KIMO Transmitter CP300

The CP 300 pressure transmitter offers a range of models with pressure measurement capabilities from 0/+10 Pa to -10,000/+10,000 Pa, featuring high resolution, configurable ranges, and optional air velocity and airflow functions. It includes dual color LED alarms, multiple output options, and supports MODBUS communication. The device is designed for easy installation and maintenance, with self-calibration and temperature compensation features to ensure measurement accuracy.

Uploaded by

kiarashloqmani
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
147 views4 pages

KIMO Transmitter CP300

The CP 300 pressure transmitter offers a range of models with pressure measurement capabilities from 0/+10 Pa to -10,000/+10,000 Pa, featuring high resolution, configurable ranges, and optional air velocity and airflow functions. It includes dual color LED alarms, multiple output options, and supports MODBUS communication. The device is designed for easy installation and maintenance, with self-calibration and temperature compensation features to ensure measurement accuracy.

Uploaded by

kiarashloqmani
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Technical Data Sheet

Pressure transmitter
CP 300
New
• Ranges from 0/+10 Pa to -10 000/+10 000 Pa (according to model)
• Transmitter resolution at 0.1 Pa on CP 301 (optional)
• Configurable intermediate and centre zero ranges
• Air velocity and airflow functions (optional)
• Interchangeable measuring sensor (SPI technology)
• Simultaneous display of 1 to 4 parameters
• External transmitter inputs (KIMO Class 200 and 300) and thermocouple K
• 2 outputs 4-20 mA (4 wires) or 0-10V, RS 232, 2 RCR relays 6 A/230 Vac
• 2 visual (dual color LED) and audible (buzzer - 80 dB) alarms
• Output diagnostics
• MODBUS network RS 485 system (optional)
• ABS or ALU IP 65 housing, with or without backlit graphic display
• Quick and easy mounting using “1/4 turn” system with wall-mounting plate

Housing made of Transmitter features


ALU or ABS WITH or WITHOUT display
Pressure
Measuring range ............................see “SPI features”
Units of measurement....................Pa, mmH2O, mbar, inWG, mmHG
Accuracy *.......................................±0,5% of reading ±1 Pa (CP 301/302/303)
±0,5% of reading ± 0.8 Pa (CP 301 with 0.1 Pa
option)
Part number
To order, just add the codes to complete the part number : .........................................................±0,5% of reading ±10 Pa (CP 304)
Zero drift .......................................none (see “self-calibration”)
Measuring range Resolution ..........................................1 Pa - 0,1 mmH2O - 0,01 mbar - 0,01 InWG - 0,01 mmHg
1 -100/+100 Pa Self-calibration .................................push-button or automatic (configurable)
For the intermediate and
2 -500/+500 Pa centre zero ranges, see Type of fluid......................................air and neutral gases
3 -1000/+1000 Pa “Configuration”. *All accuracies indicated in this technical data sheet were stated in laboratory conditions, and can be guaranted for
4 -10 000/+10 000 Pa measurements carried out in the same conditions, or carried out with calibration compensation.

Power supply / Output Functions (optional)


B 24 Vac/Vdc • 0-10 V or 4-20 mA Class 300 transmitters have 2 analogue outputs which correspond to the first 2
M 115 Vac • 0-10 V or 4-20 mA parameters displayed. You can activate 1 or 2 outputs, and for each output, you can
H 230 Vac • 0-10 V or 4-20 mA choose between pressure, temperature (optional probe), air velocity and airflow
(optional functions).
Display
O With display
Features
Measuring ranges Units and resolutions
N Without display Functions

Housing material Air 2 to 100 m/s


(according to SPI card) 0,1 m/s - 0,1 fpm
P ABS
velocity*
A ALU
0 to 100 000 m3/h 1 m3/h - 0,1 m3/s
Airflow* (depends on air velocity and duct dimensions) 0,1 l/s - 1 cfm
CP30 -
Example : CP302-BOA = pressure transmitter type CP 300, with measuring Class 300 transmitters can display up to 4 parameters simultaneously.
range of -500/+500 Pa, with power supply 24 Vac/Vdc, 0-10 V or 4-20 mA output, The last 2 parameters are only displayed, they have no output.
with display and alu housing. * differential probe (Pitot tube, Debimo blade...) sold separately

Housing dimensions Housing features


(including the wall-mounting plate)
ABS housing : 150 mm ABS : 70 mm Housing ..................................ALU or ABS
ALU housing : 155 mm ALU : 75 mm Fire-proof classification .......ABS : V 0 as per UL94
Dimensions ............................see drawing alongside
ABS housing : 117 mm
ALU housing : 122 mm
ABS housing : 140 mm
ALU housing : 145 mm

Protection ...............................IP65
Display ....................................graphic from 1 to 4-line, 70 mm x 38 mm
.....................................................backlit, protection screen made of PMMA
Fittings....................................barbed fittings Ø 6,2 mm
100 mm

Connection gland ..................ALU : nickel plated brass for cables Ø 9 mm max.


