B0750aq Z
B0750aq Z
Control HMI
User’s Guide
*B0750AQ* *Z*
B0750AQ, Rev Z
December 2023
https://www.se.com
Legal Information
The information provided in this document contains general descriptions, technical
characteristics and/or recommendations related to products/solutions.
This document is not intended as a substitute for a detailed study or operational and
site-specific development or schematic plan. It is not to be used for determining
suitability or reliability of the products/solutions for specific user applications. It is the
duty of any such user to perform or have any professional expert of its choice
(integrator, specifier or the like) perform the appropriate and comprehensive risk
analysis, evaluation and testing of the products/solutions with respect to the relevant
specific application or use thereof.
The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this document are the property of Schneider Electric SE or
its subsidiaries. All other brands may be trademarks of their respective owner.
This document and its content are protected under applicable copyright laws and
provided for informative use only. No part of this document may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the
document or its content, except for a non-exclusive and personal license to consult it
on an "as is" basis.
Schneider Electric reserves the right to make changes or updates with respect to or in
the content of this document or the format thereof, at any time without notice.
To the extent permitted by applicable law, no responsibility or liability is
assumed by Schneider Electric and its subsidiaries for any errors or omissions
in the informational content of this document, as well as any non-intended use
or misuse of the content thereof.
Control HMI User’s Guide
Table of Contents
Preface ...............................................................................................................9
Revision Information.........................................................................................9
Related Documents........................................................................................10
Foxboro DCS User Documentation ............................................................10
AVEVA User Documentation ..................................................................... 11
Schneider Electric Products Mentioned in this Document .................................. 11
Global Customer Support ............................................................................... 11
We Welcome Your Comments......................................................................... 11
Chapter 1: Introduction to Control HMI........................................................12
Typical Workflow ............................................................................................12
Runtime Features.....................................................................................13
Configuration Features .............................................................................14
Control Core Services Hardware .....................................................................14
Multi-monitor Workstations..............................................................................15
Monitor Resolutions........................................................................................15
Control Software 7.x Migration Support for Legacy Control HMI User
Interface ........................................................................................................15
Configurators .................................................................................................16
Industrial Graphic Symbol Editor................................................................16
WindowMaker ..........................................................................................16
Framer ....................................................................................................17
Read-Only Mode............................................................................................17
Chapter 2: Main Window and Menus ..........................................................18
Control HMI Main User Interface .....................................................................18
Control HMI Header (Menu Bar) ......................................................................18
Control HMI Menus ........................................................................................21
File Menu.................................................................................................22
Alarms Menu............................................................................................23
Views Menu .............................................................................................24
Utilities Menu ...........................................................................................24
Help Menu ...............................................................................................26
Chapter 3: Using Control HMI.......................................................................27
Starting Control HMI .......................................................................................27
Configuring Security and Role Permissions ................................................27
Logging in to Control HMI ...............................................................................28
Running Control HMI and FoxView on the Same Workstation ............................28
Sending Commands to FoxView ................................................................29
Control HMI Features .....................................................................................30
Navigation Browser ..................................................................................30
Navigation SoftPanel ................................................................................32
Favorites .................................................................................................35
Recent Windows ......................................................................................36
Block Select .............................................................................................37
Tag Bar....................................................................................................37
B0750AQ, Rev Z 3
Control HMI User’s Guide
4 B0750AQ, Rev Z
Control HMI User’s Guide
B0750AQ, Rev Z 5
Control HMI User’s Guide
6 B0750AQ, Rev Z
Important Safety Instructions Control HMI User’s Guide
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death
or serious injury.
Failure to follow these instructions will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation that, if not avoided, could result in
death or serious injury.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
CAUTION
CAUTION indicates a hazardous situation that, if not avoided, could result in
minor or moderate injury.
Failure to follow these instructions can result in injury or equipment damage.
NOTICE
NOTICE is used to address practices not related to physical injury.
Failure to follow these instructions can result in equipment damage.
Please Note
Electrical equipment should only be installed, operated, serviced, and maintained by
qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training to
recognize and avoid the hazards involved.
B0750AQ, Rev Z 7
Preface Control HMI User’s Guide
Preface
EcoStruxure™ Foxboro™ DCS Control HMI (“Control HMI”) is the user interface to
process displays, alarm monitoring, historical data, and process control compounds
and blocks. This software is part of the Foxboro DCS Control Software (“Control
Software”).
This version of the document applies to Foxboro DCS Control Software 8.0. For
earlier versions of Control Software, see earlier revisions of this document.
The terms controller, control processor, and CP are used interchangeably throughout
this document.
Revision Information
This revision of the document includes these changes:
B0750AQ, Rev Z 9
Control HMI User’s Guide Preface
Related Documents
Foxboro DCS User Documentation
• Access Manager User's Guide (B0750AD)
• Control Software Deployment Guide (B0750BA)
• DeviceNet Network Implementation Guide (B0750CH)
• Framer and Alarm Management User’s Guide (B0750AR)
• System Manager v2.1.6 and Earlier User’s Guide (B0750AP)
• Window Construction User's Guide (B0750AS)
Find the latest versions of these documents on the Global Customer Support website
at https://pasupport.se.com (registration required).
10 B0750AQ, Rev Z
Preface Control HMI User’s Guide
B0750AQ, Rev Z 11
Control HMI User’s Guide Chapter 1: Introduction to Control HMI
Typical Workflow
The typical workflow is:
1. Edit the Control HMI $Template from the System Platform IDE template toolbox.
2. Test changes to the $ControlHMI Template before deploying changes to operator
workstations. Open WindowMaker and click Runtime to test the changes locally
in the runtime environment. This does not require deployment.
3. Use the Control HMI Framer application to manage user and station-based
runtime layouts, user permissions, and general features and functionality. Control
HMI Framer settings are accessed from System Platform IDE. The $ControlHMI
template does not need to be opened in WindowMaker. Right-click the
$ControlHMI Template to open IDE.
4. When changes to Framer and the ControlHMI application are tested and checked
in, update operator workstations by redeploying the Control HMI instances on
each workstation.
5. Create and assign the instances to ViewApp Engines on each station.
6. Deploy instances of $ControlHMI template to operator workstations.
For read-only runtime, create an instance of the Read-Only View Engine and
deploy an instance of the Control HMI $Template.
12 B0750AQ, Rev Z
Chapter 1: Introduction to Control HMI Control HMI User’s Guide
NOTE:
• The Managed Control HMI Application supports the use of Industrial Graphics
and Situational Awareness (SA) Libraries.
• InTouch WindowMaker need not convert the application resolution when
opened in different resolutions. If the application is opened in a different
resolution, select No when asked whether to convert the application.
• To reduce application size, the managed application contains three sets of
Detail Displays. The five sets of Detail Displays that are not a part of the
default set are available in the workstation and can be imported back into the
HMI application.
Runtime Features
• Control HMI provides access to the running plant environment. Control HMI
includes windows for monitoring and servicing alarms, navigation windows for
accessing user-built content, windows for viewing historical alarms and process
values, and detail display windows for viewing and servicing control blocks
created in the DCS system.
• Navigation support for user-created windows and content.
• Historian Client Trend windows for accessing historical process values.
• Windows for reviewing and servicing alarms.
◦ Runtime - Process Alarms
◦ Runtime - Device Condition messages
◦ Runtime - Recent System events and messages
◦ Historical - Alarm Logger Databases
◦ Historical - Historized DCS alarm messages
• Control HMI Framer application is used to manage user and station-based
runtime layouts, user permissions, and general features and functionality. Access
Control HMI Framer settings from the System Platform IDE. You do not need to
open the Control HMI $Template from WindowMaker. In the IDE Template
toolbox, right-click Control HMI $Template, then select Framer.
The Control HMI Framer application provides the ability to:
◦ Define the appearance of the runtime.
◦ Define user and station based navigations of created windows and folders.
◦ Define user permissions and grant access to Control HMI features and
functionality.
◦ Define default alarm queries, annunciation, and horns.
◦ Create multiple definitions and deploy them to different areas or operator
workstations.
• Control HMI and FoxView can run on the same station, at the same time. For
more information, see Running Control HMI and FoxView on the Same
Workstation, page 28.
◦ Only one alarm sub-system can be active. During the system configuration,
select the Foxboro DCS Alarm Manager or Control HMI Alarm Server.
◦ The Control HMI Process and System buttons will show the alarm state of
either alarm subsystem.
B0750AQ, Rev Z 13
Control HMI User’s Guide Chapter 1: Introduction to Control HMI
• Provides access to other external tools for managing and servicing the system.
◦ Block Select utility for viewing the status of deployed Control Blocks and
Componds. Using Block Select, you can open highly detailed windows of
selected blocks and compounds, allowing you to view and maintain block
settings and control of the process.
◦ Alarm Shelving Utility or Alarm Shelving Tool (if installed).
◦ System Manager for interfacing with the Control Core Services hardware. For
more information, see System Manager v2.1.6 and Earlier User’s Guide
(B0750AP).
◦ Troubleshooting tools such as the System Platform Logger and the System
Platform Object Viewer.
◦ Quick Block Editor for quick access to the Control Editors for selected control
blocks.
Configuration Features
Control HMI also includes a library of Industrial Graphics and templates for creating
process control windows, in addition to libraries and examples for customizing the
layout of the runtime Control HMI.
• You can create customized copies of Control HMI content to replace the default
Control HMI content. This includes:
◦ Modern UI headers and menus
◦ Industrial Graphic Detail Displays
◦ Alarm Panels
Control HMI and FoxView can communicate through the use of OM Variables.
• Use the ITCMD OM variables to communicate to the Control HMI.
• Use the DCCMD OM variables to communicate to the FoxView.
Control HMI supports the ability to run in Read-Only mode.
• An instance of the Control HMI can be deployed to a Read-Only View Engine.
• This instance is always Read-Only and requires a Read-Only license to run.
14 B0750AQ, Rev Z
Chapter 1: Introduction to Control HMI Control HMI User’s Guide
Multi-monitor Workstations
A Control Core Services workstation can support multiple monitors. The Control HMI
supports one, two, or four monitor setups. For more information, see Framer and
Alarm Management User’s Guide (B0750AR).
When configuring for multiple monitors, the AVEVA Intouch HMI requires these
conditions to be met. Any deviation might have unexpected results on the appearance
and layout of the Control HMI.
• All monitors must have the same desktop resolution.
• Monitor 1 must be the top and left most monitor. Additional monitors are
numbered from left to right, then top to bottom.
• The Wonderware Win.ini file, for each user account, must have the InTouch
multiscreen setting set to 1.
When configured for multi-monitor operation, standard monitors share a single
keyboard and pointing device, and the cursor moves from one screen to the other
screen.
Monitor Resolutions
The Control HMI supports 1920x1080 desktop resolution. When migrating from an
older system, you can choose to continue using the older Control HMI user interface,
which also supports 1280x1024 desktop resolution.
B0750AQ, Rev Z 15
Control HMI User’s Guide Chapter 1: Introduction to Control HMI
Control HMI also supports migrated windows from legacy 4:3 applications and the
ability to display widescreen formatted windows. All windows must be assigned to a
window style. By default, all windows belong to the default style of the application.
Windows that are not using the default style are the only windows that require
configuring. See Framer and Alarm Management User’s Guide (B0750AR) for details
on configuring WinStyles and window assignments.
Key Window Style Features:
• Automatic placement of 4:3 formatted windows on each monitor.
• Automatic user notification when viewing 16:9 windows on 4:3 stations.
• Custom features for window styles.
Configurators
Use these configurators to create and configure Control HMI functions and create and
configure content for display on the Control HMI:
• Industrial Graphic Symbol Editor
• WindowMaker
• Control HMI Framer
WindowMaker
The Control HMI is an InTouch HMI View application that is created and maintained by
the InTouch WindowMaker Software. This tool is used to create additional process
windows that can be accessed through the Control HMI framework and navigation
browser.
We recommend to first create the process window as a single industrial graphic. From
the WindowMaker, create a new window and link, or embed, the Industrial Graphic
Symbol into the InTouch window. Additionally, windows can be arranged and
organized into different folders that represent different plants, areas, or equipment.
The Control HMI’s Framer application can be used to set access permission on
windows and folders created in WindowMaker. It can also be used to change the
Control HMI runtime layout and functionality for different users and workstations.
16 B0750AQ, Rev Z
Chapter 1: Introduction to Control HMI Control HMI User’s Guide
Framer
Use the Control HMI Framer tool to configure the general functions of the user
experience. You can create and deploy different configurations to different
workstations. To launch Framer from the IDE, right-click Control HMI $Template in
the Template Toolbox, then click Framer.
