An Adjustable Differential Protection Scheme for Microgrids
An Adjustable Differential Protection Scheme for Microgrids
Volume
Zaid Alhadrawi et al., International Journal of Advanced 9,inNo.1.4,
Trends 2020
Computer Science and Engineering, 9(1.4), 2020, 664 - 672
International Journal of Advanced Trends in Computer Science and Engineering
Available Online at http://www.warse.org/IJATCSE/static/pdf/file/ijatcse9391.42020.pdf
https://doi.org/10.30534/ijatcse/2020/9391.42020
4
An Adjustable Differential Protection Scheme for Microgrids
with Inverter-Based Distributed Generation
Zaid Alhadrawi 1, M. N. Abdullah 2, HazlieMokhlis 3
1
Department of Electrical Engineering, Faculty of Engineering, University of Kufa, IRAQ,
[email protected]
1,2
Green and Sustainable Energy (GSEnergy) Focus Group, Faculty of Electrical and Electronic Engineering,
Universiti Tun Hussein Onn Malaysia, 86400 Parit Raja, BatuPahat, Johor, MALAYSIA,
[email protected]
3
Department of Electrical Engineering, Faculty of Engineering, University Malaya, 50603 Kuala Lumpur,
MALAYSIA, [email protected]
664
Zaid Alhadrawi et al., International Journal of Advanced Trends in Computer Science and Engineering, 9(1.4), 2020, 664 - 672
Also, the authors did not consider the fault current magnitude 2. DIFFERENTIAL PROTECTION METHOD FOR
variation due to microgrid modes, fault types, and unbalance MICROGRID FEEDERS
loads that lead to the blinding of protection or false tripping. A
differential protection scheme based on the differences in the Differential protection method has been widely used as
current frequency components was proposed in [22] to detect the main protection of an electrical unit such as a generator,
and isolate faults for the islanded mode only. Also, [23] used a bus, transformer, or power line due to its great performance.
differential scheme based on symmetrical components with a The method is one of the highest sensitive and powerful
central communication system for the islanded microgrid. methods of presenting protection against faults for the
Fuzzy process was used in [24] with the Hilbert space-based islanded mode and grid-connected mode [1]. The concept of
power theory to enhance differential protection performance. differential protection is uncomplicated, where it is based on
The scheme was limited to the grid-connected microgrid and the fact that any fault inside an electrical apparatus would
neglected the islanded mode. A positive sequence current result in the current entering the apparatus to be different than
proposed in [25] instead of the phase current presented into the current leaving the apparatus. Thus, the two currents can
the differential protection. The most important limitations of be compared and a trip output can be issued if the difference
this scheme are the scheme ignored the islanded mode and exceeds the threshold value. Consider a system shown in
disregarded the most common fault type (i.e., single-phase Figure 1. The current coming in the first end (I1) must be
fault). After a careful study of the protection schemes similar with the current leaving the second end (I2). The two
accessible in the literature, it is concluded that differential currents do not remain equal when a fault occurs between the
schemes are a suitable method to protect a microgrid. This is two ends. Alternatively, one could form an algebraic sum of
because the schemes can overcome the problems of the two currents entering the protected apparatus as presented
coordinating a large number of series protections and low in (1):
fault current supply from inverted-based DGs.However, there
are problems associated with this scheme, which are related to = + (1)
the fault current magnitude difference as a result of the change Under a normal operation, ideally, the magnitude
of operation mode, fault types, or unbalance loads that lead to ofdifferential current should be zero. In practical, it has a
the blinding of protection or false tripping. Furthermore, a small value, both under healthy conditions and external faults
conventional differential relay normally employs three due to the current transformer error, ratio mismatch, or line
differential units to cover all fault types; therefore, it requires charging current [26].Until recently, the differential
more channels and creates computational burden. In addition, protection method has not been applied for line protection due
the aforementioned schemes have not been examined for to the distances involved. For a three-phase line, six
other expected disturbances; hence, the schemes could fail to communication links would be required: one for the neutral,
operate correctly during non-fault events. The protection one for each phase, and two for tripping the circuit breakers.
centre used by several previous schemes caused additional However, as computers are becoming more diffused and
cost as multi-channels are required to connect all protection communication is more developed, line current differential
devices. Therefore, it is necessary to find a suitable protection protection has become popular [27]. The application of
scheme capable of solving these problems.This paper current differential protection to microgrid lines requires the
proposed an adjustable differential scheme for microgrid consideration of problems associated with this scheme, which
protection based on positive sequence current and detection are related to the fault current magnitude difference to avoid
mode to overcome the limitations of conventional differential the blinding of protection or false tripping. In this paper, a
protection. The proposed scheme is able to protect looped and modified differential current protection that used the
radial microgrids under all possible circumstances in both differential of positive sequence current for both feeder sides
operation modes. The effectiveness of the proposed scheme is is proposed.
provedby PSCAD/EMTDC software simulation of case study.
