SCHEDULE-OF-LOADS (1)

The document outlines the electrical load schedule and computations for five panel boards across different floors, detailing the power, voltage, and current for various circuits. It includes calculations for service entrance conductors and main protective devices, specifying the required wire sizes and circuit breaker ratings. Additionally, it provides transformer sizing based on the total calculated load for the main panel board.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
18 views13 pages

SCHEDULE-OF-LOADS (1)

The document outlines the electrical load schedule and computations for five panel boards across different floors, detailing the power, voltage, and current for various circuits. It includes calculations for service entrance conductors and main protective devices, specifying the required wire sizes and circuit breaker ratings. Additionally, it provides transformer sizing based on the total calculated load for the main panel board.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 13

SCHEDULE OF LOADS AND COMPUTATIONS

Panel Board PB #1 @Ground Floor


Ckt. Description Power Voltage Current
Qty. Phase
No. of Load VA volts Amp.
1 Light Outlets 13 1,300 230 1Ø 5.65
2 Light Outlets 12 1,200 230 1Ø 5.22
3 Light Outlets 9 900 230 1Ø 3.91
4 Light Outlets 10 1,000 230 1Ø 4.35
5 Light Outlets 11 1,100 230 1Ø 4.78
6 Light Outlets 14 1,400 230 1Ø 6.09
7 Light Outlets 12 1,200 230 1Ø 5.22
8 Convenience Outlet 7 1,260 230 1Ø 5.48
9 Spare 1 1,000 230 1Ø 4.35
10 Spare 1 1,000 230 1Ø 4.35
11,360 49.39
9,960

Size of Service Entrance Conductors: Size of Main Protective Device:

I = 9,960 + (1,400 x 1.25) I =


230
= 50.913 =
Use : 2 - # 14 mm2 THW Wires installed in a 20 mm Ø rigid Use :
steel conduit

Panel Board PB #2 @Second Floor


Ckt. Description Power Voltage Current
Qty. Phase
No. of Load VA volts Amp.
1 Light Outlets 10 1,000 230 1Ø 4.35
2 Light Outlets 12 1,200 230 1Ø 5.22
3 Light Outlets 9 900 230 1Ø 3.91
4 Light Outlets 10 1,000 230 1Ø 4.35
5 Light Outlets 10 1,000 230 1Ø 4.35
6 Light Outlets 14 1,400 230 1Ø 6.09
7 Light Outlets 12 1,200 230 1Ø 5.22
8 Convenience Outlet 7 1,260 230 1Ø 5.48
9 Spare 1 1,000 230 1Ø 4.35
10 Spare 1 1,000 230 1Ø 4.35
10,960 47.65
9,560

Size of Service Entrance Conductors: Size of Main Protective Device:

I = 9,560 + (1,400 x 1.25) I =


230
= 49.174 =
Use : 2 - # 14 mm2 THW Wires installed in a 20 mm Ø rigid Use :
steel conduit
Panel Board PB #3 @Third Floor
Ckt. Description Power Voltage Current
Qty. Phase
No. of Load VA volts Amp.
1 Light Outlets 10 1,000 230 1Ø 4.35
2 Light Outlets 12 1,200 230 1Ø 5.22
3 Light Outlets 9 900 230 1Ø 3.91
4 Light Outlets 10 1,000 230 1Ø 4.35
5 Light Outlets 10 1,000 230 1Ø 4.35
6 Light Outlets 14 1,400 230 1Ø 6.09
7 Light Outlets 12 1,200 230 1Ø 5.22
8 Convenience Outlet 7 1,260 230 1Ø 5.48
9 Spare 1 1,000 230 1Ø 4.35
10 Spare 1 1,000 230 1Ø 4.35
10,960 47.65
9,560

Size of Service Entrance Conductors: Size of Main Protective Device:

I = 9,560 + (1,400 x 1.25) I =


230
= 49.174 =
Use : 2 - # 14 mm2 THW Wires installed in a 20 mm Ø rigid Use :
steel conduit

