NFPA-13 Reviewer
NFPA-13 Reviewer
3. Fire Protection Automatic Sprinkler Must comply with NFPA 13 for design,
Systems Systems installation, and maintenance.
4. Hazardous Storage and Handling of Must comply with NFPA 30 for safe storage
Materials Flammable Liquids and use.
Emergency Lighting and Must comply with NFPA 101 for occupant
Egress safety during an emergency.
6. Life Safety Specifies minimum exit widths, exit signs,
Means of Egress
Measures and emergency escape routes.
7. Fire Prevention Open Flame and Smoking Restricts smoking and open flames in high-
& Inspection Regulations risk areas.
Minimum Distance
6 ft (1.8 m)
Between Sprinklers
Additional Water Flow Light Hazard: 100 gpm (379 L/min) Ordinary
8. Hose
Requirements for Fire Hazard: 250 gpm (946 L/min) Extra Hazard:
Allowance
Hoses 500 gpm (1,893 L/min)
Maximum Allowable Generally 175 psi (12.1 bar) for most systems
Pressure unless otherwise specified.
13. Fire Pump Minimum Pressure for Varies depending on hazard classification but
Requirements Fire Pumps typically 100-175 psi (6.9-12.1 bar).
14. Storage Clearance for Storage Minimum 18 in (457 mm) clearance below
Considerations Racks sprinkler heads for proper water distribution.
16. Test & Hydrostatic Testing Systems must be tested at 200 psi (13.8 bar)
Maintenance Pressure for at least 2 hours.
Class III Standpipe Combines Class I and Class II, allowing for
System both 1½-inch and 2½-inch connections.
Semi-Automatic
Requires manual activation to supply water.
Standpipe
Minimum Residual
4. Pressure Class I & III: 100 psi (6.9 bar) Class II: 65 psi
Pressure at Most
Requirements (4.5 bar)
Remote Outlet
Minimum Flow Class I & III: 500 gpm for first standpipe, 250
Requirements for gpm per additional standpipe, max 1250
Standpipe Systems gpm.
10. Testing and Hydrostatic Testing 200 psi (13.8 bar) for 2 hours or 50 psi
Inspection Pressure Requirement above working pressure if over 150 psi.
Visual Inspection
Annually for pipes, valves, and FDCs.
Frequency
11. Obstruction Clearance from Storage 18 inches (457 mm) minimum clearance
Rules and Equipment from obstructions.
Minimum Pressure for Fire Typically ranges from 40 psi to 250 psi
4. Rated Pressure
Pumps (2.8 to 17.2 bar).
6. Water Supply Adequate and Reliable Can be from municipal supply, storage
Requirements Water Source tanks, reservoirs, or wells.
7. Pump Room
Fire Pump Room Location Must be protected from fire and flooding.
Requirements
10. Relief Valves & Relief Valves for Diesel Required if pressure exceeds 175 psi or
Pressure Regulation Pumps system components' rated pressure.
13. Performance Minimum Suction Pressure Positive pressure at suction inlet must be
Requirements for Pump Operation maintained.
14. Fuel Supply for Minimum Fuel Storage Must provide at least 8 hours of
Diesel Pumps Capacity operation at rated load.
Must comply with UL 142 or UL 2085
Fuel Tank Construction
standards for fire resistance.
NFPA 25 (2022) - Standard for the Inspection, Testing, and Maintenance of Water-Based
Fire Protection Systems
2. System Fire Alarm Control Units Central processing unit for monitoring and
Components (FACU) controlling alarm signals.