The main contributions of this scheme are as follows: 3. PROPOSED PROTECTION SCHEME
•Reducing computational burden and communication units.
•Considering both modes of microgrid operation (i.e., This paper suggests a comprehensive protection scheme that
grid-connected and isolated). is able to protect any type of microgrid for all possible
•Detecting and identifying the faulty line in a microgrid configurations against various types of faults. The proposed
during high penetration of inverter-based DG. protection scheme used a fault current magnitude
•The ability of dealing with radial and loop configuration, and andundervoltage protection to distinguish between the
avoiding the need to modify protection devices with each islanded mode and the grid-connected mode. The fault
configuration. currents and voltages retrieved at the two ends are reprocessed
The remaining of the paper is arranged as follows. The to determine the faulty phase. Then, the differential of
background of differential protection is presented in Section 2. positive sequence
Section 3 debates the proposed protection scheme. Section 4 current is used for fault detection and isolation. The
discusses the test system and the simulation results. Finally, in procedures of the proposed scheme are presented in Figure
Section 5, the principal conclusions of this study are 2.The proposed scheme consists of two parts. The first part is
presented. the mode detector to choose the appropriate settings and the
second part is the fault detection as shown in Figure 3.
665
Zaid Alhadrawi et al., International Journal of Advanced Trends in Computer Science and Engineering, 9(1.4), 2020, 664 - 672
666
Zaid Alhadrawi et al., International Journal of Advanced Trends in Computer Science and Engineering, 9(1.4), 2020, 664 - 672
Mode detector
V(abc) Sequence V+ Threshold
Island mode
analyzer Comparator
Threshold
Island Grid connected Setting
I(abc) Sequence I+ Threshold mode
analyzer Comparator
Grid
Grid
69 KV / 24.9 KV
B1
L1 4 Km
B2
L2 0.5 Km
2 Km L3 3 Km L4
B3 B4 B5
PV
Load 1
PV
L8 6 Km
L6 3 Km B6
L5 4 Km Load 2
L9 3 Km
B8
B7
Load 4
L7
Load 3
8 Km
L10 3 Km
B9 B10
Load 5
WT
667
Zaid Alhadrawi et al., International Journal of Advanced Trends in Computer Science and Engineering, 9(1.4), 2020, 664 - 672
1.00
4. SIMULATION RESULTS 0.90
0.80
0.70
To verify the validation of the proposed scheme, the 0.60
Current (kA)
microgrid test system of Figure 4 was performed using 0.50
0.40
PSCAD/EMTDC software. The voltage level of the studied 0.30
system was 24.9 kV and the operating frequency was 0.20
0.10
maintained at 50 Hz. The microgrid was connected to the grid 0.00
with a main circuit breaker that can be opened to simulate the Sec 0.00 0.20 0.40 0.60 0.80 1.00
effect of the islanded operation mode. As shown in this figure, (a)
the microgrid is connected to the main grid by a 69 kV/24.9
kV Dyn transformer. It also contains two photovoltaic 1.00
systems (640 KVA) and one wind turbine (504 KVA) that are 0.50
Voltage (p.u)
connected with the power network through a power electronic 0.00
inverter circuit [28], [29]. Each DG source is interfaced
-0.50
through a 0.4/24.9 kV transformer. Radial and loop
configuration can be achieved when the circuit breakers of L6 -1.00
are opened or closed. All types of faults (including SLG, LL, -1.50
LLG, and three phases to ground) were applied to the test the sec 0.140 0.160 0.180 0.200 0.220
microgrid for different locations in both islanded and (b)
grid-connected operation modes. In order to analysis
performance of the protection scheme, different scenarios 0.250
were simulated. 0.200
Current (KA)
0.150
4.1 RADIAL CONFIGURATION IN GRID-CONNECTED MODE
0.100
The objective of this scenario is to verify the
effectiveness of the proposed scheme during the 0.050
668
Zaid Alhadrawi et al., International Journal of Advanced Trends in Computer Science and Engineering, 9(1.4), 2020, 664 - 672
Ia Ib IC Ia Ib Ic
0.90
0.80
0.0250
0.70