Panel Board PB #4 @Fourth Floor


Ckt. Description Power Voltage Current
Qty. Phase
No. of Load VA volts Amp.
1 Light Outlets 6 600 230 1Ø 2.61
2 Light Outlets 12 1,200 230 1Ø 5.22
3 Light Outlets 9 900 230 1Ø 3.91
4 Light Outlets 10 1,000 230 1Ø 4.35
5 Light Outlets 10 1,000 230 1Ø 4.35
6 Light Outlets 14 1,400 230 1Ø 6.09
7 Light Outlets 10 1,000 230 1Ø 4.35
8 Light Outlets 4 400 230 1Ø 1.74
9 Convenience Outlet 7 1,260 230 1Ø 5.48
10 Spare 1 1,000 230 1Ø 4.35
11 Spare 1 1,000 230 1Ø 4.35
10,760 46.78
9,360

Size of Service Entrance Conductors: Size of Main Protective Device:

I = 9,360 + (1,400 x 1.25) I =


230
= 48.304 =
Use : 2 - # 14 mm2 THW Wires installed in a 20 mm Ø rigid Use :
steel conduit
Panel Board PB #5 @Ground Floor
Ckt. Description Power Voltage Current
Qty. Phase
No. of Load VA volts Amp.
1 Elevator Motor, 15 hp 1 16,731 230 3Ø 42.00
2 Fire Pump Motor, 40 hp 1 29,877 230 3Ø 75.00
3 Jockey Pump Motor, 4 hp 1 5,179 230 3Ø 13.00
51,787 130.00
21,910

Size of Service Entrance Conductors: Size of Main Protective Device:

I = 21,910 + (51.787 x 1.25) I =


230 x 1.732
= 148.750 =
Use : 3 - # 38 mm2 THW Wires installed in a 40 mm Ø rigid Use :
steel conduit
Air Circuit Breaker Conduit
Size of Circuit Conductors
Rating, Amp Size
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20
2 - # 3.5 mm2 THW Wires 20

Size of Main Protective Device:

9,960 + (1,400 x 2.5)


230
58.522
1 - 30 AT, 230 V, 2-pole, 60 Hz, 10 KAIC molded case
air circuit breaker

Air Circuit Breaker Conduit


Size of Circuit Conductors
Rating, Amp Size
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20
2 - # 3.5 mm2 THW Wires 20

Size of Main Protective Device:

9,960 + (1,400 x 2.5)


230
56.783
1 - 30 AT, 230 V, 2-pole, 60 Hz, 10 KAIC molded case
air circuit breaker
Air Circuit Breaker Conduit
Size of Circuit Conductors
Rating, Amp Size
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20
2 - # 3.5 mm2 THW Wires 20

Size of Main Protective Device:

9,560 + (1,400 x 2.5)


230
56.783
1 - 30 AT, 230 V, 2-pole, 60 Hz, 10 KAIC molded case
air circuit breaker

Air Circuit Breaker Conduit


Size of Circuit Conductors
Rating, Amp Size
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20 15 mm Ø
2 - # 3.5 mm2 THW Wires 20
2 - # 3.5 mm2 THW Wires 20

Size of Main Protective Device:

9,360 + (1,400 x 2.5)


230
55.913
1 - 30 AT, 230 V, 2-pole, 60 Hz, 10 KAIC molded case
air circuit breaker
Air Circuit Breaker Conduit
Size of Circuit Conductors
Rating, Amp Size
3 - # 14 mm2 THW Wires 110 25 mm Ø
3 - # 14 mm2 THW Wires 110 25 mm Ø
3 - # 5.5 mm2 THW Wires 30 15 mm Ø

Size of Main Protective Device:

22,786 + (16,731 x 2.5)


230 x 1.732
242.500
1 - 300 AT, 230 V, 3-pole, 60 Hz, molded case
air circuit breaker
Main Panel Board MPB
Ckt. Description Power Voltage Current, Amp.
Qty. Phase
No. of Load VA volts L1 L2
1 PB1 1 11,360 230 1Ø 49.39 49.39
2 PB2 1 10,960 230 1Ø 47.65
3 PB3 1 10,960 230 1Ø 47.65
4 PB4 1 10,760 230 1Ø 48.304
5 PB5 1 51,787 230 3Ø 148.75 148.75
95,827 246.444 293.44
44,040

