DM Specification
DM Specification
Dubai Municipality
Drainage and Irrigation Department
a) General Requirements
1. The coating system and the surface preparation shall be to the approved
standard and shall conform to the ‘schedule of surface preparation and protection
systems’ given below for concrete work.
DM/DNID Section 7 Corrosion Protection and Surface Coating Rev 00 June Page 40 of 91
2016
General Specifications for Civil Works
Dubai Municipality
Drainage and Irrigation Department
2. Give special attention to ensure that edges, corners, crevices, welds, bolts, and
other areas, as determined by the Engineer, receive a film thickness at least
equivalent to that of adjacent coated surfaces.
– When it is expected that the relative humidity will exceed 85% or that the air
temperature will drop below 5 C within 18 hours after the application of the coating
or paint.
ii. If the above conditions are prevalent, coating shall be delayed until surfaces are
dry.
iii. The day’s coating shall be completed in advance of the probable time of day
when condensation will occur in order to permit the film a sufficient drying time prior
to the formation of moisture.
2016
General Specifications for Civil Works
Dubai Municipality
Drainage and Irrigation Department
iii. Drop cloths shall be used to protect floors, fixtures, and equipment.
iv. Care shall be exercised to prevent paint from being spattered onto surfaces from
which such paint cannot be removed.
vi. Apply second coat at right angles to first coat, ensuring pinholes are covered.
ii. Sufficient time shall be allowed to elapse between successive coats to permit
satisfactory recoating, but once commenced, the entire coating operation shall be
completed without delay.
12. Clean up
13. Protective coating properties tests are to be conducted on the final coated
surface and shall comply with the requirements specified in Table 7 –22.
DM/DNID Section 7 Corrosion Protection and Surface Coating Rev 00 June Page 42 of 91
2016
General Specifications for Civil Works
Dubai Municipality
Drainage and Irrigation Department
System- A - 1 7 mm thick in-situ GRP lamination with grit bonding on top of final
finish coat as specified in CL.7.1.14.
System - ‘B’ 1mm thick heavy duty glass flake vinylester resin based coating
250 micron each. Total D.F.T 4 x 250 microns + Approved Primer recommended by
the paint manufacturer.
System - ‘C’ 1mm thick Polysulphide modified Epoxy resin coating system
designed for superior adhesion, corrosion Protection, Chemical resistance &
waterproof coating 250 micron for each coat. Total D.F.T (4 x 250 micron) = 1 mm +
approved primer recommended by the paint manufacturer.
System - ‘D’ 0.5 mm thick solvent free 100% solid content polyamine based
Epoxy + Polyurethane resin coating.
System - ‘F’ Fibre reinforced acid resistant, mineral based alkaline silicate
mortar minimum 6 mm thick with finish top coat for hard floor coating.
DM/DNID Section 7 Corrosion Protection and Surface Coating Rev 00 June Page 43 of 91
2016
General Specifications for Civil Works
Dubai Municipality
Drainage and Irrigation Department
System - ‘I’ 7mm thick in-situ GRP lamination over grano benching for sewer
MH’s as specified in CL 7.1.6.
System - ‘J’ 7mm thick Prefabricated GRP liner as specified in CL 7.1.5 for
sewer manholes.
System - ‘K’ Two component Epoxy mortar 10mm thick over grano benching of
storm water MH’s as specified in CL 7.1.7
System - ‘L’ Solvent free 100% solid content Polyamine based pure Epoxy 300
micron thick + primer, for storm water MH’s and Inspection chambers (sewer) etc.
System - ‘N’ 5 mm thick GRP pre fabricated benching or in-situ lamination over
benching of inspection chambers (sewer) as specified in Clause 7.2.3.
