EKM7DC MCCB 1500V
Non-P olarity DC MCCB - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Standard_lEC60947-2
| Technical Parameters
Molded case circuit breaker EKM7DC-320 EKM7DC-400 EKM7DC-630 EKM7DC-1600
100,125,140,160,180, 800,1000,1250,1500,
Fame size current In 250,315,350,400A 400,500,630A
200,225,250,280,315A 1600A
Pole number 2P 2P 2P 3P,4P
Rated working voltage Ue (V), DC DC750V, DClOOOV, DC1200V, DClSOOV
Rated insulation voltage Ui {V) 1600V
Rated impulse withstand voltage Uimp (kV) 12kV
DC750V 85 85 85 50
Rated operating short-circuit
capacity lcs= lcu (kA)
DClOOOV
DC1200V
50
35
I 50
35
[ 50
35
30
15
DClSOOV 20 20 20 10
二
Machine life (times) 4000 4000 4000 2500
Electrical life (times) 1000 1000 1000 500
Arcing distance (mm) 50 (plus arc suppression cover)
Instantaneous tripper Sin or 101n
| Capacity Reduction Coefficient
EKM7DC Molded case circuit breaker temperature change reduction coefficient table
Model Frame size rated current(A) S0°C ss 0 c 60°C 6S0 c 70° C
EKM7DC-320/2300 250 1 0.95 0.93 0.91 0.88
EKM7DC-400/2300 400 1 0.93 0.91 0.89 0.85
EKM7DC-630/2300 630 1 0.92 0.90 0.89 0.83
EKM7DC-1600/2300 1600 1 0.936 0.915 0.894 0.873
| High Altitude Capacity Reduction
EKM7DC Molded case circuit breaker high altitude capacity reduction coefficient table
Altitude (m) 2000 2500 3000 3500 4000 4500 5000
Working current correction coefficient 1 1 0.98 0.97 0.96 0.95 0.94
Short-circuit breaking capacity correction coefficient
Power frequency withstand voltage correction coefficient
1
1
l 1
1
0.83
0.89
0.77
0.85
0.71
0.80
0.67
0.77
0.63
0.73