S 216 Content
S 216 Content
2020
COURSE CONTENT
Columns
The capacity of an axially loaded slender member in compression is governed by the critical buckling load
(Pcr), however, for extremely stocky members compression failure may occur via yielding rather than
buckling. The formula for calculating Pcr, developed by Euler, for a column pinned at each end with no
intermediate brace points, and no load eccentricities is;
If the critical buckling load is divided by the area of a given member the critical buckling stress is obtained
as;
For less slender, or stocky, members E is replaced by Et (Tangent Modulus) to account for the non-linear
relationship between stress an strain that results because the relative small slenderness ratio (L/r) for these
types of members results in large buckling stress values that are greater than the proportional limit of the
material. Et is smaller than E and because of its variability the calculation of Pcr in the inelastic range is
difficult and requires a trial and error approach. For this reason the AISC design specifications contain
empirical formulas for inelastic columns.
The critical buckling stress can be plotted as a function of the slenderness ratio as shown in Figure 1.
FIGURE 1
End conditions other than pinned/pinned are accounted for by the use of K, the effective length factor.
Modifying the critical buckling stress (Fcr) using K results in the elastic buckling stress; Fe = π2E/(KL/r)2 =
Pe/Ag; where Pe = the buckling load and Ag = the gross area of the section.
Values of K for isolated columns that are not a part of a continuous frame are provided in Table C-C2.2 of
the 13th Edition on page 16.1-240. To determine the K factors for columns that form a part of a frame with
rigid joints, alignment charts are provided on page 16.1-241 and 16.1-242 for sidesway inhibited (i.e. braced)
and sidesway uninhibited (i.e. moment frame) conditions, respectively. It should be noted that when using
the referenced alignment charts G = 10.0 for a pinned foundation support and G = 1.0 for a fixed foundation
support.
Also, in a braced frame the beam-to-column connections are not normally detailed or constructed as moment
resisting because the bracing system is designed to resist all lateral loads independent of the surrounding
unbraced beam/column bents. In this scenario there is no continuity between the beams and columns and the
alignment charts cannot be used. For this type of braced frame K = 1.0.
It should also be noted that if the slenderness ratio, KL/r is less than 4.71(E/Fy)½ the column will buckle
inelastically and the K factors obtained from the alignment charts will be overly conservative. A procedure
for determining K for inelastic columns that allows for the use of the alignment charts can be found on page
16.1-247 of the 13th Edition Commentary. This method involves the use of a stiffness reduction factor (τa),
which is used to modify Fe = Pe2/ τaAg; where Pe2 = elastic critical buckling load. This value of Fe is then
used to determine Fcr for the purposes of calculating the nominal compression strength (Pn) in Section E3 of
the AISC Specifications.
The requirements for compression members in the 13th Edition, Chapter E, list the nominal compression
strength; Pn = FcrAg. For LRFD Pu ≤ ΦPn (where the resistance factor Φ = 0.90 for compression members)
and for ASD (Allowable Strength Design) Pa ≤ Pn/Ω (where the safety factor Ω = 1.67 for compression
members).
For compact and non-compact compression members (without slenderness elements) per Section E3 of the
specifications; Pn = FcrAg (based on the limit state of flexural buckling). Fcr is defined by Equations E3-2 and
E3-3 on page 16.1-33 as determined by whether Kl/r is less than or equal to 4.71(E/Fy)½ (i.e. inelastic
buckling) or greater than 4.71(E/Fy)½. The variation in Fcr is represented in Figure 2.
FIGURE 2
The compression strength of a member based on the above buckling mode cannot be developed if the
elements of the member’s cross section are so thin that local buckling can occur. If the limiting width-
thickness ratio (λ) of any unstiffened elements is greater than 0.56(E/Fy)½ the shape is slender and the
potential for local buckling must be accounted for. For the projecting unstiffened flange of I and H shapes; λ
© D. Matthew Stuart Page 3 of 15
www.PDHcenter.com PDH Course S216 www.PDHonline.org
= bf/2tf. If the limiting width-thickness ratio (λ) of any stiffened elements is greater than 1.49(E/Fy)½ the
shape is slender and the potential for local buckling must also be accounted for. For the stiffened web of I
and H shapes; λ = h/tw, where h is the distance between the roots of the flanges. Pn for members with slender
elements is provided in Section E7 of the specifications and is based on the limit state of flexural, torsional
and flexural-torsional buckling.
