to below the Check the voltage and the MN
without any over- reset button is not threshold detected by MN supply circuit (V > 0.85 Un).
current electrical fault. popped out and no trip undervoltage release.
cause LED is lit. An order (for example load- Check the parameters of the
shedding) sent to the MX device that sent the order.
opening voltage release by
another device.
Unnecessary opening order from Determine the origin of the order
the MX opening voltage release. and cancel it.
Device trips in a The blue fault-trip Thermal memory is still active Check whether there is still an
shorter time than reset button is popped and current on the line is above overload on the line. If necessary,
expected after attempt out and the Ir LED is the Ir threshold. make a correction. For details of
to close the device. lit. thermal memory, refer to
DOCA0102EN
MasterPact MTZ - MicroLogic X
Control Unit - User Guide.
The blue fault-trip ERMS is active so device opens The ERMS function
reset button is popped at lower protection settings. (see page 51) applies reduced
out, the Ir or Isd LED is protection settings for use during
lit, and the ERMS LED maintenance. Check whether
is lit. maintenance is in progress. If
ERMS is no longer necessary,
disengage it to revert to normal
protection settings.
– The tripping curves (A or B) have This might be a change in
been modified, or the control unit intended behavior so not a
is not set to the usual set of problem. Check the tripping
tripping curves (A or B). curve definitions are describing
the intended behavior. Modify the
definitions if necessary.
Immediate tripping The blue fault-trip Transient overcurrent when  Modify the distribution system
after an attempt to reset button is popped closing. or the control unit settings.
close the device. out and the Ir LED is  Check the condition of the
lit. device before putting it back
into service.
Immediate tripping – Closing on a short-circuit. Refer to MasterPact MTZ critical
after an attempt to cases (see page 107).
close the device with
activation of the blue
fault-trip reset button.
Nuisance tripping of – Blue fault-trip reset button is not Push in the blue fault-trip reset
the device with pushed-in completely. button completely.
activation of the blue
– Transient overcurrent detected Intended behavior. If necessary,
fault-trip reset button.
on the line and fast adjust the settings in EcoStruxure
instantaneous trip setting is Power Commission software.
active in EcoStruxure Power
Commission software.

DOCA0101EN-04 07/2020 145


MasterPact MTZ Troubleshooting

Troubleshooting: Mechanical Control Operations

Definition
Mechanical control operations are operations that are made using the opening or closing pushbuttons.

Device Cannot be Closed by Using the Mechanical Closing Pushbutton

Symptom Probable causes Solutions


The blue fault-trip reset button is The blue fault-trip reset button has  Clear the fault.
popped out. not been reset.  Push the blue fault-trip reset button.

– Device is padlocked or keylocked in Unlock the device.


the open position.
– Device is interlocked mechanically  Check the position of the other device
in a mechanical interlocking in the changeover system.
system.  Modify the situation to release the
interlock.
The closing spring and ready-to- Stored energy mechanism is not  Charge the mechanism manually.
close indicator shows that the charged.  If the device is equipped with an MCH
mechanism is discharged. gear motor, check the supply of power
to the motor. If the problem persists,
replace the MCH gear motor.
.
The closing spring and ready-to- MX opening voltage release is As there is an opening order, determine
close indicator shows that the permanently powered. the origin of the order. The order must be
mechanism is charged but the canceled before the device can be closed.
device is not ready to close.
MN undervoltage release is not As there is an opening order, determine
powered due to an opening order. the origin of the order. The order must be
canceled before the device can be closed.
MN undervoltage release is not Check the voltage and the MN supply
powered due to insufficient voltage circuit (V > 0.85 Un).
power supply. If the problem persists, replace the MN
undervoltage release.
Recurring undervoltage trip. The measured voltage remains at Set the undervoltage behavior parameter,
0 V. Vmin behavior, to Force to Off when CB is
open. For more information, refer to
DOCA0102EN MasterPact MTZ -
MicroLogic X Control Unit - User Guide.
The position release button on the Device is not correctly connected. Terminate racking in (connection) of the
chassis of the drawout device is device, making sure that it is fully inserted
pushed in. in the chassis, to the connected position.
Check that the position release button is
popped out.

Device Cannot be Opened by Using the Mechanical Opening Pushbutton

Probable causes Solutions


Operating mechanism incident or welded contacts. Contact your field service representative.