Use Framer configurations to:
• Create navigation treeviews and assign the user location based access.
• Assign windows to the Control HMI’s navigation panel. The navigation panel
monitors the assigned alarm states of windows and communicates the alarm
state to the main Control HMI user interface.
• Assign windows and alarm tags to hardware annunciator keys and to the
navigation panel.
• Create alarm queries used by the Alarm Server to monitor the alarms received by
the station.
• Configure role-based permissions for accessing Control HMI features.
• Override the default graphics used in the Control HMI user interface. This
includes alarm panels and the main Control HMI user interface header.
• Define different monitor layout configurations.
• Assign created configurations to different workstations and groups.
Read-Only Mode
Control Software contains a Read-Only View Engine. Instances of Control HMI that
are deployed to this View Engine will run in Read-Only mode. When in Read-Only
mode:
• There is no access to the Tools menus and applications such as BlockSelect and
PLB Monitor.
• Users cannot acknowledge alarm or silence and mute horns.
• Alarm Panel actions for managing alarm states are disabled.
• Writing to all external connections are disabled.
• All permissions related to Alarm Management, writing data, or accessing tools are
overwritten and set to false.
• Custom alarm queries, filters, and scratchpad setups are disabled.
To create and set up a Read-Only Control HMI, see Control Software Deployment
Guide (B0750BA).
B0750AQ, Rev Z 17
Control HMI User’s Guide Chapter 2: Main Window and Menus
A Control HMI header (menu bar) that provides access to alarm status and information navigation,
quick access to tools, customizable menu system, and user login and information.
B Area where process windows appear.
C Customizable function bar where users can add additional content and information for operators.
D Basic status bar that shows navigation panel information and time.
18 B0750AQ, Rev Z
Chapter 2: Main Window and Menus Control HMI User’s Guide
• Click the icon to show the Control HMI Help About dialog.
B0750AQ, Rev Z 19
Control HMI User’s Guide Chapter 2: Main Window and Menus
When the MENUS action tab is not selected. The Tag bar is shown.
Features from left to right:
• The Selected Tag name. Action buttons to the right reflect the available actions that can be
executed on this tag.
• Drop-down list of recent selected tags.
• Open the detail display for the selected tag in the next available position or use the dropdown to
open the display in a selected location.
• Open the user display that this tag is assigned to. For information about assigning tags to windows,
the navigation panel, and annunciator configurations, see Framer and Alarm Management User’s
Guide (B0750AR).
• Open the source detail display for the selected tag parameter.
• Activate the Quick Block Editor tool to open the strategy and block editor in the system platform
IDE.
• Open the configured Alarm Shelving Utility or Alarm Shelving Tool
20 B0750AQ, Rev Z
Chapter 2: Main Window and Menus Control HMI User’s Guide
When the MENUS action tab is selected, the Control HMI menus are shown.
The Control HMI Menu is a set of configurable menus that can provide different actions and tools to
different users and workstations.
• For descriptions of default operations, see Chapter 3: Using Control HMI, page 27.
• For instructions on creating custom menus, see Window Construction User's Guide (B0750AS).
F Login and Action Tag
B0750AQ, Rev Z 21
Control HMI User’s Guide Chapter 2: Main Window and Menus
File Menu
The File menu consists of:
22 B0750AQ, Rev Z
Chapter 2: Main Window and Menus Control HMI User’s Guide
Alarms Menu
The Alarms menu contains menu items for showing the different Alarm Panels.
The Alarm Shelving Utility and Alarm Shelving Tool appear in the Alarms menu when
they are installed and configured. When ASU or AST are enabled, these menu items
are available.
Alarm Shelving Utility(a) Opens the System Advisor Alarm Shelving Utility (ASU).
ASU replaces the Alarm Shelving Tool’s function when it
is installed and enabled. For more information, see
Alarm Shelving Utility User’s Guide (B0750HC).
Alarm Shelving Tool(b) Menu
Configure Opens the Alarm Shelving Tool (AST) configuration
interface used to configure the AST software. You must
be logged in as an AST Engineer to access this option.
For more information, see Alarm Shelving Tool (AST)
Software Configuration and Administration Guide
(B0700CZ).
B0750AQ, Rev Z 23
Control HMI User’s Guide Chapter 2: Main Window and Menus
Tag Search Opens the AST Tag Search interface used to search all
compounds blocks on the control network for potential
shelving/unshelving targets. For more information, see
Alarm Shelving Tool (AST) Software Configuration and
Administration Guide (B0700CZ).
Summary Opens the AST Summary Statistics interface used to
provide a quick look at the resources that dedicated to
alarm shelving. For more information, see Alarm
Shelving Tool (AST) Software Configuration and
Administration Guide (B0700CZ).
Shelved Alarms Opens the AST Currently Shelved Alarms display used
to view all shelved alarms on the control network. For
more information, see Alarm Shelving Tool (AST)
Software Configuration and Administration Guide
(B0700CZ).
(a) The Alarm Shelving Utility is available only if it is installed and configured.
(b) The Alarm Shelving options in the Tools menu are available only if the Alarm
Shelving Tool is installed and configured.
For more information on alarm concepts, alarm handling, and the operator interface
with alarms, see the InTouch User’s Guide..
Views Menu
The Views menu contains menu items for showing the different Control HMI utility
panels.
States View Shows the State View panel for monitoring electrical
systems.
For more information, see States View Panel Details,
page 166.
Watch Panel Shows the Watch panel for adding and monitoring user
assigned references.
For more information, see Watch Panel, page 41.
Historian Trends Shows the Historian Client (Scratchpad) Trend panel for
viewing trends of historized data points.
For more information, see Historian Trends, page 42.
Utilities Menu
The Utilities menu provides access to various tools and utilities.
24 B0750AQ, Rev Z
Chapter 2: Main Window and Menus Control HMI User’s Guide
B0750AQ, Rev Z 25
Control HMI User’s Guide Chapter 2: Main Window and Menus
NOTE:
• The PLB Monitor menu item is available only when Exceed is installed on the
station. If Exceed is not installed, the PLB Monitor menu item is not shown.
Exceed is part of an optional Control Core Services package.
• All utilities, except for the PLB Monitor, are disabled when using a Read-Only
License. When Control HMI is running in Read-Only mode, the PLB Monitor
menu item opens the PLB Monitor application in View-Only mode.
• Block Select is the only utility available to non-administrators or FCS
Engineering roles.
Help Menu
The Help menu contains information about the Control HMI.
To access the Control HMI User's Guide (B0750AQ), click the Help icon in the
Control HMI Quick Access toolbar.
26 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
B0750AQ, Rev Z 27
Control HMI User’s Guide Chapter 3: Using Control HMI
1. Enter the domain if using a domain controller. Do not enter a domain name if
running in a local workgroup.
2. Enter your username and press Enter.
3. Enter your password and press Enter. If the user password is empty, click Login.
Control HMI will attempt to login when the password is entered. The dialog box will
automatically close if the login is successful. Otherwise, an unsuccessful attempt
message will appear.
If log in is not successful, open the OCMC Logger to review messages.
28 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
• Control HMI Framer cannot be used to configure Horns and Annunciator panels.
You need to use FoxView tools and utilities to configure Horns and Annunciators.
Annunciator panels and horns will be managed at runtime through FoxView and
the Alarm Manager displays.
• Control HMI Framer cannot be used to configure InTouch windows associated
with alarms. This feature is used in Annunciator panel configuration and when
selecting an alarm in the Alarm Panels to open the associated user display.
• Remote Desktop Server Clients (or Thin Clients) have to use the same
configured alarm subsystem as the Server station.
• Control HMI System and Process Alarm indicators will continue to show current
alarm states.
• ITCMD and DMCMD OM (Object Manager) variables are used to send supported
commands between FoxView and Control HMI. For instance, a button in FoxView
can be configured to open Control HMI windows in the WindowViewer. This
command will open “MyWindow” and then opens an AIN Detail Display faceplate
for “MY.AIN” in the Control HMI InTouch application:
ITCMD = “showwin MyWindow; stddisp MY.AIN AIN”
ITCMD and DMCMD OM (Object Manager) variables are used to send supported
commands between FoxView and the Control HMI.
HY1W03 is the virtual machine (VM) name where Control HMI is running.
DMCMDis the command to send instructions from Control HMI to FoxView.
2. Launch the display in FoxView from Control HMI using the command stddisp
<COMPOUND:BLOCK>.
In this example:
B0750AQ, Rev Z 29
Control HMI User’s Guide Chapter 3: Using Control HMI
30 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
Control HMI will show the same windows treeview as seen in WindowMaker, without
any additional configurations. It does not list Control HMI specific windows and
templates.
Customized navigation views can be created using Control HMI’s Framer Navigation
Browser configurator. The navigation browser configurator is used to create a custom
view and assign user and station-based access rules to folders and windows. For
more information, see Framer and Alarm Management User’s Guide (B0750AR).
B0750AQ, Rev Z 31
Control HMI User’s Guide Chapter 3: Using Control HMI
The navigation browser will only show windows and folders that the station, or user,
has permission to access. For more information, see Window Construction User's
Guide (B0750AS) and Framer and Alarm Management User’s Guide (B0750AR).
To open a window, double-click on the window name, or select the window and click
Show. The browser window will automatically close. Click Pin to keep the navigation
browser open.
2. Double-click on the window name to open the window on the selected monitor.
Navigation SoftPanel
SoftPanel, located on the Control HMI Action Bar, shows the alarm status of windows
assigned to the Navigation SoftPanel. Click SoftPanel to show the Navigation Soft
Panel.
The panel is divided into 3 levels: Areas, Cells, and Units. There are 12 Areas at the
top level. Each Area has its own set of 12 Cells and each Cell has its own set of 12
Units. Every Area, Cell, or Unit can be assigned a window and alarm using the
Framer. All active alarms propagate up to their parent level, which enables the
operator to find and identify windows in alarm easier.
General
Keys in the navigation panel show the assigned windows configured in Framer. The
keys will flash red or green if there is an active, unacknowledged alarm assigned to
the windows in each key.
32 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
All unit alarms are propagated up to the parent cell keys. Cell alarms are propagated
to the area keys, and area alarms are propagated to the SoftPanel indicator in the
Control HMI action bar.
Item Description
Selection or Current Navigation Location.
Highlighted
A window is assigned to this key.
Light Gray
No window is assigned to this key but a window has
been assigned to one of it sub-units.
Dark Gray
No window or sub-unit is assigned.
Subdued
The window assigned to this key or one of its sub-
units has an active unacknowledged alarm.
Red Flashing
The window assigned to this key or one of its sub-
units has an active alarm that has been
acknowledged.
Red Solid
The window assigned to this key or one of its sub-
units has an unacknowledged alarm that is no longer
active.
Green Flashing
This key has been selected.
B0750AQ, Rev Z 33
Control HMI User’s Guide Chapter 3: Using Control HMI
34 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
Favorites
The Favorites menu contains the list of favorite windows assigned by the user.
Each Control HMI operator can have their own list of favorite windows. Windows are
assigned to the favorites list from the Navigation Browser. Open the Navigation
Browser and right-click on the window name and select Assign Favorites.
B0750AQ, Rev Z 35
Control HMI User’s Guide Chapter 3: Using Control HMI
Click any Shft+# to assign the window. This dialog box remains open until it is closed.
Users can select other windows in the browser and assign them to a different Shft.
Windows are saved to the key automatically. Close the dialog box when assignments
are complete. To remove a window, click the X next to the window’s name.
Recent Windows
The Recentmenu contains a list of windows that have been opened on each separate
monitor. The recent list, on monitor 1, contains a list of windows that were opened on
monitor 1. Monitors 2–4 have their own separate list.
Select one of the listed windows to reopen it. Not all windows are added to the list.
Windows added to the list include:
• InTouch Replace type windows that are open via the Control HMI’s Show quick
function.
• InTouch windows that are opened from the Control HMI navigation browser.
Windows not added to the list include:
• InTouch Overlay and Popup type windows.
• Windows opened using the standard InTouch Show functions and animations.
36 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
Block Select
Block Select provides a view of deployed Foxboro DCS controllers, compounds, and
blocks. Operators can use Block Select to open compound and block detail displays
(for more information, see Detail Displays, page 60). Block Select can also be used to
review the control database and generate reports. For more information, see Chapter
5: Block Select, page 131.
Block Select can be opened by clicking Block Select in the Control HMI Quick Access
toolbar, or by selecting Block Select from the Control HMI’s Utilities menu.
Tag Bar
The Control HMI Tag Bar is located on the Control HMI Action bar and provides
access to utilities and features that are related to a selected or entered tag reference.