The 13th Edition contains useful tables for the analysis and design of columns governed by flexural buckling.
Table 4-22 provides available critical stress values of ΦcFcr for LRFD and Fcr/Ωc for ASD as a function of
KL/r for various values of Fy. This table does not provide values above the recommended KL/r limit of 200
for compression members. The available strength Tables 4-1 through 4-20, however, are more useful and
provide values of ΦcPn for LRFD and Pn/Ωc for ASD as a function of KL for a number of different sections
and values of Fy. As with Table 4-22, values above the recommended KL/r limit of 200 are not provided.
The values in Table 4-22 are based on flexural buckling and Equations E3-2 and E3-3, therefore local
stability is assumed and width-thickness ratio limits must not be exceeded. However, some of the shapes in
the column load tables exceed these limits (and are identified by the footnote “c”) but the tabulated strength
provided has been computed according to Section E7 as described above.
All of the notes provided up to this point in the course have dealt with failure as a result of flexural buckling
(including local buckling effects). For some cross sections, however, failure may occur as a result of twisting
(i.e. torsional buckling) or by a combination of twisting and bending (i.e. flexural-torsional buckling). When
an axially loaded compression member becomes globally unstable it can buckle in one of three ways (see
Figure 3):
1. Flexural Buckling: This type of buckling, as indicated above, has already been discussed. It is
deflection caused by bending about the axis corresponding to the largest slenderness which typically
occurs about the minor principal axis (i.e. the axis with the smallest radius of gyration). Compression
members with any type of cross section can fail in this manner.
2. Torsional Buckling: This type of failure is caused by twisting about the longitudinal axis of the
member. This type of buckling occurs only with doubly symmetrical sections with very slender cross-
sectional elements. Standard rolled shapes are not susceptible to torsional buckling, however,
members built up from thin plate elements should be investigated for this type of failure. The
cruciform shape shown in Figure 3 is particularly vulnerable to this type of buckling.
3. Flexural-Torsional Buckling: This type of failure is caused by a combination of flexural and torsional
buckling and is exhibited by a member bending and twisting simultaneously. This type of buckling
can occur only with unsymmetrical sections, both those with one axis of symmetry (i.e. channels,
tees, double angles, equal leg angles) and those with no axis of symmetry such as unequal leg angles.
FIGURE 3
Section E4(a) of the specifications covers double angle and tee shaped members. Section E4(b) provides a
more general approach that can be used for any shape.
As with the analysis and design of compression members subjected to flexural buckling, the strength of most
double angles and tees that are subject to flexural-torsional buckling can be found in the column load tables
of the 13th Edition. These tables give two sets of values of the available strength; one based on flexural
buckling about the x-axis and one based on flexural-torsional buckling about the y-axis (as provided by
Section E4(a)). Available compression strength tables are also provided for single angle members. The
values provided for these members are based on the provisions of Section E5 only.
The categories of combined bending and axial loading (along with the likely mode of failure) include:
2. Axial compression and bending about one axis; failure by instability in the plane of bending without
twisting.
3. Axial compression and bending about the strong axis; failure by lateral torsional buckling.
4. Axial compression and biaxial bending (torsional stiff sections); failure by instability in one of the
principal directions.
5. Axial compression and biaxial bending (thin-walled sections); failure by combined twisting and
bending.
6. Axial compression, biaxial bending and torsion; failure by combined twisting and bending when
plane of bending does not include the shear center.
The provisions for the design and analysis of members subjected to combined bending and axial forces are
provided in Chapter H of the 13th Edition. In general this Chapter provides interaction equations for axial and
© D. Matthew Stuart Page 5 of 15
www.PDHcenter.com PDH Course S216 www.PDHonline.org
bending strengths (i.e. required strength/available strength ≤ 1.0) that in combination have to be less than or
equal to 1.0.