146 DOCA0101EN-04 07/2020


MasterPact MTZ Troubleshooting

Troubleshooting: Electrical Control Operations

Definition
Electrical control operations are operations that are made by an electrical order through a voltage release
or by an external pushbutton that is directly connected to a voltage release.

Troubleshooting Voltage Releases


Troubleshooting depends on the type of voltage release, as follows:
 For communicating voltage releases, consult the MicroLogic X event messages and then refer to
MasterPact MTZ Critical Cases (see page 116)
 For standard voltage releases, follow the troubleshooting instructions given in the following tables. If the
problem persists, replace the voltage release.

Device Cannot be Closed by Using an External Pushbutton/Electrical Order

Symptom Probable causes Solutions


– Device is padlocked or keylocked in Unlock the device.
the open position.
– Electrical closing order not executed Check the voltage and the XF supply
by the XF closing voltage release due circuit (0.85–1.1 Un).
to insufficient voltage power supply. If the problem persists, replace the XF
closing voltage release.
The closing spring and ready-to- MX opening voltage release is As there is an opening order,
close indicator shows that the permanently powered. determine the origin of the order. The
mechanism is charged but the device order must be canceled before the
is not ready to close. device can be closed.
MN undervoltage release is not As there is an opening order,
powered due to an opening order. determine the origin of the order. The
order must be canceled before the
device can be closed.
MN undervoltage release is not Check the voltage and the MN supply
powered due to insufficient voltage circuit (V > 0.85 Un).
power supply. If the problem persists, replace the MN
undervoltage release.
– XF closing voltage release is  Remove the power supply to the
continuously supplied, but device was XF closing voltage release.
not ready-to-close when the closing  Only if the device is ready-to-close,
order was sent (XF closing voltage send the closing order again via the
release is not wired in series with PF XF closing voltage release.
ready-to-close contact).

Device Cannot be Opened by Using an External Pushbutton/Electrical Order

Probable causes Solutions


Opening order is not executed by the MN undervoltage Drop in voltage insufficient or residual voltage (V
release. > 0.35 Un) across the terminals of the MN undervoltage
release.
If the problem persists, replace the MN undervoltage
release.
Opening order is not executed by the MX opening voltage Check the voltage and the MX supply circuit (0.7–1.1 Un).
release. If the problem persists, replace the MX opening voltage
release.

Device Cannot be Reset by Using RES Electrical Remote Reset

Symptom Probable causes Solutions


The blue fault-trip reset button is Insufficient supply voltage for the RES Check the voltage and the RES supply
popped out. electrical remote reset. circuit (0.7–1.1 Un).
If the problem persists, replace the
RES electrical remote reset.

DOCA0101EN-04 07/2020 147


MasterPact MTZ Troubleshooting

Additional Checks
If the troubleshooting actions described above do not work, refer to the troubleshooting information for
Mechanical Control Operations (see page 146).

148 DOCA0101EN-04 07/2020


MasterPact MTZ Troubleshooting

Troubleshooting: Control Operations from EcoStruxure Power Device App

Definition
Control operations include commands to open and close the device from the EcoStruxure Power Device
app.

Device Cannot be Controlled from the EcoStruxure Power Device App

Problem description Symptom Probable causes Solutions


Device cannot be opened or – The device control mode Change the control mode to
closed. (see page 39) is set to Auto (see page 42).
Manual.
– The device control mode Change the control mode to
(see page 39) is set to Auto Auto Local (see page 42).
Remote.
The EcoStruxure Power The MasterPact Operation Use EcoStruxure Power
Device app displays a Assistant Digital Module is Commission software to
message to download the not installed. download and install the
MasterPact Operation MasterPact Operation
Assistant Digital Module. Assistant Digital Module in
the MicroLogic X control
unit.
The EcoStruxure Power The EcoStruxure Power Update the EcoStruxure
Device app displays a Device app on the Power Device app.
message indicating a smartphone is not
firmware version mismatch. compatible with the
firmware version of the
MicroLogic X control unit.
Device cannot be closed. – The close command is Enable the close command
inhibited by the IO module. by using the selector switch
wired on a digital input of the
IO module (I=1).
The close command is In EcoStruxure Power
inhibited by a command Commission software, in the
from the communication Device Check-up →
network or EcoStruxure Devices menu, change the
Power Commission value of the Remote Close
software. Breaker Inhibited parameter
from Enabled by
communication to Disabled.

