maximum-demand-controller
maximum-demand-controller
Application Feature
Ÿ Commercial and industrial sanctioned demand monitoring & Ÿ Two modes of programming - preventive mode (only
controlling applications alarm no control), predictive mode (alarm and automatic
Ÿ Control panels for complete plant demand controlling control)
Ÿ Demand management for commerce and industry Ÿ Predictive demand control to forewarn, take corrective
measures and check maximum demand crossovers
Ÿ Multi-level (phase wise and shift wise) priority based
Benefits automatic load control mechanism to disconnect low
Ÿ Easy interface with external devices through built-in priority loads in phased manner
Modbus (RS-485) Ÿ Configurable demand integration period for sliding and
Ÿ Detachable connectors for easy installation fixed type
Ÿ Three relay and one alarm output Ÿ Optimised load disconnection time
Ÿ Suitable for star or delta connections and for low or Ÿ Online load planning by continuously indicating loads
high-voltage applications that can be added or need to be disconnected (within
Ÿ Alarm output for audible indication. safe operating limits)
Ÿ Field-configurable CT/PT primary and secondary values Ÿ Check meter with accuracy class 0.2s,0.5s and 1.0
using push-buttons Ÿ Auto and push button display
Ÿ Calibration LED for on-site accuracy check Ÿ An user friendly software to program and monitor
Ÿ Configurable software (ConfigView) for reading of Ÿ Control outputs for alarm and trip applications - it
parameters and load survey provides 3 control and one alarm outputs, in the form of
Ÿ Shift wise demand configuration potential free contacts
Ÿ Large four-line seven-digit display (9.7 H x 5 W mm) with
quadrant identification section and bar graph for
instantaneous power-level indication
Ÿ Ethernet gateway module for easy integration
Maxchek 400
Enriched software - ConfigView
Tripping Priority
configuration of
trip circuits in
shifts
Connection diagram
S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1S2 S1 S2
V1 V2 V3 VN V1 V2 V3 VN V1 V2 V3 VN
I1 I2 I3 I1 I2 I3 I1 I2 I3
Mechanical dimensions
96 mm
m mm
57 m 65
mm
45
96 mm
56 mm
m
58 m
Ethernet
Meter with control & alarm module Ethernet module Meter with control & alarm and Ethernet module
Maxcheck 400
Technical specifications
Electrical
Connection type Common product for HT3/ HT4/LT application
Wiring configuration Common product for 3 P-3 W and 3 P-4 W application
Voltage range:
Measurement voltage range 57.7 V(100V) - 240 V (415 V) AC 3 phase 4 wire (3 phase 3 wire)
Tolerance -30% to +20% of Vn
Aux power supply range 80 - 300 V AC/DC or 24 - 60 V DC (variant)
Current range Available 1-2A and 5-10 A in single variant (field configurable)
Main frequency 50/60Hz with ±5%
Accuracy class 0.2s, 0.5s, 1.0
Burden Aux burden: 3.5 VA; 8VA with module connected
Current ckt burden: 1 A - 0.05VA per phase, 5 A - 0.25 VA per phase
Voltage ckt burden: 0.15 VA per phase
Energy type Active Imp (T), Apparent Imp, Active Forwarded, Apparent Forwarded
Averaging period 1min or 5min
Trip circuit 3 Circuit
Alarm activation time Active for 30 seconds or active for whole averaging period
Short time over current 20 x Imax for 1 sec., 10 x Imax for 3 sec., 7 x Imax for 10 sec.
Compliance
Standards* IS13779, IS14697, IEC62052-11, IEC62053-23 and IEC62053-22, IEC61010
Mechanical
Dimensions (WXHXD) 96 x 96 x 115 mm
Cut out size 92 x 92 mm
Weight 0.5 kg (approx)
Mechanical enclosure FRPC
Terminals Combicon connector
Max conductor size 2.5 mm2
Environmental
Iingress protection IP 54 (front fascia); IP20 (at terminals)
Insulation 4 kV RMS 50 Hz
Impulse withstand 6 kV
Temperature -20 °C to +60 °C (operating)
-25 °C to +80 °C (storage)
Humidity 95% non-condensing
Features
Favourite page On/Off
CT/VT primary Configurable in field through keypad
Communication RS485 Modbus half duplex (default) and data will be available in floating point
format
Specifications are subject to change without prior notice
Modules
Control & alarm 1 Alarm (230VAC/DC at 100mA) and 3 control output (2A at 230VAC, SPST NO
type)
Ethernet 10/100base-T for Modbus over TCP/IP communication
www.securemeters.com
2-18/Ver 2.0