The above approach to the design of combined bending and axial loads is satisfactory as long as the axial
load is not too large. This is because the presence of an axial load produces secondary moments as a result of
the deflection caused from the flexural buckling, which must be accounted for unless the axial load is
relatively small. See Appendix 7 of the 13th Edition (page 16.1-196) for guidance concerning the axial load
limit. It should be noted that pinned end columns with no lateral load or applied end moment will not have
any secondary effects, therefore Table 4-22 provides the appropriate values from equations E3-2 and E3-3
with the required safety and resistance factors for use in calculating of the available axial strength of a
column.
An example of the impact of this secondary effect is shown in Figure 4. For this example the secondary
moment is largest where the deflection of the column is the largest, in this case at mid-height, where the total
moment = wL2/8 + Pδ. This combined moment results in even more deflection over and above that resulting
from the transverse load, however the total deflection cannot be found directly because of the non-linear
nature of the condition.
FIGURE 4
Ordinary structural analysis methods that do not take into account the displaced geometry described above
are referred to as first-order methods. Iterative numerical techniques, referred to as second-order methods,
can be used to find the defections and secondary moments, however these methods are impractical for
manual calculations and are usually only available via a computer program. Most current building codes,
including the AISC Specifications, permit the use of second-order analysis or an alternate approach referred
to as a moment magnification method. This later method involves computing the maximum bending
moments resulting from the flexural loading using first-order analysis methods then multiplying the result by
a moment magnification or amplification factor to account for the secondary moment.
Chapter C of the 13th Edition provides the methods of moment amplification for steel members. Two
amplification factors are provided in this Chapter; one to account for amplification resulting for the member
deflection and one to account for the effect of sway when the member is a part of an unbraced frame. This
approach is very similar to the methods used in ACI 318-05 for reinforced concrete design. For LRFD the
amplification factor = 1/(1 – (Pu/Pe)).
For members in a braced frame (i.e. where no sway can occur and the ends of the column cannot translate
with respect to one another) there are two conditions that can occur: Single Curvature bending (see Figure 5);
where the maximum moment amplification occurs at the center where the deflection is the largest, and
Reverse Curvature bending (see Figure 6); where the maximum primary moment is at one of the ends of the
column and the maximum amplification occurs between the two ends.
FIGURE 5 FIGURE 6
The maximum moment in a beam-column therefore depends on the distribution of the bending moment
within the member. This distribution is accounted for by a factor Cm, which is applied to the amplification
factor (B1) such that;
Where: Pr = the required axial compression strength = Pu for LRFD; = Pa for ASD
α = 1.0 for LRFD; = 1.60 for ASD
Pe1 = π2EI/(K1L)2
Note that subscripts in the equations provide in Chapter H are 1 for a braced condition and 2 for an unbraced
condition. Also, the factor Cm applies only to braced conditions. Values of Cm in Chapter H are provided for
two conditions; one where there is a transverse load applied between the ends of the member, and another
where there is no transverse loading between the ends. The values for Cm for these two conditions are
provided in Equations C2-4 (page 16.1-22) and C-C2-2 (page 16.1-235), respectively. The later equation is
provided only if a more refined analysis is required, otherwise Cm = 1.0.
For beam-column members in unbraced frames in which the ends of the columns are free to translate the
maximum primary moment resulting from the effects of the sidesway almost always occur at one end of the
member. In addition, the maximum secondary moment in an unbraced frame always occurs at the member
end. As a result of this condition, the maximum primary and secondary moments are usually additive and
there is no need for a Cm factor. The moment amplification factor for unbraced frames (B2) is provide in
Equation C2-3 of the 13th Edition (page 16.1-21). The rationale for using the summation of the Pe2 and Pnt
(the first order axial force assuming no lateral sidesway) in the equation for B2 is that if sidesway is going to
occur all columns in that story of the building must sway simultaneously. For a further discussion of the
related topic of Leaner Columns, see Leaner Columns Course S121.