Inhibit Closing by IO Module is Not Operational

Problem description Probable cause Solution


Device can be closed while selector The MicroLogic X setting Breaker In EcoStruxure Power Commission
switch wired on a digital input of the closing by digital input is disabled. software, in the General menu, in
IO module is set to Inhibit (I4=0). Breaker Closing Inhibition, change the
value of the Allow control by a digital
input parameter to Enable.

Device Cannot be Controlled from the EcoStruxure Power Device App Connected Through Bluetooth

Problem description Probable causes Solutions


The Bluetooth LED does not light up The Bluetooth function is not enabled Enable Bluetooth communication in
when you press the Bluetooth in the MicroLogic X control unit. the MicroLogic X control unit.
activation pushbutton on the
The MicroLogic X control unit is not Check the power supply of the
MicroLogic X control unit. powered. MicroLogic X control unit.
The Bluetooth connection was The smartphone has been moved out Place the smartphone within the
established but the signal is lost. of range. range for Bluetooth and establish a
new connection.
The Bluetooth LED is blinking on the A smartphone is already connected to Check whether another smartphone
control unit but you cannot see its ID the MicroLogic X control unit. within range is also connected to the
number in the list of devices available. control unit.

DOCA0101EN-04 07/2020 149


MasterPact MTZ Troubleshooting

Additional Checks
If the troubleshooting actions described above do not work, the problem might be in the mechanical or
electrical operations of the device. Refer to the troubleshooting information for Mechanical Control
Operations (see page 146) and Electrical Control Operations (see page 147).

150 DOCA0101EN-04 07/2020


MasterPact MTZ Troubleshooting

Troubleshooting: Control Operations from IO Module

Definition
Control operations include commands to open and close the device from the IO module with the Breaker
Operation predefined application.
For information about control operations from the IO module, refer to DOCA0055EN Enerlin'X IO -
Input/Output Application Module for One IEC Circuit Breaker - User Guide.

Device Cannot be Controlled from the IO Module

Problem description Symptom Probable causes Solutions


Device cannot be opened – The IO module is not Configure the IO module for
or closed. configured for Breaker Breaker Operation
Operation predefined predefined application 2, by
application 2. using the rotary switch and
pressing the Test/Reset
button for 5 seconds to
validate the configuration.
– The device control mode Change the control mode to
(see page 39) is set to Auto (see page 42).
Manual.
Local open or close orders The device control mode Change the control mode to
wired on digital inputs I5 or (see page 39) is set to Local (see page 42) by using
I6 do not control the device. Remote. the control mode selector
switch wired on the digital
input I1 of the IO module
(I1=0).
Remote open or close The device control mode Change the control mode to
orders wired on digital (see page 39) is set to Remote (see page 42) by
inputs I2 or I3 do not control Local. using the control mode
the device. selector switch wired on the
digital input I1 of the IO
module (I1=1).
Device cannot be closed. – The close command is Enable the close command
inhibited by the IO module by using the selector switch
configured in the Breaker wired on the digital input I4 of
Operation predefined the IO module (I4=1).
application 2.
– The close command is In EcoStruxure Power
inhibited by a command Commission software, in the
from the communication Device Check-up → Devices
network or EcoStruxure menu, change the value of
Power Commission the Remote Close Breaker
software. Inhibited parameter from
Enabled by communication
to Disabled.

Inhibit Closing by IO Module is Not Operational

Problem description Probable cause Solution


Device can be closed while selector The MicroLogic X setting Breaker In EcoStruxure Power Commission
switch wired on a digital input of the closing by digital input is disabled. software, in the General menu, in
IO module is set to Inhibit (I4=0). Breaker Closing Inhibition, change the
value of the Allow control by a digital
input parameter to Enable.

Additional Checks
If the troubleshooting actions described above do not work, the problem might be in the mechanical or
electrical operations of the device. Refer to the troubleshooting information for Mechanical Control
Operations (see page 146) and Electrical Control Operations (see page 147).

DOCA0101EN-04 07/2020 151


MasterPact MTZ Troubleshooting

Troubleshooting: Control Operations from EcoStruxure Power Commission Software

Definition
Control operations include commands to open and close the device from EcoStruxure Power Commission
software.