2 Above Ground Level System ‘H’ Approved sealer coat and filler coat and
Alkali resistant acrylic based anticarbonation
coating (300 micron) thick
DM/DNID Section 7 Corrosion Protection and Surface Coating Rev 00 June Page 44 of 91
2016
General Specifications for Civil Works
Dubai Municipality
Drainage and Irrigation Department
Floor, Wall, Roof System ‘D’ Approved primer recommended by the paint
manufacturer + 300 micron pure epoxy paint
+ 200 micron polyurethane Paint
2 Chemical Storage Area Bund System ‘A’ GRP Liner (7mm thick)
Concrete Base floor and support System ‘D’ Approved primer recommended by the paint
wall manufacturer + 300 micron pure epoxy paint
+ 200 micron polyurethane Paint
4 Aeration Tanks
Floors, Walls & Ceiling, inlet/ System ‘B’ Approved primer recommended by the paint
Outlet channels manufacturer + 1 mm thick heavy duty glass
flake vinyl ester resin based coating.
Valve chamber ( Waste activated System ‘L’ 300 micron pure epoxy paint ( Polyamine
Sludge) based) ( Solvent free 100% solid content)
All chambers walls / floors System ‘C’ Approved primer recommended by the paint
manufacturer + Polysulphide modified epoxy
resin coating 1mm thick
6 Gas Holders
DM/DNID Section 7 Corrosion Protection and Surface Coating Rev 00 June Page 45 of 91
2016
General Specifications for Civil Works
Dubai Municipality
Drainage and Irrigation Department
3 Pull of adhesion strength ASTM D4541/ISO 4624 3.00 N/mm2 for epoxy coating
Notes: (1) Freedom from pinhole shall be established by the use of a spark tester.
7.2.6 Coating System for Ferrous, Non Ferrous Metals and Plastics
7.2.6.1 GENERAL
a) DESCRIPTION
DM/DNID Section 7 Corrosion Protection and Surface Coating Rev 00 June Page 46 of 91
2016
General Specifications for Civil Works
Dubai Municipality
Drainage and Irrigation Department
equipment.
5. Exposed galvanized metal except handrails, grating, piping and checkered plate.
b) SUBMITTALS.
Manufacturer’s Data
ii. Name, address and telephone number of manufacturer and local distributor.
iv. Detailed procedures for light repairs such as scratches and staining.
7. Abrasive:
DM/DNID Section 7 Corrosion Protection and Surface Coating Rev 00 June Page 47 of 91
2016
General Specifications for Civil Works
Dubai Municipality
Drainage and Irrigation Department
– pH value.
– Approved sample panels will be used for quality control in applying coating
systems.
v. F. Test Reports.
1. Delivery
– Manufacturer's name.
– Application instructions.
2. Storage
ii. Store materials on site in a suitable location, protected from exposure to extreme
weather.
2016
General Specifications for Civil Works
Dubai Municipality
Drainage and Irrigation Department
vii. Cloth and Cotton wastes that might constitute of fire hazard shall be placed in
closed metal containers or destroyed at the end of each workday.
d) QUALITY ASSURANCE
1. Applicator Qualifications
3. The protective coating systems specification, report on paint work progress and
the final report on corrosion protection should be provided by the applicator in the
formats (A), (B) and (C) given in this clause.
Form A – Form for a Protective Paint System Specification for New Work
(To be filled in for each constituent element of the structure by the applicator)
Project:
Name of Client:
DM/DNID Section 7 Corrosion Protection and Surface Coating Rev 00 June Page 49 of 91
2016
General Specifications for Civil Works
Dubai Municipality
Drainage and Irrigation Department
Shop Application
1st Coat
2nd Coat
3rd Coat
4th Coat
Total:
Site Application
Touch up:
Complete:
DM/DNID Section 7 Corrosion Protection and Surface Coating Rev 00 June Page 50 of 91
2016
General Specifications for Civil Works
Dubai Municipality
Drainage and Irrigation Department
1st Coat
2nd Coat
3rd Coat
4th Coat
Total:
DM/DNID Section 7 Corrosion Protection and Surface Coating Rev 00 June Page 51 of 91