When a Foxboro DCS IO reference is selected or entered into the tag name field, the
Control HMI collects information about the tag and enables tag related features that
are available to the current operator.
Tag Name An operator can select a tag from the Control HMI detail
display or enter the name of a tag. This field shows the last
tag that was entered or selected. For more information, see
Window Construction User's Guide (B0750AS).
Recent Tags Menu Click the down arrow to open a list of recent, selected, or
entered tags. Select any item to show it in the tag name field.
Open Detail This is enabled if the current tag is a valid Foxboro DCS IO
Displays reference. Click this to show the detail display in the next
available faceplate location.
Faceplate Displays Use this menu to show a detail display in specific faceplate
Grid grid location.
Assigned User This will open a user assigned display if the references were
Display configured in Framer. It will show the block detail display if it
has not been assigned to a display.
B0750AQ, Rev Z 37
Control HMI User’s Guide Chapter 3: Using Control HMI
Tagname Field
Entering a Control Block Tag
When the entered point is a control block tag, Faceplate Map and Source will
become active.
38 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
A Tagname
B Edit Block
The Quick Block Editor (QBE) is part of the Control HMI Tag Bar. Clicking Edit Block
from the CHMI launches the Control Editors of the selected block in the IDE for
Control Software. This helps eliminate the need to manually search for the controller
compound or strategy that contains the block in the IDE to launch its editor.
If you have the IDE permission configured in Framer, you can access the QBE
through on of these methods:
• CHMI Tag Bar
• InTouch Scripts
• Graphic Commands
• Preference Commands
When you use the QBE it:
• Launches the IDE.
• Brings the IDE to the foreground if it is running in the background.
• Maximizes the IDE if it is minimized.
The QBE always opens the editor for the selected block in the Blocks tab of the
Strategy Editor of the IDE.
NOTE: You might need to enter a valid username and password when using the
QBE depending on your security settings.
B0750AQ, Rev Z 39
Control HMI User’s Guide Chapter 3: Using Control HMI
A Tagname
B Edit Block
2. Click Edit Block to launch the IDE with the editor of the selected block.
These are valid string formats that you can enter in the Tag Bar to launch the
QBE:
• Compound:Block.[Parameter]
• Compound:Block.[Parameter]#Ext
• Compound:Block
• Compound.Block.[Parameter]
• Compound.Block.[Parameter]#Ext
• Compound.Block
40 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
• Compound.Block
A Tagname
B Alarm Shelving
2. Click the Alarm Shelving button to open the Alarm Shelving Utility.
Watch Panel
This panel displays the current value of user-assigned parameters in a tabular form.
Each line in the window displays the name of the parameter along with the current
value. Up to 27 parameters – three columns of nine lines each – are available. The
values of settable points can also be modified from this panel. Control Core Services,
Galaxy or InTouch Memory tags can be assigned to the Watch Panel.
Watch window connections are retained, if the watch overlay is closed.
You can select/assign parameters to the watch window. The system detects the data
type and an indicator is shown next to the tag name. The indicators and data types
are:
• D - Discrete
• I - Integer - no decimal points in the Value field.
• M - Message
• R - Real Floating Point - Floating point precision will automatically update based
on Decimal precision configuration settings for the WindowViewer application.
B0750AQ, Rev Z 41
Control HMI User’s Guide Chapter 3: Using Control HMI
To configure an Click in the Tagname field and enter a control block tagname or
item on the AppObject reference, and press Enter.
panel
• Control Core Services Point Format - COMPOUND.
BLOCK.PARAMETER
Galaxy and Local DI Object name will be added
automatically.
◦ AppObject Format - Galaxy:AppObject.Attribute
◦ InTouch Format - InTouch:Tagname
To assign a point Click on a data field so that the tag string appears in the Tag bar,
from a faceplate then click an A to assign it.
To delete an item Click its associated Del and it is deleted without confirmation
To change a Click in the Value field next to the point, enter the new value,
point value and press Enter.
The point will not change if it is secured or the operator does not
have proper security clearance.
To change Select the “.” indicator next to the point to toggle through the
floating point available decimal settings.
precision view
Historian Trends
The historian trends panel is used to view historical data from the AVEVA Historian.
Only points being historized can be added to these trends. Up to four historian trends
can be shown at the same time. There are four window sizes to select from which can
be shown in several different locations:
• Small - 1/6 the screen in the:
◦ Upper left or right of the program window
◦ Middle left or right of the program window
◦ Lower left or right of the program window
• Medium - 1/3 screen in the top, middle or bottom of the window
• Large - 2/3 screen in the top or bottom of the window
• Full window
You can create named sets of points to be displayed within the trend. For more
information on AVEVA Historian trending functionality, see the AVEVA user
documentation.
NOTE: Use Window Authentication when adding historian servers to the historian
trends or the tag picker window. Windows Authentication helps provide enhanced
security.
42 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
The application properly configures the support entities only if you log in with SQL
administrator privileges. Once configured, SQL administrator privileges are not
required.
When an AVEVA Historian Client application or trend connects to an AVEVA Historian
Server, it validates the presence of required client control support in the Runtime
database (for example, stored procedures and tables). If the supporting entities are
not found, the user must log into the Historian Server with an account that has SQL
administrator privileges. This can be done from the Historian Client Trend application.
1. Right-click the Trend Control and from the menu, select Tools > Servers.
The Server List Configuration dialog appears.
B0750AQ, Rev Z 43
Control HMI User’s Guide Chapter 3: Using Control HMI
44 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
2. Use the resize buttons, on the title bar, to open the trends in a different size.
These buttons allow you to resize the window to small, medium, large, and extra
large.
NOTE: When the small window is used there is insufficient area to display all
actions. Therefore, a window is accessed by clicking Trend Action. All
actions are the same as those found on the larger trend windows.
Item Description
Click to print to the computer's default printer. If there is no default
printer, a dialog appears and assists you in configuration.
Print Graph
Opens the InSQL File Browser dialog. See Saving Historian
Server Trends, page 49 and Loading Saved Historian Server
Trends, page 50.
Save and Load Dialog
B0750AQ, Rev Z 45
Control HMI User’s Guide Chapter 3: Using Control HMI
Item Description
Pan the trend to the left or right.
Item Description
Trend X-Axis Options
Toggles the Time toolbar on/off.
Show Time Toolbar
Toggles the trend's time format between Date/Time and Relative
Time format.
ShowTimeStamp or Relative Time
Zooms the window in/out on the time axis. See Trend Properties,
page 50.
Zoom In On Time Axis/Zoom Out On Time
Axis
Item Description
Shows the scale for each configured tag, next to the trend graph.
46 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
Item Description
Shows the selected Tag as a single line trend, hiding all other tags.
Single Tag
Changes the trend view to multiple trends, one for each point, and
stacks them.
Stack Graph
Toggles the X-axis cursor on/off.
Item Description
Assigns the selected tag that appears in the HMI Tag bar. The
point will only be added, if it is being historized.
Assign Tag from Menu
Open the Tag Browser dialog as a stand alone. See Using the
Tag Browser/Tag Picker, page 51.
Show Tag Browser Dialog
Item Description
Removes and deletes the tag from the Trend window.
Delete Tag
Removes and deletes all tags from the Trend window.
Item Description
Remove the pen line from the graph. It does not delete the pen.
Hide Pen
Opens the standard Windows Color dialog to associate the
selected pen with a color.
Select Pen Color
Highlights the trend line of the selected tag.
Highlight Tag
B0750AQ, Rev Z 47
Control HMI User’s Guide Chapter 3: Using Control HMI
Item Description
Automatically scales the value axis range to reflect the actual data
currently being displayed for the trend. For example, if the default
value axis range is 0 to 3000, and the data ranged from 1827 to
2059, the scale might be automatically adjusted to a range of 1800
to 2100. The adjusted scale does not exactly match the actual
minimum and maximum data values for the chart. The calculation
rounds the values so as to make the chart easier to read. Also, a
percentage allocation is added to the final values so that the
adjusted scale fits within the boundaries of the trend chart.
Autoscale Tag Therefore, the adjusted scale will be a round number slightly
above the actual data values. You can automatically scale a single
tag or all of the tags in a trend. For information on resetting scale
back to the original default, see Returning Tags to Their Original
Scale. Autoscaling is not performed continually for a trend. Also, if
the trended data includes points outside of the scale region, an
indicator ( ) is displayed to remind you to perform a second
autoscale operation.
Scales the selected tag up. It doubles the tag's scale. For
example, if the scale is 0 to 20, it becomes 0 to 40.
Move Tag Up
Scales the selected tag down. It halves the tag's scale. For
example, if the scale is 0 to 20, it becomes 0 to 10.
Move Tag Down
Enable or disable rubber band scaling for the selected tag (s). Use
rubber band scaling so that an area of the trend chart can be
dragged with the mouse to automatically adjust the time axis scale
based on the area selected.
Enable/Disable Rubberband Scale for Tag
The Rubber Band Zoom increases the view of the selected area
up to 500% of its default size.
Item Description
Same as Selected Tag except that it is applied to all tags in the
trend.
Autoscale Tag
Same as Selected Tag except that it is applied to all tags in the
trend.
Scale All Tags Up
Same as Selected Tag except that it is applied to all tags in the
trend.
Scale All Tags Down
Same as Selected Tag except that it is applied to all tags in the
trend.
Enable/Disable Rubberband Scale for Tag
Uses one scale for all assigned pens. A dialog will open to assign
the upper and lower scale limits.
Select One Scale for All Tags
48 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
Item Description
Opens the Trend Properties dialog. See Trend Properties, page
50.
Trend Properties
Causes the previous or next tag to be selected.
1. Click the Time toolbar icon , if the toolbar is not already present.
2. Configure the time range by peforming one of these actions:
• Click the down arrow to access the Custom menu and select the duration
from the list.
• Enter a From and To range in the fields provided and click Apply.
B0750AQ, Rev Z 49
Control HMI User’s Guide Chapter 3: Using Control HMI
Trend Properties
Use this window to configure the properties for the Trend window and files as a whole.
The trend file properties are saved with the trend file. Configurable trend properties
include:
• General Properties
• Color Properties
• Axes Properties
• Limits Properties
• Summarized Data Properties
• Annotation Properties
The property dialog boxes shown are described in the AVEVA user documentation.
50 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
B0750AQ, Rev Z 51
Control HMI User’s Guide Chapter 3: Using Control HMI
Each ScratchPad Trend has access to an embedded Tag Browser or a separate Tag
Browser dialog. On smaller trends, there is not much space for displaying this
embedded control so a separate dialog is provided.
NOTE: Framer includes settings to automatically fill in the Tag Picker dialog and
log onto the configured server.
Click Tag Browser . The Tag Browser will automatically connect to the
AVEVA Historian Server and open to the Tag Picker dialog, if these InSQL Framer
configuration settings are properly configured:
• Server name
• Login name
When the dialog opens, it will show a login dialog box. Click OK to complete the login
and connect to the server.
If the Tag Browser cannot log into the Server, right-click on the server in the Servers
list, and click LogOn. The Connect Server dialog opens, showing the server name
that is being connected to and the Login ID and password being used to login. If any
of these fields are wrong, you must update settings in Framer. Do not select Use
Integrated security checkbox.
52 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
Server Name
Do not check
this box
Login ID
Password
The Server Name is not editable from this dialog. Enter a valid Login ID and Password
for the selected server. If the login settings configured with Framer are incorrect, this
dialog will appear each time the Tag Browser dialog is opened. To help prevent this
dialog from opening, specify valid login information through Framer. The operator may
retype new values to login but if the default values are wrong, the operator will need to
login each time the Tag Browser dialog is opened until the settings in Framer are
updated.
The values in the “Timeouts in seconds” field in the dialog has to be set to your
desired values. The default timeout for queries is two minutes. The WindowViewer
application collects data from the server every cycle. If the server is busy or it
disconnects, WindowViewer will try to reestablish communications with the server for
two minutes before timing out. All other window updates and actions will be
suspended until the two minutes timeout expires.
• Connection is the connection timeout in seconds between 1 and 600.
• Query is the query timeout in seconds between 1 and 600.
CAUTION
RISK OF OPERATOR CONTROL LOSS
The WindowViewer application will freeze if the Historian Server is not connected
and a window with a Historian Client Control is opened or is opening. The
WindowViewer application will freeze until this timeout setting expires, or the
Historian Server is connected. When configuring timeout settings, it is
recommended that you set the range to 5-20 seconds to minimize the duration of
timeouts when the connection to the Historian Server is broken.
Failure to follow these instructions can result in operator control loss.