Size of Service Entrance Conductors:

I = 44,040 + (51787 x 1.25)


230 x 1.732
= 273.053
Use : 3 - # 150 mm2 THHN Wires installed in a 80 mm Ø rigid
steel conduit

SIZE OF TRANSFORMERS:

KVA =1.732 x 293.44 x 230/1,000


=116.895
Use: 3 - 50 kva, 10,120/230 Volts, 60 hz, oil-filled single phase transformers.
Current, Amp. Air Circuit Breaker Conduit
Size of Circuit Conductors
L3 Rating, Amp Size
2 - # 14 mm2 THW Wires 100 20 mm Ø
47.65 2 - # 14 mm2 THW Wires 100 20 mm Ø
47.65 2 - # 14 mm2 THW Wires 100 20 mm Ø
48.30 2 - # 14 mm2 THW Wires 100 20 mm Ø
148.75 3 - # 38 mm2 THW Wires 400 125 mm Ø
292.35

Size of Main Protective Device:

I = 44,040 + (51,787 x 2.5)


230 x 1.732
= 435.553
Use : 1 - 500 AT, 230 V, 3-pole, 60 Hz, molded case
air circuit breaker
Utility Power Supply

10,150V 3 - 50 kva 1Ø, oil-filled transformer


230V 3%

3 - # 150 mm2 THW Wires, stranded, 600 V installed in a


80 mm Ø rigid steel conduit.

500 A
3P
# 38 mm2 Cu wire

2 - # 14 mm2 THHN Wires, stranded, 600V


installed in a 20 mm Ø rigid steel conduit.
100A
2P

20A 20A 20A 20A 20A 20A 20A 20A


2P 2P 2P 2P 2P 2P 2P 2P

C1 C2 C3 C4 C5 C6 C7 C8

# 14 mm2 Cu wire
PB #1

2 - # 14 mm2 THHN Wires, stranded, 600V


installed in a 20 mm Ø rigid steel conduit.
100A
2P

20A 20A 20A 20A 20A 20A 20A 20A


2P 2P 2P 2P 2P 2P 2P 2P

C1 C2 C3 C4 C5 C6 C7 C8
#14 mm2 Cu wire
PB #2

2 - # 30 mm2 THHN Wires, stranded, 600V


installed in a 32 mm Ø rigid steel conduit.
100A
2P

20A 20A 30A 30A 30A 30A 30A 20A


2P 2P 2P 2P 2P 2P 2P 2P

C1 C2 C3 C4 C5 C6 C7 C8

#14 mm2 Cu wire


PB #3

3 - # 38 mm2 THHN Wires, stranded, 600V


installed in a 40 mm Ø rigid steel conduit.
300 A
3P

110A 30A 110A


3P 3P 3P

C1 C2 C3

# 14 mm2 Cu wire
PB #4

SINGLE LINE DIAGRAM


SPECIFICATIONS:
1. Service entrance conductors shall be 3 - # 150 mm2 THW Wires, stranded, 600volts, installed overhead in a 8
2. Main Protective Device shall be 1 - 500 AT, 3-pole, 230 V, 60 Hz, 10 KAIC molded case air circuit breaker.
3. All electrical equipment shall be properly grounded.
4. All switch and convenience outlets shall be 1200 mm and 300 mm above the floor line respectively.
5. Branch circuit conductors shall be installed in a PVC conduit pipes with proper fittings.
6. All electrical installations shall be supervised by a duly licensed Electrical Engineer.
7. All electrical works herein shall conform with the provisions of the latest Edition of Philippine Electrical Code,
Rules & Regulations of Distribution Utility.
nstalled overhead in a 80 mm Ø rigid steel conduit.
air circuit breaker.

e respectively.

hilippine Electrical Code, City Ordinances and