23 mm .................................................ABS : polyamide for cables Ø 7 mm max.
Weight.....................................ABS : 800 g - ALU : 1300 g (with display)

SENTRONIC AG Produkte, Support und Service


Rugghölzli 2
CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18
Fax +41 (0)56 222 10 12
[email protected]
www.sentronic.com
SPI system features Measurement and temperature compensation
Interchangeable Pressure Sensor
Temperature compensation can be made either manually (by entering a temperature
value) or automatically via a thermocouple K temperature probe (optional). This
The SPI board (Interchangeable Pressure Probe) includes a probe can measure and display temperature, and can compensate air velocity
piezoresistive sensitive element with its digital electronic system. This formula in real-time (for better accuracy).
system is individually adjusted and records all the calibration
parameters. Type of transmitter........................Thermocouple K (optional)
Via the automatic recognition by the transmitter, this digital board is Measuring range ..........................-200 to +1300 °C (probe dependent)
totally interchangeable. Maintenance, service and calibration are Units of measurement .................°C, °F
easily performed on site, with no need to stop the process. Resolution.....................................0,1°C - 0,1°F
Configurable intermediate and centre zero ranges
Ref. of the probe Pressure range Air velocity* range Technical Specifications
SPI 100 -100/+100Pa 2 to 10 m/s Power supply .............................24 Vac / Vdc ±10%
SPI 500 -500/+500 Pa 2 to 22 m/s .....................................................115 Vac or 230 Vac ±10%, 50-60 Hz
SPI 1000 -1000/+1000 Pa 2 to 30 m/s Output .........................................2 x 4-20 mA or 2 x 0-10 V (4 wires)
SPI 10000 -10 000/+10 000 Pa 2 to 100 m/s .....................................................maximum load : 500 Ohms (4-20 mA)
.....................................................minimum load : 1 K Ohms (0-10 V)
* Air velocity ranges are given as an indication based on a differential probe DEBIMO
(Cm = 1). They do not take into account temperature compensation.
Galvanic isolation ......................inputs and outputs (on 115 Vac/230 Vac models)
outputs (on 24 Vac/Vdc models)
The minimum configurable range is 10% of the full range. Consumption..............................5 VA
Relays .........................................2 RCR relays 6A / 230 Vac
Overpressure tolerated..........25 000 Pa (CP 301, CP 302, CP 303) Visual alarms..............................2 dual color LED
................................................70 000 Pa (CP 304) Audible alarm .............................buzzer
Response time .......................1/e (63%) 0,3 sec. Electro-magnetical compatibility ...EN 61 326
Type ........................................digital Electrical connection ..................screw terminal block for cables Ø 1.5 mm² max
Dimensions ............................L = 60 mm, l = 25 mm RS 485 communication .............digital : Modbus RTU system
Working temperature ............0 to +50 °C .....................................................communication speed configurable from
Storage temperature .............-10 to +70 °C 2400 to 115200 Bauds
RS 232 communication .............digital : ASCII, proprietary protocol
Working temperature.................0 to +50°C
Air velocity and airflow functions Storage temperature..................-10 to +70°C
(optional) Environment...............................air and neutral gases
Pressure transmitters working with a differential probe (such as DEBIMO, Pitot
tube, orifice plate...) can be configured with a square root function. Via this Relays and Alarms
function, and from the differential pressure, the transmitter can calculate air
velocity and/or airflow in a duct. Class 300 transmitters has 4 stand-alone and configurable alarms :
2 visual alarms (dual color LED) and 2 relays (contacts).
Pitot tubes (with or You can set :
without temperature
Debimo blades compensation) - the parameter (pressure, air velocity, temperature…)
- 1 or 2 set points (rising and falling action) for each alarm
- the time-delay / 60 sec max.
- the alarm action (rising or falling)
- the relay operation mode : positive or negative security
- the audible alarm (buzzer) activation.