Most of the moment transferred from a beam to a column in a rigid connection involves a force-couple
consisting of tensile and compressive stresses in the beam flanges that result in the application of large
concentrated loads to the column. This condition typically requires that the column be reinforced to avoid
local buckling. For the condition represented in Figure 7, the applied negative moment from the beam results
© D. Matthew Stuart Page 7 of 15
www.PDHcenter.com PDH Course S216 www.PDHonline.org
in concentrated flanges forces (tension in the top and compression in the bottom) being transmitted to the
column web via the column flanges. To prevent distortion of the column flange (for the tension condition)
and buckling of the column web (for the compression condition) web stiffeners are typically added
Figure 7
Section J10 of the 13th Edition provides the basis for determining if stiffeners are required for forces applied
normal to the flanges of a wide flange section. Specific local condition checks included in this section of the
AISC Specifications are (with the exception of Web Sidesway Bucking – see Section J10.4):
1. Local Bending of the Column Flange: To avoid local bending failure of the column flange the tensile
load applied from the beam flange must not exceed the nominal strength;
Rn = 6.25tf2Fyf
For LRFD, the design strength = ΦRn, where Φ = 0.90. For ASD the allowable strength = Rn/Ω,
where Ω = 1.67. It should also be noted that if the beam flange tensile load is applied at a distance
less than 10tf from the end of the column, the nominal strength must be reduced by 50%.
2. Local Web Yielding: The available web strength due to compression yielding for loads applied at a
distance from the end of the column that is more than the depth of the column;
Rn = (5k + N)Fywtw
If the load is applied at a distance from the end of the column that is less than the depth of the
column;
Rn = (2.5k + N)Fywtw
Where:
k = the distance from the outer flange surface of the column to the toe of the fillet of the column web
N = length of the applied load = thickness of the beam flange or flange plate
For LRFD, the design strength = ΦRn, where Φ = 1.00. For ASD the allowable strength = Rn/Ω,
where Ω = 1.50.
3. Web Crippling: To prevent web crippling when the compressive load is applied to one flange only (as
in the case with an exterior column with a beam connected to one side only) the applied load must not
exceed the available strength provided by Equation J10-4 (page 16.1-117), where d = the total
column depth. If the load is applied less than d/2 from the end of the column then Equation J10-5a or
J10-5a controls (depending on the relationship of N/d). For LRFD, the design strength = ΦRn, where
Φ = 0.75. For ASD the allowable strength = Rn/Ω, where Ω = 2.00.
4. Web Compression Buckling: Compression buckling of the column web must be investigated when the
loads are delivered to both column flanges (as in the case of an interior column with beams on both
sides of the column). The nominal strength for this limit case is provided by Equation J10-8 (page
16.1-119), where h = the column web depth from toe to toe of the flange fillets. If the applied load is
within a distance d/2 from the end of the column, the strength must be reduced by 50%. For LRFD,
the design strength = ΦRn, where Φ = 0.90. For ASD the allowable strength = Rn/Ω, where Ω = 1.67.
5. Web Panel Zone Shear: The transfer of large moments to a column can produce large shearing
stresses in the column web within the boundaries of the connection. This region is usually defined as
the “panel zone” as represented in Figure 8. The nominal web shear strength for this condition is
provided by Equation J10-9 (page 16.1-119) or J10-10 (depending on the relationship of Pr and
0.4Pc). Equation J10-11 is provided for plastic deformation of the panel zone when frame stability is
considered as a part of the analysis. For LRFD, the design strength = ΦRn, where Φ = 0.90. For ASD
the allowable strength = Rn/Ω, where Ω = 1.67.
FIGURE 8
If the required strength is greater than the available strength for any of the above limit states, column web
stiffener plates must be provided. The nominal strength provided by a stiffener plate = FystAst, where Fyst =
the yield stress of the stiffener and Ast = the area of the stiffener.
For LRFD, the design strength of the stiffener is equated to the extra strength needed with the required area
of the stiffener solved for as;
For ASD, the allowable strength of the stiffener is equated to the extra strength needed with the area of the
required stiffener solved for as;
For column webs with insufficient panel zone shear strength it is more common to add a doubler plate, a
diagonal stiffener or increase the column size to a section with a thicker web. Section J10.8 (page 16.1-120)
provides guidelines for the proportioning of stiffener plates.
Additional guidelines can also be found in AISC Design Guide 13; Wide-Flange Column Stiffening at
Moment Connections.