For detailed information about standard log in procedures and settings, see the
AVEVA user documentation.
B0750AQ, Rev Z 53
Control HMI User’s Guide Chapter 3: Using Control HMI
If the server is not connected, you can manually login. The embedded Tag
Browser will retain the logged in user.
2. Right-click on the server name.
3. Click Log On.
The Connect Server dialog opens.
4. Enter your Login ID and password.
5. Click OK.
54 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
Additionally, the series of tabs below the Tags pane filters tag shown by:
• Analog - Analog tags only
• Discrete - Discrete tags only
• String - String tags only
• Event - Events only
• All - Returns all tag to the Tags list
This table lists wildcard characters for use as part of the filter criteria:
For example, to find all tagnames ending with level, enter %level.
When the:
B0750AQ, Rev Z 55
Control HMI User’s Guide Chapter 3: Using Control HMI
• Servers pane and the Filter pane are both visible, the filter conditions apply to the
selected group in the Servers pane.
• Servers pane is hidden, the filter applies to all of the tags for the selected AVEVA
Historian Server.
The filter criteria is not case-sensitive.
1. In the Server field, specify or verify the server.
If the Servers pane is visible, this field is not available.
2. In the Tag name field, enter the string to match for the tagname.
3. In the Description field, enter the string to match for the description.
4. In the I/O Address field, enter the string to match for the I/O address.
5. Select Exact match to search for tags that exactly match the entire string (and no
more) provided for the tagname and description.
For example, if you specify level as the tagname and Exact match is not
selected, any tagname that contains the string level appears. For example,
ReactLevel, ProdLevel, and AccessLevel.
Exact match does not apply to the I/O address.
6. Click Apply to apply the filter criteria.
Preferences
The preferences dialog is accessed from the Control HMI Quick Access Toolbar.
Data entry settings only apply to Control HMI windows that are designed to switch the
data entry functionality. This setting can be used in user-built windows and symbols by
performing these steps:
1. Create 2 text boxes with a user input animation.
• Textbox1 — User input with Use Keypad option checked.
• Textbox2 — User input without Use Keypad checked.
56 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
2. Add a visibility to each text box connected to the boolean InTouch tag ZHMI-App-
DataEntry-Style.
• True — Textbox1 (use keypad) is visible.
• False — Textbox2 is visible
NOTE: The resizable options apply to only the Industrial Graphic Detail Display
windows. They do not apply to legacy smart symbol detail display windows.
Help - QuickKeys
The Shortcut Keys dialog box shows a list of available shortcut keys and actions.
B0750AQ, Rev Z 57
Control HMI User’s Guide Chapter 3: Using Control HMI
Help - About
To access the About dialog box, click Help > About.
Help - About provides version and quick fix information for:
• Control Software
• Control HMI
• Control Core Services
If you are using a read-only license, Read-Only License appears across the top of
the dialog box.
58 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
B0750AQ, Rev Z 59
Control HMI User’s Guide Chapter 3: Using Control HMI
Detail Displays
A Detail Display is a Control HMI window that contains a single faceplate style symbol
connected to a single block in the controller. Up to eight Detail Displays can be
opened at one time.
NOTE: By default, only three Detail Displays are available in the Control HMI
Template. To add more, see Window Construction User's Guide (B0750AS).
Detail Displays are being enhanced and migrated to newer Industrial Graphic
technology. The Control HMI has two styles of Detail Displays while displays are being
updated. The more widely used control blocks are being upgraded first.
• Industrial Graphic Style Displays
Industrial Graphic Style Detail Displays can be customized and configured to
replace the Control HMI graphic symbols.
For more information see Window Construction User's Guide (B0750AS).
60 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
• Open a CMD window and use pref to execute a stddisp DMCMD command.
• Perform these Control HMI actions and use the Control HMI Tag bar Grid selector
to open a Detail Display.
◦ Enter the full COMPOUND.BLOCK in the Tag field of the Control HMI Tag bar.
◦ Select an updating field within a Detail Display or other display object that
uses the Control HMI Industrial Graphic or InTouch Smart Symbols.
◦ Select an alarm from the Alarm Panel.
◦ Select a tag from the Tag bar list of previously used tags.
InTouch Style shows which blocks have not been upgraded to the new design.
B0750AQ, Rev Z 61
Control HMI User’s Guide Chapter 3: Using Control HMI
62 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
General Features
These features are only available with Industrial Graphic style Detail Displays.
• Tooltips available on all values that shows the parameter name and value.
• The main Detail Displays can be pinned open using the icon.
• The Quick Block Editor can be opened directly from the displays using the
icon.
• The sequence code views automatic attempts to connect to the block’s CP host
station and shows the HLBL source code. You must already have access to the
host station before a connection can be made. Otherwise, the code view will
search the local station for the source code.
B0750AQ, Rev Z 63
Control HMI User’s Guide Chapter 3: Using Control HMI
• The Detail Views have a tabular interface for showing related values. For
example, the IO page of the PIDA detail view has three tabs for showing the Main
IO values, Feed Forward Values, and Supervisory settings.
• When ramping an analog value, the ramp buttons have a configurable ramp
factor setting that allows you to increase or decrease the ramp rate from the
standard one or five units or percent. The one and five ramp rates are multiplied
with the ramp factor to change the rate.
64 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
Layout
When opening a Detail Display, the first window that appears is the main DD faceplate
window. The layout and functionality is similar to the Control HMI InTouch Detail
Display.
The Detail View window, larger but with a similar layout, opens beside the main
window.
B0750AQ, Rev Z 65
Control HMI User’s Guide Chapter 3: Using Control HMI
Depending on the block type, this area will show key states of the BLKSTA parameter
such as Manual/Auto, Local/Remote, Hold, Interlock, etc.
66 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
The block status indicator includes a tooltip that explains its meaning.
The alarm status indicator shows the current alarm state of the block. The alarm
status color represents the priority of the alarm and its current acknowledged state.
When an alarm is unacknowledged, the indicator is filled with the alarm color and has
a white border.
• The inhibit icon is shown when the alarm is disabled or the block alarms are
inhibited.
The selections in the bottom right corner of the window are used to:
B0750AQ, Rev Z 67
Control HMI User’s Guide Chapter 3: Using Control HMI
◦ Detail Views
◦ Block Actions
◦ Parameter Actions
See the images in Views, Blocks, and Parameter Actions, page 68 for a
detail view of the action mode options.
• Open the Trend window for the block.
Detail Views
This set of options shows the detailed views available for the block type. This view
contains different parameter values based on how they are related to the block. For
example:
• IO — Shows parameters related to the input and output of the block.
• ALARM — Shows parameters related to alarming.
• TUNE — Shows parameters related to tuning.
• CONFIG — Shows parameters related to block configurations settings.
NOTE: Some parameters are shown on multiple views and tabs.
Block Actions
This set of options provides the user with one-click access to key block mode
operation values such as Manual/Auto, Local/Remote, Hold, etc..
68 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
Parameter Actions
This set of options is available when a configurable parameter is selected. The
available actions are based on the type of parameter selected.
Inputs Outputs
B0750AQ, Rev Z 69
Control HMI User’s Guide Chapter 3: Using Control HMI
70 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
The trend shows real and historical values. The parameter must be historized and the
InSQL Framer setting must be set to the name of the Historian Server.
B0750AQ, Rev Z 71
Control HMI User’s Guide Chapter 3: Using Control HMI
72 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
• When you hover the mouse cursor over the chart area, a window will display the
values of all pens beneath the cursor.
B0750AQ, Rev Z 73
Control HMI User’s Guide Chapter 3: Using Control HMI
The STEPS view does not automatically refresh if new steps are deployed while the
window is open. Click the Refresh icon to get the latest steps.
74 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
HLBL code is not available on all stations unless it is manually copied to all stations.
The CODE detail view will attempt to locate the host station that contains the code
and load it. If the user does not have access to the host station, the CODE view and
the CP Host will display a “not found” and “not connected” message. The CODE view
will search the local workstation for the code.
• The CODE view includes a menu for available DCS workstations. This menu can
be used to search for source code on other stations.
• The STEPS tab shows the formatted code that includes step and sub-routine
numbers.
• The STEPS tab can search for an enter string and jump to the code location if a
match is found.
• The SOURCE tab shows the raw source code.
B0750AQ, Rev Z 75
Control HMI User’s Guide Chapter 3: Using Control HMI
Each tab contains four channels and the status of the relative set of modules.
• If any of the eight modules are in an abnormal state, a status icon appears on the
module status bar. Click Show all to show all modules in a single view.
Click Show All a second time to close this view and return to the Channel Tab
views.
• If any channel, on any of the tabs is in an abnormal state, a status icon appears
on the tab where the channel is assigned.
From any channel tab, the user can select a channel to show that channels
configuration information.
You can use the page options to switch between channels, or use Close (upper
right), to return the main view.
76 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
This table highlights general Detail Display features. Not every Detail Display contains
all features.
B0750AQ, Rev Z 77
Control HMI User’s Guide Chapter 3: Using Control HMI
Item Description
Switches the button view from Paging
buttons to Action buttons. It appears only
when in paging mode.
Perform an Action
Opens a real time trend of the block’s most
important parameters.
Trend
Switches the button view from Action buttons
to Paging buttons. It appears only when in
action mode.
Detail View
This area has two labels which can be
configured in Framer, an Exit options, and
the Block type.
This area also includes a Block Type and
Version Indicator.
• Block Type and Version:
◦ Block type label appears in lower
right corner
◦ If enabled, the Block type will include
an “*” when the faceplate is not at the
latest revision - such as PID*
• Configurable labels views include:
◦ Description
◦ LoopID
◦ COMPOUND.BLOCK
◦ COMPOUND
◦ BLOCK
◦ [Empty]
• Selecting the top label will assign the
COMPOUND BLOCK to the HMI Tag
bar:
◦ Holding the top label Selection will
allow the operator to move the
faceplate.
◦ When a faceplate has been moved,
Restore appears next to Exit.
◦ Click Restore to return moved
faceplates to their original location.
• Selecting the bottom label will cycle the
bottom label through the different label
views.
• Click Exit to close the faceplate.
Click this icon, which appears in the upper
right corner of the detail display, to return the
faceplate to its previous location.
78 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
Item Description
B0750AQ, Rev Z 79
Control HMI User’s Guide Chapter 3: Using Control HMI
Item Description
A graphical representation of block values.
This area might contain other indicators such
as Alarm Limits, Clamping Values and Data
Quality.
• Click or to ramp a
value by 5% percent or by a preset
engineering unit.
• Click or to ramp a
value by 1% percent or by a preset
engineering unit.
◦ Percent of Scale -
calculates a ramping value from the
High and Low Scale of the
parameter.
◦ Absolute EU - Uses a
fixed value for ramping - 1 unit is
equal to either 1 or .1 depending on
the parameter scale.
80 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
Item Description
Toggle - Toggles a selected boolean on/off
for Boolean blocks, such as CALCA. Click in
any Boolean field and this appears.
NOTE: Toggle is shown when a
configurable Boolean parameter is
selected.
Adjust process variables in this area. Areas
with a:
• Light grey backgrounds indicate
adjustable fields.
• Dark grey backgrounds indicate display
only fields.
B0750AQ, Rev Z 81
Control HMI User’s Guide Chapter 3: Using Control HMI
Meas 6 5
2 SPT
RSP
SPT ramp target (PIDA)
3
Clamps
OUT OUT HI and
LO Alarms
4
1 Indicates a HiHi Alarm Limit and its value. It will flash, if its alarm is active.
2 Indicates Lo and Hi Alarm Limits and their value. The range indicated by
the yellow is the range between the LoLo and HiHi. The red range is the
range beyond the configured HiHi value. It will flash, if its alarm is active.
3 Indicates a LoLo Alarm Limit and its value. It will flash, if its alarm is active.
4 Indicates the Output percentage. It will flash, if its alarm is active.
5 Indicates the percentage of the configured SPT (on the left) and the
percentage of the RSP (on the right).
The clamps will change to white, if value is being clamped.
The SPT Target will flash when setpoint ramping is active (PIDA only).
6 Indicates a deviation alarm is configured, along with it limit.
This appears only on a Detail View.
Text
Meaning Indicator Character Color Example
Data value is ***** ^ Cyan
unavailable to Control
HMI, i.e. the
DAServer is not
available.