Self calibration
Thanks to the temperature compensation of the gain (from 0 to 50°C) and to the self
calibration system, Class 300 transmitters guarantee an excellent long-term
stability, along with a great measurement accuracy.
Air velocity calculation function : Self calibration principle : the microprocessor drives an electro-valve that
compensates for any long-term drift of the sensitive element.
Air velocity (m/s) = CM x CC x CT x D
pressure Pa) Compensation is made by regular automatic adjustment of the zero. True differential
pressure measurement is then made regardless of the environmental conditions of
CM : cœfficient of the differential probe the transmitter.
CC : coefficient to adapt the measuring system to the specifications of
your air movement conditions . Electro-valve lifetime .....................100-million cycles
CT : temperature compensation coefficient, with the formula below :
Benefit..............................................no zero drift
CT =
574,2 x temp. (°C) + 156842,77 Self calibration frequency .............can be disabled or set between 1 and 60 min
101325

Airflow calculation function : Integration of pressure measurement


The pressure measurement element is very sensitive and reacts to pressure
Airflow (m3/h) = air velocity (m/s) x surface (m2) x 3600 changes. When making measurements in unstable air movement conditions, the
Surface : setting of duct type (rectangular or circular) and duct pressure measurement may fluctuate. The integration coefficient (from 0 to 9)
dimensions (in mm or in inches). makes an average of the measurements ; this helps to avoid any excessive
variations and guarantees a stable measurement.

SENTRONIC AG Produkte, Support und Service


Rugghölzli 2
CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18
Fax +41 (0)56 222 10 12
[email protected]
www.sentronic.com
Connection
Manual k SPI sensitive d c b Relay
self calibration element j RS 485 terminal blocks
Output selection Analogue connection
4-20 mA outputs
or 0-10 V h

Power supply
a terminal block

i 24 Vdc / ac
230 Vac
115 Vac
The ticked box shows
the power supply type
of the transmitter.
e
RS 232 connector Pressure f
connections Thermocouple K
input

d c b g Connection fittings
{

{
Analogue output 1 Analogue output 2
RS485
(Modbus) Relay 1 Relay 2 a or a or a

ge ag
e B A For 24 Vdc For 24 Vac For 230 Vac 115 Vac
o lta nd olt und - + power supply models power supply models power supply models
. . v ou t . v
... r n ... ro nt
. . ... .....g urre . . ... ...g rre
en n
. ... ..c . . .. u pe
... ... ... ..c op yo
V ...... ...... V ...... ...... all
y
ed all _
10 .. ... 10 .. .. ed
m + ~ ~
0- D . A 0- D . A .
m
or mon clos n or mon clos
N m N m .. .n
ly .. . m ly
G 20 G 20 ... ..co mal
m ... ..co mal phase
4- 4- NO M. nor NO M. nor security earth
.. ..
CO .... CO .... neutral
NC NC

Electrical connections - as per NFC15-100 Norm


! This connection must be made by a qualified technician. Whilst making the connection, the transmitter must not be energized.

Power supply connection : Output signal selection Connection of SUB-D15


! Before making the connection, you must first check the voltage (0-10 V) or current (4-20 mA) RS 232 and RS 485 (Modbus)
power supply which is indicated on the transmitter board ( see e on drawing connection)
(see i on the connection drawing). The on-off switch located on the left top of the
8 7 6 5 4 3 2 1
transmitter (see h on connection drawing) allows
• For 24 Vdc power supply models :
selection of the required outputs. 15 14 13 12 11 10 9
-
+

Power supply Down Up


terminal block 0-10 V 4-20 mA Pin # Description

- 1 NC *
24 Vdc 2 NC *
power supply
3 NC *
+

4 B- (RS 485)
• For 24 Vac power supply models :
Output connection : 5 A+ (RS 485)
Vac Vac
• 4-20mA current output : 6 NC *
Power supply ~ ~ N L
0-10 V GND 4-20 mA
terminal block
7 NC *
OR -
Output 8 NC *
+

terminal block
Pe
9 RX (RS 232)
N ~ Pe 10 NC *
230 Vac 24 Vac
L
N N Regulator display - 11 TX (RS 232)
~ 230 Vac 24 Vac
or PLC/BMS
L Ph +
power supply
passive type 12 NC *
Class II power supply
13 NC *
• For 115 or 230 Vac power supply models : • 0-10 V voltage output : 14 NC *
ground Phase 0-10 V GND 4-20 mA
Neutral 15 GND (RS 232)
Output -
+