The design of column base plates subjected to axial compression is fairly straight forward. The design of
compression only base plates involves:
1. Determining the minimum area of the base plate as controlled by the bearing strength of the concrete
(or grout) under the steel.
2. Determining the thickness of the plate as controlled by the bending strength of the plate.
The allowable bearing strength of concrete is governed by Section 10.17 of ACI 318-05. The design bearing
strength of concrete shall not exceed; Φ(0.85fc’A1); where Φ = 0.65 and A1 = the loaded or bearing area.
When the supporting surface of the concrete is wider on all sides than the loaded area, then the design
strength can be increased by the ratio (A2/A1)½, but not more than 2.0; where A2 is as shown in Figure 9.
FIGURE 9
The methods of calculating the minimum base plate thickness are provided on page 14-6 of the 13th Edition
as;
The calculation of a base plate subjected to both compression and overturning moment is somewhat more
complicated in that the situation is similar to the derivation of the soil bearing stress under a footing
subjected to an axial load and overturning moment because the grout or concrete under a base plate cannot
resist any tension in the same way that soil cannot resist any tensile stresses. The difference with a base plate,
however, is that the tensile force induced by the overturning moment is resisted by anchor rods (formally
referred to as anchor bolts).
There are a number of different methods available for the analysis of base plates subjected to axial loads and
overturning moments. Some are based on elastic analysis and some are based on limit state or ultimate
strength analysis. An example of an ultimate strength approach is provided in Calculating Service Moment
Capacity of Anchor Bolted Connections; Practice Periodical on Structural Design and Construction; February
1999. Other resources include the AISC Design Guide #1; Base Plate and Anchor Rod Design, unfortunately
the 3rd Edition of this publication is being developed right now and as a result the 2nd Edition is no longer
available on line. Another practical approach referenced by Steel Structures Design and Behavior, 4th Edition
is that provided by Omar Blodgett in the Design of Welded Structures.
Anchor rod material is covered under the ASTM F1554 specification which was introduced in 1999. This
specification is the first time that hooked, headed, threaded, and nutted rods in multiple grades of materials
were fully addressed in one specification. Prior to ASTM F1554, A36 and A307 bolts were the most
common type of material to be specified for anchor rods. ASTM F1554 rods are available in three grades; 36
ksi, 55 ksi and 105 ksi. Different grades of rods are identified by color; 36 is blue, 55 is yellow and 105 is
red.
Grade 36 is the most commonly specified and has a tensile strength of 58 ksi and comes in sizes up to 4
inches in diameter which are all weldable. Grade 55 has a 75 ksi tensile strength and is also available up to 4
inches in diameter. Weldablity Supplement S1 and the carbon equivalent formula in Section S1.5.2.1 of
ASTM F1554 can be specified to allow for welded field corrections of this grade of rod. Grade 105 has a
tensile strength or 125 ksi and comes in sizes up to 3 inches in diameter. All three grades of rods are suitable
for galvanizing by either a hot-dip process (ASTM A153 Class C) or a mechanical process (ASTM B695
Class 50). It should be noted that the same galvanizing process used for the rods should also be used for the
nuts to assure proper matching of the threads. Appropriate ASTM A563 nuts for the various grades of rods
are provided in Section 6.6.1 of ASTM F1554.
Threads for ASTM F1554 rods can be made by either rolling or cutting. Rolled and cut threaded rods have
the same strength (because the stress area remains the same for each), however, the elongation of the rods
with rolled threads and cut threads will differ. This is because a rolled threaded rod has about 14% less
resistance to elongation because the minimum body diameter of a rolled thread is 0.9067 inches (for a 1 inch
diameter rod) while the minimum body diameter of a cut thread rod is 0.9755 inches (for a 1 inch diameter
rod).