0.60 0.0200
Current (kA)
Current (kA)
0.50
0.0150
0.40
0.30 0.0100
0.20
0.0050
0.10
0.00 0.0000
Sec 0.00 0.10 0.20 0.30 0.40 0.50 0.60 Sec 0.00 0.10 0.20 0.30 0.40
(a) (a)
1.00 1.00
0.50 0.50
Voltage (p.u)
Voltage (p.u)
0.00 0.00
-0.50 -0.50
-1.00 -1.00
-1.50 -1.50
sec 0.120 0.140 0.160 0.180 0.200 0.220 0.240 sec 0.140 0.160 0.180 0.200 0.220
(b) (b)
0.450 0.0060
0.400
0.0050
0.350
0.300 0.0040
Current (KA)
Current (KA)
0.250
0.0030
0.200
0.150 0.0020
0.100
0.0010
0.050
0.000 0.0000
Sec 0.00 0.20 0.40 0.60 0.80 1.00 Sec 0.00 0.10 0.20 0.30 0.40 0.50
(c) (c)
1.20 1.50
1.00
1.00
0.80
0.60 0.50
0.40 0.00
0.20 -0.50
0.00
-0.20 -1.00
-0.40 -1.50
-0.60 Sec 0.100 0.125 0.150 0.175 0.200 0.225 0.250 0.275
Sec 0.100 0.150 0.200 0.250 0.300
(d)
(d)
Figure7: SLG Fault at L5 in Islanded Mode/ Radial Configuration
Figure 6:LL Fault at L6 in Grid-Connected Mode/ Loop
(a) Magnitude Fault Currents (b) Three-Phase Voltages (c) Positive
Configuration (a) Magnitude Fault Currents (b) Three-Phase
Current Differential (d) Trip Signal
Voltages (c) Positive Current Differential (d) Trip Signal
4.4 LOOP CONFIGURATION IN ISLAND MODE
A SLG fault was occurred at line L5 with fault resistance is 10 The objective of this scenario is to verify the
Ω at simulation time is 0.2 S. In this case, the RMS current effectiveness of the proposed scheme during the
value of the faulted phase (a) raised to 0.015 KA while the grid-connected mode for loop configuration of the microgrid.
voltage decreased significantly as shown in Figure7 (a) and 7 This case is largely similar to the loop structure when the grid
(b) respectively. The current value within island range, is connected. However, the transients are smaller due to the
therefore the mode detector in the proposed scheme choose lower short circuit capacity of the system. Figure8. show fault
the setting of island mode. The difference between the
current magnitudes, the voltages, the differential of positive
positive current of the two feeder ends current increase to 4 A
so the trip signal was generated. Figure7 (c) and 7 (d) show current, and tripping signal waveforms, respectively for a
the ∆I+ and trip signal respectively. LLG fault at L9.
669
Zaid Alhadrawi et al., International Journal of Advanced Trends in Computer Science and Engineering, 9(1.4), 2020, 664 - 672
Current (kA)
0.50
proposed scheme 0.40
Ia Ib Ic 0.30
0.0450 0.20
0.0400 0.10
0.0350 0.00
0.0300 Sec 0.00 0.20 0.40 0.60 0.80
Current (kA)
0.0250
0.0200 (a)
0.0150
0.0100
0.0050
0.0000 1.00
Sec 0.00 0.20 0.40 0.60 0.80 1.00 1.20 0.50
Voltage (p.u)
(a) 0.00
-0.50
1.00 -1.00
0.50 -1.50
Voltage (p.u)
-0.50 (b)
-1.00
0.90
-1.50 0.80
Sec 0.140 0.160 0.180 0.200 0.220 0.70
0.60
Current (KA)
(b) 0.50
0.40
0.30
0.0050 0.20
0.10
0.0040
Current (KA)
0.00
0.0030 Sec 0.00 0.20 0.40 0.60 0.80
0.0020 (c)
0.0010
1.25
0.0000
1.00
Sec 0.000 0.050 0.100 0.150 0.200 0.250 0.300 0.350 0.75
(c) 0.50
0.25
0.00
1.25
-0.25
1.00
-0.50
0.75
0.50 Sec 0.100 0.150 0.200 0.250 0.300
0.25
0.00
(d)
-0.25
-0.50
Figure9: Three-Phase Fault at L6 in Grid-Connected Mode/ Radial
Sec 0.100 0.150 0.200 0.250 0.300 Configuration for Unbalanced Load (a) Magnitude Fault Currents (b)
Three-Phase Voltages (c) Positive Current Differential (d) Trip
(d)
Signal
0.0125
0.0100
2. A. A. Kamoona, A. N. alfadli, and I. A. Alshabeeb.New
0.0075 method for oc relay coordination,J. Electr. Comput. Eng.,
0.0050
0.0025 Vol. 2020, pp. 1–11, May 2020.
0.0000 3. D. A. Gadanayak and R. K. Mallick.Microgrid
Sec 0.000 0.050 0.100 0.150 0.200 0.250 0.300 0.350
differential protection scheme using downsampling
(a) empirical mode decomposition and Teager energy
operator, Electr. Power Syst. Res.,Vol. 173, pp. 173–182,
1.50
August 2019.
1.00 4. E. Sortomme, S. S. Venkata and J. Mitra.Microgrid
0.50 protection using communication-assisted digital relays,
Voltage (p.u)
671
Zaid Alhadrawi et al., International Journal of Advanced Trends in Computer Science and Engineering, 9(1.4), 2020, 664 - 672