Device Cannot be Controlled from EcoStruxure Power Commission Software Connected to a Mini USB Port

Problem description Symptom Probable causes Solutions


Device cannot be opened or EcoStruxure Power The device control mode Change the control mode to
closed. Commission message: (see page 39) is set to Auto (see page 42).
Breaker operation not Manual.
successful: actuator is in
manual mode. Remote
breaker commands are not
allowed
EcoStruxure Power The device control mode Change the control mode to
Commission message: (see page 39) is set to Auto Auto Local (see page 42).
Breaker operation not Remote.
successful: Operation
mode is Remote
EcoStruxure Power Insufficient access rights. Log in to EcoStruxure Power
Commission software does Commission software with
not display the relevant Administrator rights.
option.
EcoStruxure Power The password is incorrect: Enter the password again.
Commission message: error entering password or In the case of insufficient
Insufficient user rights the user has insufficient access rights, check the
(incorrect password) access rights. password validity with the
system administrator.
Device cannot be closed. EcoStruxure Power The close command is Enable the close command
Commission message: inhibited by the IO. by using the selector switch
Breaker operation not wired on a digital input of the
successful: The requested IO module (I=1).
action is not allowed as it
The close command is In EcoStruxure Power
has been previously
inhibited by a command Commission software, in the
inhibited from the communication Device Check-up →
network or EcoStruxure Devices menu, change the
Power Commission value of the Remote Close
software. Breaker Inhibited parameter
from Enabled by
communication to Disabled.

Inhibit Closing by IO Module is Not Operational

Problem description Probable cause Solution


Device can be closed while selector The MicroLogic X setting Breaker In EcoStruxure Power Commission
switch wired on a digital input of the closing by digital input is disabled. software, in the General menu, in
IO module is set to Inhibit (I4=0). Breaker Closing Inhibition, change the
value of the Allow control by a digital
input parameter to Enable.

152 DOCA0101EN-04 07/2020


MasterPact MTZ Troubleshooting

Device Cannot be Controlled from EcoStruxure Power Commission Software Connected by IFE, EIFE, or IFM Interface

Symptom Probable causes Solutions


EcoStruxure Power Commission The remote control commands are Move the locking pad on the front of
message: disabled by the locking pad on the the IFE interface to the Unlocked
Breaker operation not successful: front of the IFE interface. position.
Either device is unable to execute the
The EIFE interface is locked by In EcoStruxure Power Commission
operation or communication interface
EcoStruxure Power Commission software, in the Configure →
is locked
software. Communication menu, change the
value of the Remote Padlock Position
parameter from Locked to Unlocked.
EcoStruxure Power Commission The device control mode Change the control mode to Auto
message: (see page 39) is set to Manual. (see page 42).
Breaker operation not successful:
actuator is in manual mode. Remote
breaker commands are not allowed
EcoStruxure Power Commission Insufficient access rights. Log in to EcoStruxure Power
software does not display the Commission software with
relevant option. Administrator rights.
EcoStruxure Power Commission The device control mode Change the control mode to Auto
message: (see page 39) is set to Auto Local. Remote (see page 42).
Breaker operation is not successful:
Operation mode is Local (Operation
via remote control is not allowed)
EcoStruxure Power Commission The password is incorrect: error Enter the password again.
message: entering password or the user has In the case of insufficient access
Insufficient user rights: Incorrect insufficient access rights. rights, check the password validity
password with the system administrator.

Additional Checks
If the troubleshooting actions described above do not work, the problem might be in the mechanical or
electrical operations of the device. Refer to the troubleshooting information for Mechanical Control
Operations (see page 146) and Electrical Control Operations (see page 147).

DOCA0101EN-04 07/2020 153


MasterPact MTZ Troubleshooting

Troubleshooting: Control Operations from IFE/EIFE Webpages

Definition
Control operations include commands to open and close the device from IFE or EIFE webpages.
For information about control operations from IFE or EIFE webpages, refer to the following guides:
 DOCA0084EN Enerlin'X IFE - Ethernet Switchboard Server - User Guide
 DOCA0142EN Enerlin'X IFE - Ethernet Interface for One IEC Circuit Breaker - User Guide
 DOCA0106EN Enerlin'X EIFE - Embedded Ethernet Interface for One MasterPact MTZ Drawout Circuit
Breaker - User Guide