The design requirements for anchor rods embedded in concrete are covered under Appendix D of ACI 318-
05. This portion of the Code covers both cast-in (i.e. headed, and threaded and nutted) and post-installed (i.e.
drilled and epoxied, undercut or wedge) anchors. Basically the tensile capacity of an anchor rod, as
controlled by concrete, is based on the resistance provided by the pullout cone similar to that shown on page
14-11 of the 13th Edition (see Figure 10). Similar cones of concrete resistance are also used to establish the
shear capacity of an anchor rod when it is located next to the edge of the concrete. The tensile cone of
concrete is engaged by the anchor rod either by bearing from a headed stud or nut and or washer located at
the base of the rod. In addition, it is also possible to engage the concrete cone via the deformations of an all-
threaded rod through mechanical anchorage with the concrete. Shear from an anchor rod is transmitted to
the concrete via bearing. It should be noted that because of the typical close spacing of anchor rods, it is
common for the cones of concrete resistance to over lap. Appendix D includes provisions for the methods of
calculating the equivalent cones of resistance for groups of closely spaced rods.
FIGURE 10
Although hooked rods are allowed in Appendix D, the use of hooked anchors is not recommended for two
reasons; first the rods (if smooth) can be physically pulled out of the concrete if enough tensile force is
applied to the anchor, and secondly these type of rods have been known to fail prematurely at the cold bend
of the hook. It is also recommended that only epoxied anchor rods be used for post-installed applications that
are subjected to cyclical loads. This is because the other types of post-installed anchors (wedge and undercut)
are susceptible to loosening under repeated cyclical loads.
Figures 11a and 11b is provided below to illustrate an example of a typical base plate and anchor rod detail
for a building. Note that a plate has been attached to the bottom of the anchor rod to help develop the
resisting cone of concrete.
Additional notes and guidelines concerning base plates and anchor rods include:
1. There are four main differences between column base plate/anchor rod connections and other steel
framing connections:
a. Anchor rods are installed during the construction of the foundation typically at a point in the
construction administration phase of the project at which the engineer of record and the
fabricator may not have communicated. This situation can lead to errors in both the shop
drawings and the field installation.
b. Larger anchor rod setting allowances have to be incorporated into the base plate details even
though the installation tolerances are relatively tight (i.e. less than or equal to 1/8 inch
between any two anchor rods and less than or equal to ¼ inch between one group of anchor
rods and another adjacent group).
c. Anchor rods can be easily damaged by heavy equipment in the field during the construction
phase.
d. If an anchor rod is damaged, the repair and or replacement of the damaged rod can be difficult
and expensive. For a discussion of the recommendations for the repair of damaged or
misplaced anchor rods see Modern Steel Construction, May 2004.
2. OSHA safety regulations require that all columns be provided with a minimum of four anchor rods.
Satisfying this requirement can be difficult in situations where placement of the column next to a wall
makes access difficult or if the allowable architectural constraints of an exposed base plate for a
relatively small column make it difficult to conceal the anchor rods.
3. Because of the significant reduction in the allowable tensile strength of anchor rods that occurs with
rods that are also subjected to shear forces, anchor rods should not be used for the transfer of the base
shear reaction from the column to the footing. Instead it is recommended that the base shear forces be
transferred to the surrounding foundation system via bearing of the embedded portion of the steel
column against the surrounding concrete slab. The slab in turn can be used to distribute the shear to
other surrounding footings, walls and foundation systems.
4. For columns that are located in a corner of the building where a wall will limit access to at least two
sides of the base plate, it should always be assumed that the wall will be in place before the column is
erected. Therefore the base plate should be detailed to allow for access to all of the anchor rods (see
Figure 11).
FIGURE 11
5. Always specify enough anchor rod projection above the top of the nut to prevent problems in the
field. A minimum of ½ inch should be provided, however, ¾ to 1 inch is recommended. See Figure
12 for an example of a field repair when the anchor rod is too short to properly engage the nut.
FIGURE 12
© D. Matthew Stuart Page 14 of 15
www.PDHcenter.com PDH Course S216 www.PDHonline.org
6. The specified grout thickness beneath a base plate should be at least 1½ inches for ¾ inch diameter
anchor rods when using leveling nuts and washers. A minimum of 2 inches of grout should be used if
a leveling plate is employed.
7. Extra threaded length of the rod should be specified in case the rod projects to high out of the top of
the concrete. Normally threads are only required to extend just 1 inch below the top of concrete.
8. Avoid specifying a number of different sizes, types and grade of anchor rods on any one project.