Connection to ***** ~ Cyan
DAServer is OK, but
no data from I/A, i.e.
invalid tagname
82 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
Text
Meaning Indicator Character Color Example
Internal Control HMI 123.45 ? White
data quality pending,
i.e. a write operation
has
not completed
Internal Control HMI 123.45 $ White
data quality security,
i.e. tried to write value
without authorization
Data value is out-of- 123.45 * Cyan
service or has
transitioned to
unavailable on the
Control Core Services
network
Data value has a Bad 123.45 ! Red
status
B0750AQ, Rev Z 83
Control HMI User’s Guide Chapter 3: Using Control HMI
For more information about a block, click Detail to show the available Detail
Views listed on the right side of the detail display.
Detail View
Buttons
Clicking any of the Detail View buttons will open a new view of the block. This figure
shows that the IO-1 View was selected (its button is highlighted on the right side of the
overlay). It also shows that there are 3 detail pages to this view, MEAS, SPT and OUT,
and that MEAS is the current page (this button is highlighted on the bottom of the
overlay).
84 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
Detail Page
Buttons
Clicking the highlighted View button will close the Detail View and return to the main
detail display view. Clicking any other Detail View or Page button will display a new
set of data for the block.
This figure shows a typical Alarm View with four Alarm Pages.
The CNFG views typically hold Block Setting, Override and State parameters. This
figure shows the PID Configuration View.
B0750AQ, Rev Z 85
Control HMI User’s Guide Chapter 3: Using Control HMI
These figures show various tune pages for PID Blocks. Tune pages change based on
the type of PID Block - PID, PIDA, PIDX, PIDE or PIDXE.
86 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
B0750AQ, Rev Z 87
Control HMI User’s Guide Chapter 3: Using Control HMI
88 B0750AQ, Rev Z
Chapter 3: Using Control HMI Control HMI User’s Guide
Scrolls up
and down
through the
pens.
The Trend window will always open with a predetermined set of parameters
depending on the block type. To add parameters to this instance of the trend, click the
B0750AQ, Rev Z 89
Control HMI User’s Guide Chapter 3: Using Control HMI
1. Click the icon in the trend to open the Trend Properties panel.
2. Select one of the 16 pens.
3. Select the Name field and enter an AppObject reference or control block Tag
name to trend:
• AppObject Format - Galaxy:AppObject.Attribute
• Control block Format - COMPOUND.BLOCK.PARAMETER
4. Click Apply (upper right).
1. Select an active process variable so that the tag name appears in the HMI Tab
bar.
2. Select a pen on the Properties page.
3. Click Assign .
4. Click Apply (upper right).
Restoring a Pen
This button restores the Properties page to its original state or to the last time the
Apply button was clicked. After you click Apply, all old settings are overwritten.
Clearing a Pen
1. Select a pen.
90 B0750AQ, Rev Z
Chapter 4: Control HMI Alarm Management Control HMI User’s Guide
Alarm Queries
Alarm panels use a query that collects a set of records from an alarm source. Each
type of alarm panel has its own set of alarm queries. The alarm queries are logically
assigned to the different alarm panels based on what is in the query. For example, the
Device Condition Alarm panel is designed to view alarm records provided by the
Fieldbus Alarm Provider. Any alarm query that collects alarms from the Fieldbus
Alarm provider are assigned to the Device Condition Alarm Panel.
The alarm panels also have the ability to view different types of alarm messages.
When the alarm panel is in Summary mode, the alarm panel shows alarms that are
currently active. When in Historical or Event mode, the alarm panels show a limited list
of the most recent event or alarm messages that have been received by the Alarm
Provider. Default alarm queries that are configured in Framer include the type of
messages to be shown. The type of message also determines where a query is
B0750AQ, Rev Z 91
Control HMI User’s Guide Chapter 4: Control HMI Alarm Management
assigned. For example, any default query that is configured for Historical messages
will be assigned to the System alarm panel.
The alarm query can contain one or more alarm provider queries, each separated by a
space. The format of a query is:
\\Node:0\Provider1\Group \\Node:0\Provider2\Group
\\Node:0\Provider3\Group
• Node is the name of the station where the alarm provider is deployed and must
include the ‘:0’ suffix
• Provider is the name of the Alarm Provider that is collecting alarm messages.
• Group is the name of the Area or Group of alarms to be shown.
Queries that are defined in Framer or saved at runtime can be selected at runtime in
each alarm panel. Each alarm panel shows the list of queries that is appropriate for
that panel. The criteria for determining which queries are presented with each alarm
panel are listed in this table.
Alarm Bars
The Alarm Bar area appears in the top center of the legacy UI window. It is an
Industrial Graphic that can be added to a customized Modern UI menu and header
graphic. The Alarm Bar features are:
• Show/Hide Process Alarm button
• Show/Hide System Alarm button
• Show/Hide Process Alarm bar
◦ If System Alarm Bar is not enabled, the Process Alarm Bar will show multiple
lines.
• Show/Hide System Alarm bar
◦ If Process Alarm bar is not enabled, the System Alarm bar will show multiple
lines
92 B0750AQ, Rev Z
Chapter 4: Control HMI Alarm Management Control HMI User’s Guide
See Window Construction User's Guide (B0750AS) for detailed configuration options
and workflows.
B0750AQ, Rev Z 93
Control HMI User’s Guide Chapter 4: Control HMI Alarm Management
94 B0750AQ, Rev Z
Chapter 4: Control HMI Alarm Management Control HMI User’s Guide
See Framer and Alarm Management User’s Guide (B0750AR) for detailed
instructions on configuring the alarm display.
B0750AQ, Rev Z 95
Control HMI User’s Guide Chapter 4: Control HMI Alarm Management
A Tool bar: Provides quick access to common actions such as Pause, Show Alarm Display, Save, and Ack
Selected.
B Status Indicator bar: Shows key information related to what is shown in the alarm record area.
C Action bar: Operator actions are shown in this area. The type of actions is determined from the Action
Selection Bar.
D Action Selection bar: Operator uses these buttons to show different actions in the Action Bar.
E Alarm Records: Shows all messages returned from the Query and Filter query.
F Filter & Query Treeview: Show all configured Queries and Filters. Operator can change the query or
enable and disable filters from these views.
96 B0750AQ, Rev Z
Chapter 4: Control HMI Alarm Management Control HMI User’s Guide
A Alarm Query String: This is the current alarm query used to show alarms.
B Modify Query: Click to enable editing the alarm query string.
C Restore Default Queries: Click to reload the original Framer, and User saved, queries and filters.
D Save Query: Save the current query string as a new query. This query is only available on this alarm
panel for the operator that created it.
E Priority Form: Set the minimum priority range value
F Priority To: Set the maximum priority range value.
G Apply Priority Range: Apply priority range changes to the alarm query.
Modify Query
Clicking Modify Query will change the appearance of the Action bar and allow the
operator to temporarily change the current alarm query string.
B0750AQ, Rev Z 97
Control HMI User’s Guide Chapter 4: Control HMI Alarm Management
A Edit Field
B Apply Changes
C Cancel Edits
Use the edit field to modify the query. Changes are not applied to the alarm panel until
the Apply Change button is clicked. Use the Cancel button to close the view and not
modify the query.
Saving Queries
Save Query adds and saves the current alarm query string to the list of available
runtime queries. To save the modified query string:
1. Click Save to open the Save Query interface. The Alarm Provider Query is
displayed on the left and cannot be modified.
2. Enter the name of the Query. The name must not already exist. The Enter Name
field will be highlighted if the name already exists. The Save button will not be
enabled until a valid name is entered.
To show a priority range of 1 value, set both fields to the same range value and click
Apply.
98 B0750AQ, Rev Z
Chapter 4: Control HMI Alarm Management Control HMI User’s Guide
A Column Selector
B Condition Selector
C Filter Value
D Create Filter
NOTE: The Alarm History Panel does not support the Filter Action Bar. To create
custom filters, use the Query and Filer dialog box. See Query and Filter Dialog
Box, page 108.
Column Selector
Choose the column to create a filter on.
The dropdown list contains the configured list of columns that users can filter. The
items in the list can be modified or removed from the Framer configuration tool. For
detailed instructions on customizing Alarm Panel Filters, see Framer and Alarm
Management User’s Guide (B0750AR).
Condition Selector
Choose the match condition for the filter.
This dropdown list contains the available match conditions for the selected column.
Each column may have different allowed match conditions such as: =, !=, Like, Not
Like, etc… When using wildcards in the filter, use the Like and Not Like conditions.
Filter Value
Enter the value that you want to match in the column.
This entry field is used to set the match value. When using the Like or Not Like
condition, the filter will support wildcards. For example, to find all tags that contain
“CV123” the settings would be: Tagname such as %CV123%
For more information on the usage of wild cards in filters and queries, see Queries,
page 127.
B0750AQ, Rev Z 99
Control HMI User’s Guide Chapter 4: Control HMI Alarm Management
Renaming a Filter
1. Right-click in the alarm record area to open the context menu.
2. Select Queries and Filters to open the dialog.
3. Click “…” next to the filter that you want to modify. This opens the Modify Query
or Filter dialog.
4. Modify the name in the top entry field. Make sure to remove the “qf_” prefix. The
“qf_” prefix identifies temporary filters.
5. Click OK on each dialog box to save and close the edit dialog boxes.
See the AVEVA user documentation for instructions on how to create and
configure alarm queries and filters.
NOTE: Hide and Unhide functionality is not available when the alarm panel is paused.
The Shelving actions on this bar work with external shelving utilities. When installed
and configured properly, these buttons will work with the AST or the ASU. To shelve
AVEVA App Object Alarms use the right-click context menu from the alarm record
area.
• See Alarm Shelving Tool (AST) Software Configuration and Administration Guide
(B0700CZ) for more information about the legacy Alarm Shelving Tool.
• See Alarm Shelving Utility User’s Guide (B0750HC) for more information about
the Alarm Shelving Utility for System Advisor - Process Control.
• See Framer and Alarm Management User’s Guide (B0750AR) for more
information about enabling and configuring ASU or AST.
Button Description
Paused When the alarm panel is frozen, or paused, the
PAUSED status indicator appears. The Pause button
is highlighted to the user. When paused, the alarm
record does not update and new alarms are not
shown until un-paused.
Filtered The Filter indicator appears when there are active
filter is applied to the alarms. The Filter indicator is
highlighted to the user because active alarms may be
filtered out of the view.
Button Description
Alarm Client Mode The alarm control can operate in different modes. This
indicator shows what mode is active.
• Active - This indicator is shown when the alarm
control is showing current alarms.
• Events - This indicator is shown when viewing
recent event message. This indicator is
highlighted as a reminder that active alarms are
not in view.
Selected This indicator shows the number of alarms that the
operator has selected. The tooltip for this indicator
shows the name of the first tag name in the selection.
Only the first tag is used when performing actions like,
Show Alarm Display or Show Detail Display.
Hidden Shows the number of alarms that were hidden. This
indicator is highlight when active alarms are hidden.
UNACK Shows the number of unacknowledged alarms in the
current alarm view.
Tool Bar
The Tool bar provides one click access to common actions. Each tool button includes
a tooltip that displays what it does. When no actions are selected, the toolbar displays
a basic tool bar. Select Tools in the Action selection bar to show all toolbar buttons.
A Play
B Pause
C Show Sort
D Reset Sort
E Current Alarm Mode
F Recent Message Mode
G Show Alarm Display
H Show Detail Display
I Show Query and Filter Dialog
J Save current Query and Filters
K Acknowledge selected alarms
• Open the Query and Filter Favorites dialog box from the toolbar or from the
Alarm panel menu.
Queries are listed in the top list and only one query can be active at a time. Filters are
listed in the bottom list and any number of filters can be active at the same time.
• To change the active query, select the desired query and click OK.
• To change active filters, select or clear the desired filters and click OK.
To create new queries or filters click the + that is above the list of Queries or Filters.
This opens the Add Query or Filter dialog box.
A and D Expand/Collapse View: Click to show or hide the Query and Filter
Treeview.
Opening the View will automatically refresh the list of queries and filters.
The alarm panel is resizable. At a certain size, this side pane will
automatically close and become disable. It will remain disabled until the
panel size is wide enough to support it.
B Query List: Shows the list of available queries. Activate a query by
selecting the checkbox next to the desired query. Only one query can be
enabled at a time.
C Filter List: Shows the list of available filters. Activate any number of
filters by selecting or clearing the boxes next to the desired filters.
E Refresh Query Filter List
G and F Increase/Decrease Size: Click to change the width of the side pane. The
side pane only supports 3 sizes, 200, 400, and 600 pixels wide. When
resizing the panel to a smaller width, the side pane size will be
recalculated. It should never consume more than half the panel size.
Alarm Records
The alarm record area shows all alarm records that match the current alarm panel
settings, query, and filters.
Operators can execute actions on the records in the alarm areas. This can be done
via the tool bar, action bars, or right-click context menus.