Device Cannot be Controlled from IFE or EIFE Webpages

Problem description Symptom Probable causes Solutions


Device cannot be opened or The Close and Open Application control is not Enable application control
closed. buttons are not displayed enabled in the IFE interface. by pressing the Test button
on the webpage. on the front of the IFE
interface for 10–15 s.
The user is not logged in as Log in as Administrator.
Administrator.
Message on webpage: The device control mode Change the control mode to
Breaker operation not (see page 39) is set to Auto (see page 42).
successful: actuator is in Manual.
manual mode. Remote
breaker commands are not
allowed
Message on webpage: The device control mode Change the control mode to
Breaker operation is not (see page 39) is set to Auto Auto Remote
successful: Operation Local. (see page 42).
mode is Local (Operation
via remote control is not
allowed).
Message on webpage: The remote control Move the locking pad on the
Close has failed. commands are disabled by front of the IFE interface to
the locking pad on the front the Unlocked position.
NOTE: There is no
of the IFE interface.
message if opening action
fails. The EIFE interface is locked In EcoStruxure Power
by EcoStruxure Power Commission software, in
Commission software. the Configure →
Communication menu,
change the value of the
Remote Padlock Position
parameter from Locked to
Unlocked.
Device cannot be closed. Message on webpage: The close command is Enable the close command
Close has failed. inhibited by the IO module. by using the selector switch
wired on a digital input of
the IO module (I=1).
The close command is In EcoStruxure Power
inhibited by a command Commission software, in
from the communication the Device Check-up →
network or EcoStruxure Devices menu, change the
Power Commission value of the Remote Close
software. Breaker Inhibited parameter
from Enabled by
communication to Disabled.

Inhibit Closing by IO Module is Not Operational

Problem description Probable cause Solution


Device can be closed while selector The MicroLogic X setting Breaker In EcoStruxure Power Commission
switch wired on a digital input of the closing by digital input is disabled. software, in the General menu, in
IO module is set to Inhibit (I4=0). Breaker Closing Inhibition, change the
value of the Allow control by a digital
input parameter to Enable.

154 DOCA0101EN-04 07/2020


MasterPact MTZ Troubleshooting

Additional Checks
If the troubleshooting actions described above do not work, the problem might be in the mechanical or
electrical operations of the device. Refer to the troubleshooting information for Mechanical Control
Operations (see page 146) and Electrical Control Operations (see page 147).

DOCA0101EN-04 07/2020 155


MasterPact MTZ Troubleshooting

Troubleshooting: Control Operations from Communication Network

Definition
Control operations include commands to open and close the device from the communication network.
For information about control operations from the communication network, refer to the following guides:
 DOCA0105EN MasterPact MTZ - Modbus Communication Guide
 DOCA0162EN MasterPact MTZ - IEC 61850 Communication Guide

Device Cannot be Controlled with a Remote Controller Connected from IFE, EIFE, or IFM Interface

Problem description Symptom Probable causes Solutions


Device cannot be opened or – The device control mode Change the control mode to
closed. (see page 39) is set to Auto (see page 42).
Manual.
– The device control mode Change the control mode to
(see page 39) is set to Auto Auto Remote (see page 42).
Local.
– The remote control Move the locking pad on the
commands are disabled by front of the IFE interface to
the locking pad on the front the Unlocked position.
of the IFE interface.
– The EIFE interface is locked In EcoStruxure Power
by EcoStruxure Power Commission software, in the
Commission software. Configure →
Communication menu,
change the value of the
Remote Padlock Position
parameter from Locked to
Unlocked.
The opening or closing The password in the Send the opening or closing
command is returned with opening or closing is command with a valid
Modbus error code 01. incorrect or the user has password.
insufficient access rights. In the case of insufficient
access rights, check the
password validity with the
system administrator.
If the password is lost, refer
to DOCA0105EN
MasterPact MTZ - Modbus
Communication Guide.
Device cannot be closed. – The close command is Enable the close command
inhibited by the IO module. by using a selector switch
wired on a digital input of the
IO module (I=1).
The close command is Use the Set Close Breaker
inhibited by a command Inhibition command to
from the communication enable the close order.
network or EcoStruxure
Power Commission
software.

Inhibit Closing by IO Module is Not Operational

Problem description Probable cause Solution


Device can be closed while selector The MicroLogic X setting Breaker In EcoStruxure Power Commission
switch wired on a digital input of the closing by digital input is disabled. software, in the General menu, in
IO module is set to Inhibit (I4=0). Breaker Closing Inhibition, change the
value of the Allow control by a digital
input parameter to Enable.

