TECHNICAL SPECIFICATION
A2XS(FL)2Y 1x630RM/120 127/220 (245) kV IEC 62067
CONSTRUCTION (x) The picture is informative only
– not to scale
❑ Round, stranded and compacted
aluminum conductor. Class 2.
APPLICATION
❑ Extruded semi-conducting
conductor screen ❑ Laying in ground
❑ Insulation XLPE – dry cured (wet or dry locations)
❑ Extruded semi-conducting ❑ Laying in air
insulation screen ❑ Laying in ducts
❑ Semi-conducting swelling tapes
❑ Metallic screen: Highest permissible conductor
copper wires screen and temperature
copper equalizing tapes
❑ Semi-conducting swelling tapes ❑ Continuous operation 90 C
❑ Longitudinal aluminum foil ❑ Short circuit 250 C
❑ Outer sheath – black HDPE (duration max 5 s)
Laying is possible without any special
measures at natural cable temperatures and
ambient temperature not lower than -5 ºC,
MARKING with Tele-Fonika supervising
TF KABLE, product name, date of
manufacture, standard, meter marking
DESCRIPTION UNIT DETAILS
CONSTRUCTION DATA Uo/U/Um 127/220 (245) kV
Conductor
❑ material Aluminium
❑ number of wires No 58
Nominal cross sectional area mm2 630
Conductor diameter and tolerance mm 29.3 -0.2 +0.4
Min./Nom. thickness semi-conducting XLPE on conductor mm 1.1 / 1.5
Nominal insulation thickness XLPE mm 23.5
Insulation thickness: minimum at a point mm 20.7
Diameter over insulation – nominal mm 79.3 ±1.5
Min./Nom. thickness semi-conducting XLPE on insulation mm 0.8 / 1.2
Thickness of semi-conducting swelling tapes No x mm 2 x ~ 0.35
Metallic screen mm2 120
❑ Copper wires No x mm 74 x 1.44
❑ Copper equalizing tape No x mm x mm 2 x 10 x 0.18
Mean diameter over metallic screen mm 85.5
Thickness of semi-conducting swelling tapes No x mm 2 x ~ 0.35
Thickness of aluminum foil mm 0.2
Diameter over aluminum foil mm 87.0
Nominal outer sheath thickness / min. mm 4.0 / 3.3
Approximate overall diameter completed cable (De) mm 95.4
Weight of complete cable (approx.) kg/km 8740
DELIVERY DATA
Diameter of wooden drum m 3.0 3.7 3.8
❑ type 300P 370P 380P
Maximum length per drum m 450 890 1060
Weight of heaviest reel, including cable kg 6060 11710 13340
(x)
Diameters are calculated values and subject to manufacturing tolerances
Page 2 of 4
ELECTRICAL DATA at 50 Hz
Maximum D.C. conductor resistance at 20 C /km 0.0469
Maximum A.C. conductor resistance at 90 C /km 0.0618
Maximum D.C. metallic screen resistance at 20 C /km 0.158
Maximum D.C. aluminum foil resistance at 20 C /km 0.481
Operating inductance
❑ trefoil formation mH/km 0.425
❑ flat formation (*) mH/km 0.609
Induction reactance
❑ trefoil formation /km 0.133
❑ flat formation (*) /km 0.191
Capacitance F/km 0.148 (+8%)
Capacitance reactance k/km 21.44
Impedance
❑ trefoil formation /km 0.147
❑ flat formation (*) /km 0.201
Max. electric stress at conductor screen / (at insulation) kV/mm 8.76 / 3.57
Dielectric losses (tg = 0.001) – per phase W/m 0.752
Partial discharge test – at 1.5Uo pC ≤5
Charging current – per phase A/km 5.92
Charging power kVA/km 752
Earth fault current – per phase A/km 17.77
MECHANICAL DATA
Recommended min. bending radius for laying m 2.38
Recommended permissible bending radius at final
installation (after pre-heating and using template) m 1.9
Maximum permissible pulling force: kN 18.9
SHORT CIRCUIT CURRENTS
Maximum permissible thermal short-circuit (IEC 60949)
Current for s 1 0.6
Phase conductor 90 → 250 C kA 60.2 77.5
Metallic screen 80 → 350 C kA 24.1 30.3
AMPACITY (**)
– Bonding of the metallic screens Cross-bonding / Both-ends
in earth
❑ flat formation (*) A 750 / 605
❑ trefoil formation A 699 / 646
in air
❑ flat formation A 954 / 807
❑ trefoil formation A 863 / 820
TESTS
AC – Test voltage – (2.5Uo; 30 min) kV 318
Lightning impulse kV 1050
Partial discharge test kV 190
Marking: TF-KABLE 5 A2XS(FL)2Y 1x630RM/120 127/220 (245) kV IEC 62067 2025
(*)
Distance between cable axes laid in flat formation De+De mm (for information)
(**)
Current rating guideline (Calculated with Cymcap 8.2 based on IEC Pub. 60287 and the following conditions)
❑ Ground temperature 20 C
❑ Laying depth 1.0 m
❑ Ground thermal resistivity 1.0 K·m/W
❑ Load factor 1.0
❑ Air temperature 35 C
(x)
Diameters are calculated values and subject to manufacturing tolerances
Page 3 of 4
Figure 1. Cables in earth, Cross-bonding, flat formation.
Figure 2. Cables in earth, Cross-bonding, trefoil formation.
(x)
Diameters are calculated values and subject to manufacturing tolerances
Page 4 of 4
Figure 3. Cables in air, Cross-bonding, flat formation.
Figure 4. Cables in air, Cross-bonding, trefoil formation.
Date: 2025-01-21; PK25008
Prepared by: Przemysław Krawczykowski
(x)
Diameters are calculated values and subject to manufacturing tolerances