When selecting alarms for Application Objects, the context menu includes object
shelving options.
The bottom status bar includes some additional information that can also be useful.
For detailed information about the AVEVA Alarm Client, see the AVEVA user
documentation.
A Tool bar: Provides quick access to common actions such as Pause, Show Alarm Display, Save, and
Ack Selected.
B Status Indicator bar: Shows key information related to what is shown in the alarm record area.
C Action bar: Operator actions are shown in this area. The type of actions is determined from the Action
Selection bar.
D Action Selection bar: Operator uses these buttons to show different actions in the Action bar.
E Filter & Query Treeview: Show all configured Queries and Filters. Operator can change the query or
enable and disable filters from these views.
F Alarm Records: Shows all messages returned from the Query and Filter query.
Use Current Time Option Select this checkbox to use time ranges that end with
the current time. Clear this checkbox to use custom
start or end times.
Time Duration Selection Select the desired Time Range to view. The list of
durations is based on the Use Current Time option.
Enable Custom Start This option is available when not using current time.
Time When selected, the time duration is starting from the
start time value. For example, 1 week, starting
January 1st.
Start Time Value This is the beginning time value. The alarm records
will show messages starting at, or after this time
value.
Enable Custom End This option is available when not using current time.
Time When selected, the time duration is ending at the end
time value. For example, 1 week, prior to January 1st.
End Time Value This is the ending time value. The alarm record will
show messages end at, or prior to this time value.
Apply Changes When using custom Start and End time, click Apply to
update the alarm records.
Alarm Priority Range Use the Priority To and From fields to set which alarm
priorities to view.
The authentication mode determines which fields are required. Changing the
authentication mode will enable the required fields. The connection is not attempted
until the Login button is clicked.
Framer includes settings for configuring the connection authentication mode. Using
Windows Integrated authentication will automatically connect the panel to the
database, if the database name and server are correctly configured in Framer. See
Framer and Alarm Management User’s Guide (B0750AR).
Using SQL Server, or Windows Account authentication modes require a password.
The panel will not connect to the database automatically. The Server Action button
will be highlighted. Open the Server Actions, set the password, and click Login.
Tool Bar
The Tool Bar provides one click access to common actions. Each tool button includes
a tooltip that displays what it does. When no actions are selected, the toolbar displays
a basic tool bar. Select Tools in the Action selection bar to show all toolbar buttons.
A Sort Dialog: Displays the alarm control’s Sort dialog. From this dialog, the
sort columns and orders can be modified.
B Reset Sort: When clicked, the alarm control’s sort options will be reset to the
default configured state.
C Records Per Page: This is the number of historical records that are being
displayed in the alarm area. Set the number of record to view per page and
click the Apply button. To page to the previous or next page of records, move
the right-side scrollbar to the top or bottom and press the scroll bar's arrow
indicator.
The alarm control status bar also shows the number of records being shown.
For example, if the Records per Page are set to 500, the status bar would
show:
• For Page 1:Displaying 1 to 500 of 20000
• For Page 2:Displaying 501 to 1000 of 20000
D Apply Changes: Use this button to apply changes to the Records per Page
value.
E Show Query and Filter dialog box.
F Save current query and filters.
G Show Alarm Messages Only: Places the alarm control into Historical Alarm
Message Mode. When active, historical alarm messages are shown in the
alarm area.
H Show Event Messages Only: Places the alarm control into Historical Event
Message Mode. When active, historical system event messages are shown
in the alarm area.
I Show Event and Alarm Messages: Places the alarm control into Historical
Alarm and Event Message Mode. When active, historical process alarm and
system event messages are shown in the alarm area.
Alarm DB Records
The alarm record area shows all historical alarm and event records that are within the
select time duration range. Alarm Records may also be filtered via the Query & Filter
Treeview.
These user actions are available from the controls right-click context menu:
The bottom status bar includes some additional information that can also be useful.
For detailed information about the AVEVA Alarm Client Control, see the AVEVA user
documentation.
A Tool bar: Provides quick access to common actions such as Pause, Show
Alarm Display, Save, and Ack Selected.
B Status Indicator bar: Shows key information related to what is shown in the
alarm record area.
C Action bar: Operator actions are shown in this area. The type of actions is
determined from the Action Selection bar.
D Action Selection bar: Operator uses these buttons to show different actions
in the Action bar.
E Alarm Records: Shows all messages returned from the Query and Filter
query.
F Filter & Query Treeview: Show all configured Queries and Filters. Operator
can change the query or enable and disable filters from these views.
For information on customizing the Alarm History Panel, see Window Construction
User's Guide (B0750AS).
starting one month ago and ending with the current time and date. Time values and
the alarm records are automatically updated when the time duration value is changed.
Use Current Time Select this checkbox to use time ranges that end with the
Option current time. Clear this checkbox to use custom start or end
times.
Time Duration Select the desired Time Range to view. The dropdown list of
Selection durations is based on the Use Current Time option.
Use Start Time This option is available when not using current time. When
Option selected, the time duration is starting from the start time
value. For example, 1 week, starting January 1st.
Use End Time This option is available when not using current time. When
selected, the time duration is ending at the end time value.
For example, 1 week, prior to January 1st.
Start Time Value This is the beginning time value. The alarm records will show
messages starting at, or after this time value.
Use End Time This is the ending time value. The alarm record will show
messages end at, or prior to this time value.
Apply Changes When using custom Start and End time, click Apply to
update the alarm records.
Alarm Priority Use the Priority To and From fields to set which alarm
Range priorities to view.
The authentication mode determines which fields are required. Changing the
authentication mode enables the required fields. The connection is not attempted until
the Login button is clicked.
Framer includes settings for configuring the connection authentication mode. Using
Windows Integrated authentication automatically connects the panel to the database,
if the database name and server are correctly configured in Framer. See Framer and
Alarm Management User’s Guide (B0750AR).
Using Windows Account authentication mode requires a password. The panel does
not connect to the database automatically. The Server Action button will be
highlighted. Open the Server Actions, set the password, and click Login.
The Alarm History Panel does not support SQL Server authentication mode.
Filtered The Filter indicator appears when there are active filters applied
to the alarms. The Filter indicator is highlighted to the user
because active alarms may be filtered out of the view.
Alarm Client The alarm control can operate in different modes. This indicator
Mode shows what mode is active.
• Historical Alarms - This indicator is shown when the alarm
control is showing only historical alarm messages.
• Historical Events - This indicator is shown when the alarm
control is showing only historical event messages.
• Historical Alarms & Events - This indicator is shown when
the alarm control is showing historical alarms and event
messages.
Connection This indicator shows the database connection status
Status • Connected - The alarm control is connected to the
database.
• In Progress - The connection to the database or retrieval
of alarm records is in progress. This status is highlighted to
inform the user that the control is busy.
• Not Connected - The alarm control is not connected to an
alarm database. This status is highlighted to the user that
the control is not connected.
Database Name This field shows the name of the database that the control is
connecting to — for example, History Blocks.
Tool Bar
The Tool Bar provides one click access to common actions. Each tool button includes
a tooltip that displays what it does. When no actions are selected, the toolbar displays
a basic tool bar. Select Tools in the Action Selection Bar to show all toolbar buttons.
A Sort Dialog: Displays the alarm control’s Sort dialog. From this dialog, the
sort columns and orders can be modified.
B Reset Sort: When clicked, the alarm control’s sort options will be reset to
the default configured state.
C Records Per Page: This is the number of historical records that are being
displayed in the alarm area. Set the number of record to view per page
and click the Apply button. To page to the previous or next page of
records, move the right-side scrollbar to the top or bottom and press the
scroll bar's arrow indicator.
The alarm control status bar also shows the number of records being
shown. For example, if the Records per Page are set to 500, the status bar
would show:
• For Page 1: Displaying 1 to 500 of 20000
• For Page 2: Displaying 501 to 1000 of 20000
D Apply Changes: Use this button to apply changes to the Records per Page
value.
E Show Query and Filter dialog.
F Save Current Query and Filters.
G Show Alarm Messages Only: Places the alarm control into Historical Alarm
Message Mode. When active, historical alarm messages are shown in the
alarm area.
H Show Event Messages Only: Places the alarm control into Historical Event
Message Mode. When active, historical system event messages are
shown in the alarm area.
I Show Event and Alarm Messages: Places the alarm control into Historical
Alarm and Event Message Mode. When active, historical process alarm
and system event messages are shown in the alarm area.
Users can execute several actions from the controls right-click context menu.
Sort Opens the Sort dialog box. See Runtime Alarm Panels, page 95 and
Toolbar, page 140.
Queries Opens the Query and Filters dialog box. See Runtime Alarm Panels,
and page 95 and Toolbar, page 140.
Filters...
Requery Sends another query request to the historical database and refreshes
the alarm records in the panel.
Reset Restores the Alarm Control to the configured default settings.
The bottom status bar includes some additional information that can also be useful.
For information about the AVEVA Alarm Client Control, see the AVEVA user
documentation.
Queries
The alarm panel can have only one alarm query active. The query retrieves all
messages from one or more Alarm Providers. The CHMI alarm Panel supports two
ways to create queries in the CHMI Alarm Panels.
• The Tools action bar which uses Alarm Provider format.
• The alarm control's Query and Filter Favorites dialog that uses SQL Alarm
Query format.
Both formats have the same basic requirements. Each provider query must include
Node, Provider, and Group. These fields do not support the usage of wildcards.
Example formats are:
Alarm Queries support more than just Tagname in the query. They can include any
additional column value:
Filters
One or more filters can be applied to the alarm panel to refine the messages that are
retrieved by the main alarm query. Filters are only applied to the message that are
returned by the main alarm query. Filters do not require a Node, Provider, or Group.
The Alarm Provider Format does not support or show filters. The CHMI alarm panel
supports two workflows for creating Filters:
• The FILTERS action bar which uses SQL Alarm Query format
• The alarm control's Query and Filter Favorites dialog that uses SQL Alarm
Query format
Filters have the same format as Alarm Queries, but do not require Node, Provider, and
Group settings: <ColumnName> <Condition> <Value>
Wildcards
Alarm Provider Format
When modifying the Alarm Provider String in the Tools Action Bar, only the "*" wildcard
is supported in the beginning or end of the Tagname value. It does not support more
than one wildcard, or the use of wildcards in the middle of the value.
Supported Alarm Provider Strings with Tagname:
• \\AW0001:0\IASeries!$System!CMP.BLK.ALMNAME
• \\AW0001:0\IASeries!$System!C*
• \\AW0001:0\IASeries!$System!*NAME
Command Description
Station View A scrollable hierarchical view of stations and
compounds on the left panel and a list of blocks for
the selected compound on the right panel
For more information, see Viewing the Control
Database, page 151.
Block View A scrollable and sortable list of blocks within all
connected stations.
For more information, see Viewing the Block List,
page 151.
The data in Station View and Block View are not updated until you perform a
Refresh operation on the stations.
NOTE: Block Select only provides data that has been downloaded to the Control
Station. It does not include the Strategy hierarchy because strategies are not part
of the Control database.
Station View
The database is organized by stations, compounds, and blocks. The database can be
viewed by placing Block Select in Station View. The stations and compounds
appear on the left panel of the screen, while the blocks for the selected compound
appear on the right panel.
Expanded Station
The expanded station displays its compounds on the left panel. Only connected
stations can be expanded.
Each compound displays:
• Status (ON or OFF), indicated by the icon
• Name
Compound is ON.
Compound is OFF.
When a compound is selected, it displays the blocks in the right panel. For each block
you can view its:
• Block status, indicated on the block icon
• Block name
• Highest alarm priority number (if an alarm exists)
• Block type
Block View
Block View displays a list of blocks within all connected stations. This list does not
include ECB blocks. For viewing the ECB blocks, select the compound containing
ECB blocks from the Station View. These icons indicate a block’s status:
Automatic
Manual
No Manual/Auto parameter
Undefined
Error
Column Description
Block The name of the block. Block state icons.
Status The block’s status.
Alarm The highest alarm priority for the block, if in alarm.
Type The block’s type.
Compound The name of the compound containing the block.
ON Y indicates the compound is ON. N indicates the compound is
OFF.
Station The name of the station containing the block.
Report Views
You can configure custom report views to display certain information on selected
compounds or blocks in the connected stations that you select. Using search filters,
you can also limit the report to compounds or blocks containing specific characters.
Predefined templates are available to provide information for these control database
conditions:
• Compounds off-scan
• Compounds in-alarm
• Compounds with alarms inhibited
• Blocks off-scan
• Blocks in-alarm
• Blocks with alarms inhibited
• Blocks not in control
• Blocks in manual
• Blocks with bad I/O
This figure shows a sample view of the blocks-in-alarm report for a selected station.