156 DOCA0101EN-04 07/2020


MasterPact MTZ Troubleshooting

Additional Checks
If the troubleshooting actions described above do not work, the problem might be in the mechanical or
electrical operations of the device. Refer to the troubleshooting information for Mechanical Control
Operations (see page 146) and Electrical Control Operations (see page 147).

DOCA0101EN-04 07/2020 157


MasterPact MTZ Troubleshooting

Troubleshooting: Control Operations from FDM128 Display

Definition
Control operations include commands to open and close the device from the FDM128 display.
For information about control operations from the FDM128 display, refer to DOCA0037EN
Enerlin’X FDM128 - Ethernet Display for Eight Devices - User Guide.

Device Cannot be Controlled from the FDM128 Display

Symptom Probable causes Solutions


On FDM128 display, in the Device You are not logged in as Log in to the FDM128 display as
view, the Control submenu is grayed Administrator. Administrator.
out.
The password is incorrect: error Enter a valid password.
entering password or the user has In the case of insufficient access
insufficient access rights. rights, check the password validity
with the system administrator.

Additional Checks
If the troubleshooting actions described above do not work, the problem might be linked to the
communication network. Refer to the troubleshooting information for the communication network
(see page 156).

158 DOCA0101EN-04 07/2020


MasterPact MTZ2/MTZ3
Schneider Electric Green Premium™
DOCA0101EN-04 07/2020

Chapter 6
Schneider Electric Green Premium™ Ecolabel

Schneider Electric Green Premium™ Ecolabel

Schneider Electric Green Premium™ Ecolabel

Description
Green Premium by Schneider Electric is a label that allows you to develop and promote an environmental
policy while preserving your business efficiency. This ecolabel is compliant with up-to-date environmental
regulations.

Accessing Green Premium


Green Premium data on labeled products can be accessed online through any of the following ways:
 By navigating to the Green Premium page on the Schneider Electric website.
 By scanning the QR code displayed in the following image:

Checking Products Through the Schneider Electric Website


To check the environmental criteria of a product using a PC or smartphone, follow these steps:

Step Action
1 From www.se.com, select Support → Green Premium.
2 Click Find Green Premium Offers to open the search tool webpage.
3 Fill in the fields:
 Enter the commercial reference or product range of the product to search for.
 Optional: Enter the manufacturing date code of the product with format YYWW. By default, this field is
filled with the date of the search.
4 To search for several products simultaneously, click the Add product button, and then fill in the fields.
5 Click Check product(s) to generate a report of the environmental criteria available for the products with
the entered commercial references.

Environmental Criteria
The Green Premium ecolabel provides documentation on the following criteria about the environmental
impact of the products:
 RoHs: European Union Restriction of Hazardous Substances (RoHS) directive.
 REACh: European Union Registration, Evaluation, Authorization, and Restriction of Chemicals
regulation.
 PEP: Product Environmental Profile.
 EoLI: End of Life Instructions.

RoHs
Schneider Electric products are subject to RoHS requirements at a worldwide level, even for the many
products that are not required to comply with the terms of the regulation. Compliance certificates are
available for products that fulfill the criteria of this European initiative, which aims to eliminate hazardous
substances.

DOCA0101EN-04 07/2020 159


Schneider Electric Green Premium™

REACh
Schneider Electric applies the strict REACh regulation on its products at a worldwide level, and discloses
extensive information concerning the presence of SVHC (Substances of Very High Concern) in all of these
products.

PEP
Schneider Electric publishes complete set of environmental data, including carbon footprint and energy
consumption data for each of the life cycle phases on all of its products, in compliance with the
ISO 14025 PEP ecopassport program. PEP is especially useful for monitoring, controlling, saving energy,
and/or reducing carbon emissions.

EoLI
These instructions provide:
 Recyclability rates for Schneider Electric products.
 Guidance to mitigate personnel hazards during the dismantling of products and before recycling
operations.
 Part identification for recycling or for selective treatment, to mitigate environmental hazards/incompati-
bility with standard recycling processes.

160 DOCA0101EN-04 07/2020


DOCA0101EN-04

Schneider Electric Industries SAS As standards, specifications and designs change from time to time, please ask for confirmation
35, rue Joseph Monier of the information given in this publication.
CS30323
F - 92506 Rueil Malmaison Cedex

www.schneider-electric.com 07/2020

You might also like