0% found this document useful (0 votes)
22 views92 pages

ETEK Solar PV System 2024

The document provides technical specifications for the EKM7DC molded case circuit breakers (MCCB) with ratings from 320A to 1600A and various voltage options up to 1500V DC. It includes details on current ratings, pole numbers, insulation voltage, short-circuit capacity, and operational life. Additionally, it outlines capacity reduction coefficients based on temperature and altitude conditions.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
22 views92 pages

ETEK Solar PV System 2024

The document provides technical specifications for the EKM7DC molded case circuit breakers (MCCB) with ratings from 320A to 1600A and various voltage options up to 1500V DC. It includes details on current ratings, pole numbers, insulation voltage, short-circuit capacity, and operational life. Additionally, it outlines capacity reduction coefficients based on temperature and altitude conditions.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 92

EKM7DC MCCB 1500V

Non-P olarity DC MCCB - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Standard_lEC60947-2

| Technical Parameters

Molded case circuit breaker EKM7DC-320 EKM7DC-400 EKM7DC-630 EKM7DC-1600

100,125,140,160,180, 800,1000,1250,1500,
Fame size current In 250,315,350,400A 400,500,630A
200,225,250,280,315A 1600A

Pole number 2P 2P 2P 3P,4P

Rated working voltage Ue (V), DC DC750V, DClOOOV, DC1200V, DClSOOV

Rated insulation voltage Ui {V) 1600V

Rated impulse withstand voltage Uimp (kV) 12kV

DC750V 85 85 85 50

Rated operating short-circuit


capacity lcs= lcu (kA)
DClOOOV

DC1200V
50

35
I 50

35
[ 50

35
30

15

DClSOOV 20 20 20 10


Machine life (times) 4000 4000 4000 2500

Electrical life (times) 1000 1000 1000 500

Arcing distance (mm) 50 (plus arc suppression cover)

Instantaneous tripper Sin or 101n

| Capacity Reduction Coefficient


EKM7DC Molded case circuit breaker temperature change reduction coefficient table

Model Frame size rated current(A) S0°C ss 0 c 60°C 6S0 c 70° C

EKM7DC-320/2300 250 1 0.95 0.93 0.91 0.88

EKM7DC-400/2300 400 1 0.93 0.91 0.89 0.85

EKM7DC-630/2300 630 1 0.92 0.90 0.89 0.83

EKM7DC-1600/2300 1600 1 0.936 0.915 0.894 0.873

| High Altitude Capacity Reduction


EKM7DC Molded case circuit breaker high altitude capacity reduction coefficient table

Altitude (m) 2000 2500 3000 3500 4000 4500 5000

Working current correction coefficient 1 1 0.98 0.97 0.96 0.95 0.94

Short-circuit breaking capacity correction coefficient

Power frequency withstand voltage correction coefficient


1

1
l 1

1
0.83

0.89
0.77

0.85
0.71

0.80
0.67

0.77