This report lists all the blocks in alarm along with the associated compound,
description, and alarm priority.
This figure shows a sample view of the blocks-in-manual report for a selected station.
This report lists all the blocks in manual along with the associated compound and
description.
Menu Bar
Options Menu
Command Description
Refresh Retrieves the current station and compound
information from the selected control stations, which
can be in any state.
Refresh All Retrieves the current station and compound
information from the control station for all connected
stations in the view. Therefore, Refresh All does not
retrieve data for stations that are in unconnected
state.
Exclude from Refresh The icons for excluded stations indicates that they
are Unconnected.
NOTE: Use this option when information is not
needed from certain stations or when you want
to speed up the Refresh All operation.
Multi-Select On Allows selection of more than one station,
compound, or block. Select this command, if you
want to clear the selected objects. Enables you to
turn multiple Control Core Services compounds ON
or OFF simultaneously, perform a Refresh operation
on more than one station at once, or cycle through
several detail displays by repeating a single action
(touch or click).
NOTE: When selected, you cannot mix stations
and Control Core Services compounds.
Find... Opens the Find dialog, which allows you to search
for stations, Control Core Services compounds, or
blocks in the view or on the network.
Show Detail Display Displays a block, compound, or station detail display
in Control HMI.
Save As... Opens the View Save As dialog for saving the
Block View or any custom report view as a text file (.
Command Description
txt) or comma separated value (.csv) file in the
\InFusion\View\Select\Reports directory.
Print Block List Opens the Block Select Print dialog for specifying
whether to print all items or only selected items in
the Block View or a custom report view.
Exit Exits from Block Select.
Compound Menu
Command Description
Compound ON Turns the selected Control Core Services
compounds ON.
Compound OFF Turns the selected Control Core Services
compounds OFF.
View Menu
A checkmark appears next to selected items in the View menu.
Command Description
Toolbar Displays or hides the buttons that call the most
frequently used commands.
Compound Toolbar Displays or hides the buttons for turning the
selected Control Core Services compounds on or
off.
TouchScreen Toolbar Displays or hides the Touchscreen toolbar.
Status Bar Displays or hides the Status Bar at the bottom of the
Block Select window.
TouchScreen Font Toggles the screen to Touchscreen mode with larger
fonts and toolbar buttons.
Command Description
Always On Top Keeps the Block Select window in front of all the
other windows, unless minimized.
Configure Report Opens the Configure Report dialog for creating
and activating custom reports views.
Help Menu
Command Description
Help Topics Displays the Block Select help screen.
About Block Select Displays the Block Select version and copyright
information.
Select To display
Station View A hierarchical view of the control database.
Block View A table view of all the blocks (excluding ECB blocks)
in all connected stations.
Status Bar
This information is displayed in the Block Select Status bar, depending on the
number of items selected:
• Current selection (if one item is selected)
• Number of items (if more than one item is selected)
• Date and time for the last Refresh command
When the mouse is placed over a toolbar icon, a description of the task is displayed in
the status bar.
Toolbar
Icon Function
With Control Core Services compounds or blocks selected, opens
the corresponding detail display.
NOTE: Same as the Show Detail Display command in the
Options menu.
Click to select multiple stations, Control Core Services compounds
or blocks. Click again to clear the selected objects.
NOTE: Same as the Multi-Select On command in the Options
menu.
Refreshes the selected stations.
NOTE: Same as the Refresh command in the Options menu.
Opens the Find dialog, which allows you to search for stations,
Control Core Services compounds, or blocks in the view or on the
network.
NOTE: Same as the Find command in the Options menu.
Displays Block Select version number and copyright information.
NOTE: Same as the About Block Select command in the Help
menu.
Compound Toolbar
Icon Function
With one or multiple Control Core Services compounds selected,
turns OFF the selected compounds.
NOTE: Same as the Compound OFF command in the
Compound menu.
With one or multiple Control Core Services compounds selected,
turns ON the selected compounds.
NOTE: Same as the Compound ON command in the
Compound menu.
Touchscreen Toolbar
Icon Function
Scrolls the selected pane up one page.
• Select the desired station and compound, use the Block field to enter the name
of the block to be located within the compound.
This table describes the elements of the Find in View tab in the Find dialog.
This table describes the elements of the Find on Network tab in the Find dialog.
Control Menu
You can operate on the Block Select window by clicking commands on the Control
menu.
The Control menu commands are described in this table.
Command Description
Restore Restores a maximized window to its previous size.
Move Lets you use arrow keys to move the window. Pressing
Enter maintains the new location.
Size Lets you reduce or enlarge the window by pressing
keyboard arrow keys. Pressing Enter maintains the new
size.
Minimize Reduces the window to a button on the taskbar at the bottom
of the screen.
Maximize Enlarges the window to full screen.
Close Exits Block Select.
To locate a Click
Station Find Station
Compound Find Compound
Compound:Block Find Block
Block Select searches for the next object name that exactly matches the
specified names.
5. To locate the next occurrence, repeat step 4.
Upon reaching the end of the list, the find operation loops to the beginning of the
list.
6. When you are finished, click Done.
1. Click in the toolbar, and select the desired stations, compounds, or blocks.
2. Click Options > Multi-Select On, and click the desired stations, compounds, or
blocks.
The status bar indicates the number of items selected.
Select To
Print all items Print the entire block list.
Print only selected items Print the selected items in the block list.
3. Select the printer from the Printer dialog, then click Print.
The block list is printed to the selected printer.
Performing a Refresh
The Refresh operation updates:
• Connection status
• Compound information
• ON/OFF status and alarm priority (if it exists) for each compound
• Status (for example, Manual/Automatic) and alarm priority of each block
Block Select automatically performs a Refresh of the station when you turn a
compound ON or OFF.
If you perform a refresh on a station that Block Select cannot access, it tries to
access the station for seven seconds, during which time the application is
unresponsive.
1. Select the required station.
2. Perform one of these actions:
click
NOTE: To select several alarms, use the Multi-Select function.
10. Click the Refresh button on the toolbar to populate the report with the defined
configuration.
Moving/Resizing a Window
You can use the window’s handles (corners) to resize the window. You can point the
mouse at the window’s title bar (caption) and drag the window to a different screen
position. Additionally, you can operate on the Block Select window by clicking
commands on the Control menu.
To move or resize the window using the Control menu:
1. Click the Block Select icon in the top left corner of the window.
The Control menu appears.
2. Select the appropriate command, from the list of commands in the table below.
Command Description
Restore Restores a maximized window to its previous
size.
Move Lets you use arrow keys to move the window.
Press Enter to drop the window.
Size Lets you reduce or enlarge the window by
pressing keyboard arrow keys. Press Enter to
drop the window.
Minimize Reduces the window to a button on the taskbar at
the bottom of the screen.
Maximize Enlarges the window to full screen.
Close Exits Block Select.
Accessing Windows
Accessing a Station Block Detail Display
A Station Block Detail Display provides information such as the Continuous
Control block processing load, total control load, basic processing cycles and
overruns, amount of dynamic free memory, and number of peer-to-peer connections.
1. Expand the station.
2. Click the Station compound.
3. Click the Station block from the right panel.
4. Perform one of these actions:
You can find more information about configuration settings and permission related to
the States View Panel functionality and operations in Framer and Alarm Management
User’s Guide (B0750AR).
You can find more information about the States View Panel user control and graphic
symbol in Window Construction User's Guide (B0750AS).
Basic Operations
Access States View from the Control HMI Quick Access toolbar or from the Control
HMI Views menu.
Navigation
The main grid area is empty when it is first opened. The Navigation pane contains a
hierarchical view of the deployed electrical system database.
The Value, Quality, and Timestamp columns (VQT) are permanent columns.
These columns cannot be hidden. They contain the live values received from the
SCD controller.
Device Information
When a row is selected, the data in the row appears in the Device Values pane. This
includes all the columns and live values.
The buttons appear in the States View ribbon and the Command Bar.
Grid Columns
Columns in the grid view can be:
• Rearranged
• Resized
• Pinned to the left or right
• Hidden
Use the column’s Filter dropdown to select the different types of filter conditions.
Clearing Filters
On the Sort and Filter pane, click Clear. This clears the data source filters.
The States View ribbon and Command Bars have indicators that show the status of
all the active data and grid filters. Click Clear to remove all grid column filters and
custom data filters.
Export
Operators can export the details of the grid view to a file. Only the current page values
are exported. If the grid contains multiple pages, use the Append option to export
different pages to the same file. The Export option is located on the ribbon, and
command bar. It is enabled when the grid contains data.
Click Export. The Verify Export Results dialog with default settings appears. The
default settings can be modified from the dialog.
The top area of the dialog shows this expected outcome when the export is
completed.
• The file will be created, replaced, or appended.
• The file format will be CSV or XML.
• The file will contain the hidden column values or not.
Exporting a File
1. Select a file type, CSV or XML.
2. Select or type in a filename.
3. Select these additional export options:
a. Include values of hidden columns.
b. Append the export data to an existing file.
4. Click Create or Replace to export the data. Or, click Cancel to cancel the export
operation.
Button Functionality
Save User Layout Save the layout to the user’s CHMI profile
location.
Load User Layout Re-load the user’s saved layout.
Delete User Layout Delete the user’s saved layout.
Restore Default Layout Load the default layout. This does not
delete the user’s saved layout.
6. Enter the tag name reference and click OK. This assigns the tag relationship to
the display.
For example:
Enter COMPOUND or enter COMPOUND.BLOCK.
7. Repeat step 5 to assign more tags to the user display.
8. Save and close the Framer.
Navigation
The navigation section contains two settings that control the way:
• The operator navigates the electrical data.
• The amount of data shown in the grid area.
The States View deployed data contains two structured pieces of data that is used to
organize the electrical devices. These pieces of data are used to build two hierarchical
views in the Navigation pane. Operators can select the different views by selecting
from the top drop-down list. This setting is available on the ribbon and command bars.
The Electrical Address view is constructed from the values found in the deployed
ORIGIN data column. For example:
ORIGIN: Substation_38EQI / LV_Bench1 / SCD6000 / ATV001
The IEC Address view is constructed from the values found in the deployed
GATEWAY and IEDNAME data. Using the same device information from the previous
example:
IEDNAME SCD_6K
GATEWAY SCD_6KSCD6K/GGIO3$ST$Ind1$stVal
The IEDNAME is separated from the gateway value and the $ information is removed.
This is used to create the hierarchical view. SCD_6K / SCD6K / GGIO3
The Page Size option allows the operator to change the number of items per page in
the grid. It is only available from the States View ribbon bar.
When working with a very large deployed database, performance can slow down. On
a pristine system with 100k records, the time to change pages, sort or filter, takes 3 to
5 seconds when the page size is at 1000. The operator can use this setting to reduce
the page size if performance has slowed.
This option is also useful if the default page size is configured to 250, and the operator
wants to export 1000 records with live values. The operator can change the setting to
increase the number of live values in the current page.
Source Data Status: States View Ribbon Bar and Command Bar Indicators
The States View panel connects to the deployed data file when it opens. This header
section shows the status of the connected data. The status indicators are available
from the States View ribbon and command bar headers.
A new deployed data file is available and not loaded yet. The
data in the States View is not current. Reload is enabled
when new data is available.
While the States View panel is open, it monitors the deployed data. Reload is
enabled when new data is deployed. Click Reload to clear the States View and load
the new deployed data.
Filter Status
Operators can create multiple data and grid column filters. However, it might not be
clear to the operator that a filter is applied if the column Is out of sight, or if the Data
Filter pane is collapsed. These indicators are always visible on the States View
ribbon or command bar to indicate if there are active grid or data filters. Click Clear to
clear all the data or column filters.
Export
Operators can export the content of the grid view to a file. Only the current page
values are exported. If the grid contains multiple pages, use the Append file option to
export different pages to the same file. The Export option is located on the ribbon,
and command bar. It is enabled when the grid contains data.
Exporting a File
XML FORMAT
The XML export file contains two main sections. The <ExportSet> section contains
information about what is exported. The <Taglist> section contains the actual data that
is exported.
Table 19 - Description
ExportTime Time when the export is done. This is used to differentiate among
multiple appended exports to the same file. The TagList data
also contains the time when it is exported
QueryString This informs about what is selected in the Navigation pane.
FilterString This informs about the Grid and Data filters applied.
PageNumber It is the main grid page number that is being exported
The TagList value contains the column and value of the grid cells being exported. The
export time value is the same value as seen in the Export Set when this value is
exported.