terminal block
Power supply ! CAUTION ! :
terminal block NC * = DO NOT CONNECT

Regulator display +
or PLC/BMS
115 / 230 Vac
passive type -
power supply

SENTRONIC AG Produkte, Support und Service


Rugghölzli 2
CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18
Fax +41 (0)56 222 10 12
[email protected]
www.sentronic.com
Numerical communication Calibration
RS 232 communication Adjusting and calibration on site
• Via the RS 232 connection, the CP 300 can display 1 or 2 parameters that :
are measured by other Class 200 and 300 transmitters. The professional configuration interface,
with a dynamic pressure calibration
Benefit : the CP 300 can display (in addition to the
bench, enables you to adjust and
pressure), other parameters such as temperature and calibrate your transmitters directly on site
humidity from a TH 200 (for example). or in laboratories.
Output diagnostics :
• Via the RS 232 connection, you can also configure With this function, you can check with a
your transmitter with the LCC-300 software. multimeter (or on a regulator/display, or on
a PLC/BMS) if the transmitter outputs work
• The RS 232 connection cable is available in 2m, 5m properly. The transmitter generates a
or 10m (maximum) lengths. voltage of 0 V, 5 V and 10 V or a current of
4 mA, 12 mA and 20 mA .
Modbus network (RS 485 system) Certificate :
• Class 300 transmitters are supplied with adjusting c e r t i f i c a t e s .

Ref. FT ang - CP 300 - 16/08/11 - RCS (24) Périgueux 349 282 095 Non-contractual document - We reserve the right to modify the characteristics of our products without prior notice.
• Class 300 transmitters can be linked Calibration certificates are offered as an option.
RS 232
in one network, on a RS 485 home • The SPI sensitive elements (interchangeable pressure probes)
bus. They can also are supplied with adjusting certificates.
be integrated into
an existing
network. RS 485 Mounting
To install the transmitter on a wall : fix the stainless steel plate to the
RS 232 wall (this plate is supplied with the transmitter). Drilling : 8 mm (with
the screws and wall-plugs supplied with
• When a Class 200 or 300 transmitter the transmitter). Insert the transmitter on
is connected to a CP 300 (with RS 232 the plate (see A on the drawing shown
connection), all the measurements can be given to the PLC/BMS via the beside) by aligning it at 30°. Rotate its
RS 485, with only one address for the 2 transmitters. housing in clockwise direction until you
hear a “click” which confirms that the
transmitter is correctly installed. Then,
• The RS 485 digital communication is a 2-wire network, on which the open the housing, lock the clamping
transmitters are connected in parallel. They are connected to a PLC/BMS via the system of the housing on the plate, with the screw as shown. (to
RTU Modbus communication system. Since the CP 300 can be configured with remove the transmitter from the plate, remember to remove the
the keypad, the MODBUS enables remote configuration, to measure 1 or 2 screw first). 120 mm
parameters or to see the status of the alarms...
Stainless
steel A

65 mm
98 mm
plate
Configuration A

You can configure all the parameters of the transmitter : units, measuring
65 mm Ø 5,4 mm
ranges, alarms, outputs, channels, calculation formula.... via the different
methods shown below. ! CAUTION !
Via keypad : only on models with display When the transmitter is installed and powered on, it will
automatically perform an autozero procedure. This guarantees
A code-locking system for keypad guarantees the security of the that the transmitter works properly, whatever its position.
installation. See configuration manual.
Via remote control (optional) only on models with display.
This is convenient to configure the transmitters located in hard to reach Maintenance
positions. Same method as with a keypad. Avoid aggressive solvents.
Via software (optional) : on all models. Protect the transmitter and probes from any cleaning product
Simple and user-friendly configuration. See LCC-300 user manual. containing formol, which may be used for cleaning rooms or
Via MODBUS (optional) : on all models. ducts.
Configuration of all parameters from your PC, via the supervision or data Options
acquisition software.
SQR/2 (square root extraction) function for
Configurable analogue outputs the calculation of air velocity and airflow
Configure the range according to your needs : outputs are automatically adjusted Digital output for Modbus network (RS 485 system)
to the new measuring ranges. LCC-300 configuration software with RS 232 cable
Range +100
-100 0 (Pa, mmH2O...)
Infrared remote control for configuration (only for models
Range with centre zero (-50/0/+50 Pa), with display)
with offset zero (-30/0/+70Pa) or Calibration certificate.
standard range (0 /+100 Pa) => you can 0V 10V
20 mA
Transmitter resolution at 0.1 Pa (CP 301)
4 mA
configure your own intermediate ranges
according to your needs, between 10% New range Optional accessories
+100
and 100% of the full scale. The minimum -100 0 50 (Pa, mmH2O...) Pitot tubes Sliding fittings
configurable range is 10% of the full Debimo measuring blades Connection gland
scale. Thermocouple K probes Clear tube
0V 10V Mounting brackets Through-connections
4 mA 20 mA
Pressure connections