CH_Two
CH_Two
CH-TWO: TRANSFORMERS
Transformer
E-mail: [email protected]
Its used to increase the power generating station ( step-up) and used to decrease the
voltage (step-down) for house hold purpose or distribution system.
By increasing the voltage the loss of the electricity in the transmission purpose is
minimized.
Power Transformer
Air filled Transformer Star-Star connection Transformer
Distribution Transformer
Oil filled Transformer Delta-Delta connection Transformer
Measurements Transformer
Natural transformer Star-Delta connection Transformer
Its has two inductive coils, these electrical separated but linked through a common
magnetic current circuit. These two coils have a high mutual induction.
Sandwiched type winding are used so insulation requirement is more. The windings
are sandwiched on each other which will give rise to a risk of short circuit fault between
the windings.
Cooling system for this types is natural not passible, it needs fans for cooling system
Its used for small or low voltage application like Electronic circuits.
Core loss or iron loss is less. Therefore efficiency is high for shell-type transformer
It use less copper conductor required for construction so cost of transformer is less
.Its maintenance job of winding are very hard, heat dissipation is not easy, more insulation
is required
10/9/2023 PE lecture Slide by Erste.T 47
Construction of the Transformer (Core-Types)
The high voltage and low voltage windings are wrapped around the core. In the core type
transformer, windings surround the core.
The high voltage and low voltage winding are divided into two parts and half parts of
both the windings are wound on one limb and the second-half part of both the
windings are wound on other limbs.
Cooling system for natural passible, because the coils is exposed to the surface
Core loss or iron loss is high. Therefore efficiency is less for core-type transformer
Its maintenance job of winding are very easy, heat dissipation is easy, less insulation is
required
10/9/2023 PE lecture Slide by Erste.T 49
Construction of the Transformer (Cont…)
When the alternating currents flows in the primary coils, a change in flux is generated
around the primary coils.
The changing in magnetic flux is transferred to the secondary coil through the iron core
The changing magnetic flux by the secondary coils, hence induces an e.m.f in the
secondary coil.
Now if load is connected to secondary winding, this e.m.f drives a currents through it.
The magnitude of the output voltage can be controlled by the ratio of the number of
primary coil to secondary coil.
10/9/2023 PE lecture Slide by Erste.T 51
Working principle of the transformer(cont…)
According to the diagram above, the primary winding is the one to which the AC supply
is connected, and the secondary winding is the one to which the load is connected.
Only alternating current can be used because mutual induction between the two windings
requires an alternating flux.
=− 2.1
=− 2.2
= 2.3
From the expression above, it is clear that the size of EMFs E1 and E2 is dependent on the
number of turns in the transformer primary and secondary windings, respectively.
If N2 > N1, then E2 > E1, and the transformer will be a step-up transformer; if N2 < N1, then
E2 < E1, and the transformer will be a step-down transformer.
10/9/2023 PE lecture Slide by Erste.T 53
Ideal Transformer
A hypothetical model of a transformer, having all the essential properties of a real
transformer except the power losses is known as an ideal transformer.
It is assumed that the flux produced in the primary winding is confined to the core and
links the secondary winding (i.e.) there is no leakage flux. But in an actual transformer,
there will be a small amount of leakage flux.
The core is assumed to have infinite permeability, meaning that the magnetizing current
needed to establish flux in the core is zero.
the core flux is unchanged by the presence of a load on the secondary, and hence the net
exciting mmf acting on the core (equal to − ) will not change and hence will
remain negligible. Thus ,
− =0 2.3
10/9/2023 PE lecture Slide by Erste.T 54
Ideal Transformer
The net mmf acting on the core therefore is zero, in accordance with the assumption that
the exciting current of an ideal transformer is zero.
= 2.4
Figure 2.3. Three circuits which are identical at terminals ab when the transformer is ideal.
and 2.5
+ = 0.05 + 0.97Ω connected in series with the secondary. The tums ratio =
14: 1. Determine:
a) Draw an equivalent circuit with the series impedance referred to the primary side.
b) For a primary voltage of 120Vrms and a short connected across the terminals A-B,
calculate the primary current and the current flowing in the short.
The terminal voltage V2 across the load is equal to the induced emf E2 in the secondary
winding less voltage drop in the secondary winding.
In this case, to draw the equivalent circuit of the transformer all the quantities are to be
referred to the primary as shown in the figure below:
Figure 2.5. Circuit Diagram of Transformer when all the Secondary Quantities are Referred to Primary Side
The following are the values of resistance and reactance given below. Secondary resistance
referred to the primary side is given as:
The equivalent circuit diagram of the transformer is shown below when all the quantities
are referred to the secondary side.
Figure 2.5. Circuit Diagram of Transformer when all the Secondary Quantities are Referred to secondary Side
No-load current I0 is hardly 3 to 5% of full load rated current, the parallel branch consisting of
resistance R0 and reactance X0 can be omitted without introducing any appreciable error in the
behavior of the transformer under the loaded condition
10/9/2023 PE lecture Slide by Erste.T 64
Regulation and Efficiency of the Transformer
Why transformer rating in KVA?
As we know, Cu loss of a transformer depends on current and Iron loss on voltage loss.
Hence total transformer loss depends on volt-ampere (VA) and not on phase angle
between voltage and currents, i.e it is independent of load power factor. This is why rating
transformer is KVA not in KW.
Regulation of transformer is defined as the deference between the full-load and no-load
secondary terminal voltage expressed as a percentage of the full load voltage.
When the transformer is loaded with a constant primary voltage, the secondary voltage
decrease because of its internal resistance and leakage reactance.
Let, = !"#$% &'( )$* &+" & %$ *$& = = ,=- because at no load the
impedance drop is negligible.
= !"#$% &'( "'./%&* )$* &+" $% 01** *$&
10/9/2023 PE lecture Slide by Erste.T 65
Regulation of a transformer or transformer regulation (Cont…..)
The change in secondary terminal voltage from no load to full load is = −
If the change is divided by i.e full load secondary terminal voltage , the it is called
regulation ‘up’
−
% "+1'& /$% $3% = × 100
−
% "+1*& /$% 56 = ∗ 100
The lesser this value , the better the transformer efficiency, because a good transformer
should be kept secondary terminal voltage as constant as possible under all condition
of the load.
10/9/2023 PE lecture Slide by Erste.T 66
Losses In Transformer
Since a transformer is a static device , there are no friction and wind age load. Hence, the
only losses occurring are:
Copper loss
It includes both hysteresis loss and eddy current loss. Because the core flux in
transformer remains practically constant for all loads the core loss is practically the same
at all loads.
: ∗; ∗<= ∗>
Ph = (kh )(f)(Bmax)1.6 and 89 = ?∗@
w/.C
Its clear that Cu loss is proportional to #1''"% $' - F So, Cu loss at half load is
one-fourth [ 1/2 =1/4] at the full load.
The value of copper load is found from the short circuit test.
Efficiency of a Transformer
The efficiency of the transformer at a particular load and power is defined as the out put
power divided by the input-the two being measured in the same unit(either watts or
kilowatts).
HIJK
Thus the equation of efficiency can be written as: G = HLM
∗ 100
The excitation branch impedances are given referred to the high voltage side the transformer.
c) Assume that this transformer is supplying rated load at 277 V and 0.85 PF lagging. What
is this transformer input voltage ? What its voltage regulation?
d) what are the copper losses and core losses in this transformer under the condition of part
(c)