In this example, the first and second pages are exported to the same file.
The TagList - export time can be used to see the contents on each page.
CSV FORMAT
The CSV export file contains two main sections. The first section contains information
about what is exported. The next sections contain the actual values that are exported.
Export Information:
ExportTime, QueryString, FilterString, PageNo
3/7/2022 10:12:32 AM,(ORIGIN like 'Substation_38EQI /%') OR
(ORIGIN like 'Substation_38EQI/%'),((SCDNAME NOT LIKE
'<100>')),2
The replacement:
InList(“SCD100” ,”SCD200” ,”SCD300”)
A Auto-hide pane
B Search for item
C Clear selected items and the
grid
D Show chcked items in the grid
E Select items to show
F Expand/collapse nodes
To find a specific device, operators can enter text in the Find box. Use the Next
or Previous buttons to search the text in the tree. Use the Find list to select
previous search values. The list contains the last 10 search values.
1. Use the Column selector to select the column for sorting the data.
A Use the resize handle to increase the size of the visible list
Show Devices that are assigned to SCDs whose names end with 100 or 200.
6. Click Apply to apply the filter.
7. Click Clear Filter to clear the filter applied.
NOTE: Selecting the Include checkbox does not automatically apply the
filter. The same applies for clearing the Include checkbox.
Wildcards
The filter string value supports the use of % or * wildcards. Wildcards are only allowed
at the beginning or end of the value. Wildcard characters located in the middle of the
text are considered as literal string values.
Supported wildcard syntax:
A Group Values
B Auto-hide pane
C Filter the list
D Groups
E Runtime values
F Deployed data values
G Sort values
Status Bar
The status bar shows information about the grid and the results of the most recent
user action. It is divided into three sections.
• Quality status of the live values appears on the right side of the Status bar.
• The message showing results of the last action appears at the center.
C Filter bar The operator can filter the data and live values on a single
page.
J Selected Row Click on a cell to view its contents. The selected cell is
outlined and the background color of the selected row is
changed to light gray.
These are the two right-click options available on the
selected cell:
• Copy the cell value to the clipboard.
• Copy the row values to the clipboard.
D Page info Shows the number of pages and the current page number.
Operators can modify the page number to jump to a specific
page.
E Last Page Opens the last page of data. This button is disabled if the last
page is already open.
F Next Page Opens the page after the current page. This button is disabled if
the last page is the current one.
G Page The Page bar shows 10 Page buttons. The page numbers
shown are based on the current page. The highlighted current
page appears at the center of the page buttons.
H Previous Opens the page before the current page. This button is disabled
Page if the first page is the current page.
I First Page Opens the first page of data. This button is disabled if the first
page is already open.
Performance Consideration
Deployed Data Size Recommendations
The size of the deployed database impacts the performance of the States View panel
and the Control HMI. Actions such as filtering, sorting, and paging slow down for
large deployed databases. With 1000 records per page, the time taken to complete an
action is approximately:
While executing different user actions, the Control HMI and States View panel is
unresponsive until the action is completed. The Windows Operating System marks
the Control HMI as unresponsive if the action takes longer than 5 seconds.
NOTE: When working with large deployed databases, consider reducing the page
size to improve performance.
Appendix B: Troubleshooting
Recovering from Unexpected Control HMI Restart
If Control HMI exits unexpectedly, the Restart Infusion View dialog appears:
<configuration>
<startup>
<requiredRuntime version="v2.0.50727" safemode="true"/>
</startup>
<runtime>
<assemblyBinding xmlns="urn:schemas-microsoftcom: asm.v1">
<dependentAssembly>
<assemblyIdentity name="ArchestrA.QuickScript.
QuickScriptCompiler"
publicKeyToken="23106a86e706d0ae" culture=""/>
<bindingRedirect oldVersion="1.0.0.0" newVersion="1.1.0.0"/
>
</dependentAssembly>
<dependentAssembly>
<assemblyIdentity name="ArchestrA.Scripting.
ScriptFx"publicKeyToken=
"23106a86e706d0ae" culture=""/>
<bindingRedirect oldVersion="3.0.0.0" newVersion="3.1.0.0"/
>
</dependentAssembly>
</assemblyBinding>
</runtime>
</configuration>
3. Add this line to the <runtime> section:
<generatePublisherEvidence enabled="false"/>
<configuration>
<startup>
<requiredRuntime version="v2.0.50727" safemode="true"/>
</startup>
<runtime>
<generatePublisherEvidence enabled="false"/>
<assemblyBinding xmlns="urn:schemas-microsoft-com:asm.v1">
<dependentAssembly>
<assemblyIdentity name="ArchestrA.QuickScript.
QuickScriptCompiler"
publicKeyToken="23106a86e706d0ae" culture=""/>
<bindingRedirect oldVersion="1.0.0.0" newVersion="1.1.0.0"/
>
</dependentAssembly>
<assemblyIdentity name="ArchestrA.Scripting.
ScriptFx"publicKeyToken=
"23106a86e706d0ae" culture=""/>
<bindingRedirect oldVersion="3.0.0.0" newVersion="3.1.0.0"/
>
</dependentAssembly>
</assemblyBinding>
</runtime>
</configuration>
NOTE: Verify that this is the issue causing the problem before implementing the
workaround.
1. Verify that AlarmServer.exe is running in the Task Manager.
a. Open WindowViewer and verify that Control HMI is running.
b. Press Ctrl+Alt+Delete and select open Task Manger.
c. Select Show Processes for all users.
d. Go to Step 2 if the AlarmServer.exe is running.
2. Verify if Alarm Server could not create runtime files.
a. Open Windows Explorer.
b. Browse to c:\program Files(x86)\Invensys\InFusion\View
\AlarmServer.
c. Verify if aaStartup.ini does not exist.
Workaround
Implement workaround if aaStartup.ini does not exist.
1. Open Windows Explorer.
2. Browse to C:\program Files(x86)\Invensys\InFusion\View
\AlarmServer.
3. Right-click the AlarmServer folder and select Properties.
4. Select the Security Tab.
5. Click Edit located in the middle of the dialog.
6. Select “Users” in the “Group or user names:” list.
7. Select Full Control Permission.
8. Click OK to save.
9. Click OK to Save.
10. Restart the Alarm Server by double-clicking AlarmServer.exe in Windows
Explorer.
Glossary
A
ASP: AVEVA™ System Platform
C
Control Core Services (CCS): Core software environment, formerly known as “I/A
(Intelligent Automation) Series software”.
Control Editors (CE): Control software engineering and configuration tools built on
the AVEVA™ System Platform Integrated Development Environment in Foxboro DCS.
Formerly known as “FCS Configuration Tools”, “InFusion Engineering Environment”,
and “IEE”.
Control HMI (CHMI): The collection of windows and related configuration files that
make up the HMI as viewed within InTouch software in Foxboro DCS. Formerly
known as the “FCS InTouch Application”.
Control Processor (CP): Foxboro DCS stations acquire input data from sensors and
control field devices through fieldbus modules. The CP performs any mix of
integrated first-level automation functions, such as continuous, sequential, or discrete
logic functions. The CP contains compounds and blocks to perform its control
functions.
NOTE: For conciseness, documents refer to “CP”, which means “a Foxboro DCS
station containing objects”. Such stations include, but are not limited to, the
Control Processors, Device Integrators, and APs.
Control Software (CS): Packages built on the AVEVA™ System Platform Integrated
Development Environment that provide expanded functionality to the Foxboro DCS
Control Core Services. Formerly known as “Foxboro Control Software”.
D
DCS: Distributed Control System. Overall term that refers to a control system in which
the safety control components are distributed, with each component controlled by one
or more controllers.
deployment: The process of making the Safety View components available for use on
different PCs or run-time nodes in the System Platform network.
Device Integration Object (DIO): AVEVA™ System Platform object that manages
communication between an external server and the controller. It enables the operator
to communicate with configured controllers, process commands, and receive
tagname data.
Dynamic Display: A type of display where the block and compound values of a
custom property are available in System Platform.
E
Equipment Control Block (ECB): An equipment control block, created for each FBM
and external field device, provides a “holding place” for the software data associated
with that FBM or external field device
F
Fieldbus Module (FBM): FBMs provide the interface between process sensors or
actuators and the Fieldbus in a standard Foxboro DCS. FBM214/214b/214e/215/216/
216b/218/244/245 are examples of the many types of FBMs offered as part of
Foxboro DCS.
G
Galaxy: The database used by System Platform™ architecture. Also referred to as
“Galaxy Repository.”
H
HMI Engineering Tool: A tool that automates the configuration of System Platform™
symbols on process displays in Control Software.
O
OCMC: Operations Control Management Console or System Platform System
Management Console. The central runtime system administration/management user
interface in which all required runtime administration functions can be accomplished.
P
Platform Object: A representation of the physical hardware that the System
Platform™ software is running on. The Platform Objects hosts the Engine Objects
(see WinPlatform).
Process Automation System: An overall term used to refer to a system which may
include either, or both, Foxboro DCS Control Software and Foxboro DCS Control
Core Services.
S
System Manager (SM): Current user interface for equipment status and change
actions.
System Platform™ IDE: The integrated design and development tool from which all
System Platform objects are configured and deployed to PCs. Use the IDE to create,
configure, and maintain the objects and underlying infrastructure required to
communicate with Triconex controllers in a System Platform environment.
W
WindowMaker: An AVEVA application used for Control HMI Development.
C K
check for publisher's certificate revocation ............... 185 Keyboard
Column width adjustment........................................ 152 Shortcuts ........................................................... 183
Compound............................................................. 141
Compound toolbar ................................................. 141
Compounds
Turning on and off ............................................... 137
L
Configurators...........................................................16 Login ID...................................................................51
Configure Report.................................................... 145
Configure Report dialog box.................................... 145
Configuring M
Report views ...................................................... 152
role permissions ...................................................27 modify ................................................................... 186
security permissions .............................................27 WindowViewer configuration file .......................... 186
Connect server ........................................................51 Moving a window ................................................... 154
Control database.................................................... 151 Multi-headed workstations ........................................14
Control Editors .........................................................12 Multiple overlays .................................................... 156
Control HMI .............................................................12
Standalone...........................................................12
Control HMI main user interface ................................18 O
Control menu ......................................................... 147 Operations Control Management Console..................12
D P
Data quality .............................................................82 Password ................................................................51
Default user interface ...............................................18 Printing a block list ................................................. 151
Detail
Display.................................................................77
Dialog box R
Configure Report ................................................ 145
Refresh ................................................................. 151
Refresh All feature ................................................. 152
E Report views.......................................................... 152
Resizing a window ................................................. 154
Exit Role
Block Select ....................................................... 148 configuring ...........................................................27
Expanded station detail .......................................... 131 permissions..........................................................27
Expanding a station................................................ 148 where to...............................................................27
F S
Find in Network ...................................................... 144 Searching
Find in Network tab ................................................ 144 For blocks ...................................................148–149
Find in View ........................................................... 142 For compounds ...........................................148–149
For blocks.......................................................148–149 For stations .................................................148–149
B0750AQ, Rev Z 191
Control HMI User’s Guide
Security
configuring ...........................................................27
permissions..........................................................27
where to configure ................................................27
Selecting Stations, Compounds, or Blocks ............... 150
Shortcuts............................................................... 183
Standalone ..............................................................12
Station .................................................................. 140
Station connection status........................................ 131
Station tabs ........................................................... 140
Station View .......................................................... 131
Status bar.............................................................. 140
System Manager......................................................12
T
Tabs
Block View ......................................................... 140
Find in Network................................................... 144
Find in View........................................................ 142
Station ............................................................... 140
Tag browser.............................................................51
Tag picker................................................................51
Tag picker filtering functions ......................................54
Toolbar .................................................................. 140
Toolbars
Compound ......................................................... 141
Touchscreen....................................................... 141
Touchscreen .......................................................... 141
Touchscreen toolbar ............................................... 141
Trend properties.......................................................50
troubleshooting ...................................................... 184
Turning Compounds OFF ....................................... 151
Turning Compounds ON ......................................... 151
Turning compounds on and off ................................ 137
Turning Multiple Compounds OFF ........................... 151
Turning Multiple Compounds ON............................. 151
Turning on and off .................................................. 137
U
Updating information, see Refresh........................... 151
Use integrated security .............................................51
V
Viewing
Block list ............................................................ 151
Control database ................................................ 151
Multiple overlays................................................. 156
Views .................................................................... 152
W
Window moving and resizing................................... 154
WindowMaker..........................................................16
WindowViewer configuration file.............................. 186
modify................................................................ 186
Workstations............................................................14
FoxView and Control HMI ......................................28