Ee 8411 Em-II Lab Manual 2017 Reg
Ee 8411 Em-II Lab Manual 2017 Reg
ENGINEERING COLLEGE
VILLUPURAM
(Approved by AICTE, New Delhi & Affiliated to Anna university, Chennai)
Vadakuchipalayam, Kappiyampuliyur post,Villupuram-605601,Tamilnadu.
LAB MANUAL
YEAR/SEMESTER: II/IV
REGULATION: R-2017
1
SYLLABUS
EE8411 ELECTRICAL MACHINES LABORATORY – II LTPC 0042
OBJECTIVES:
▪ To expose the students to the operation of synchronous machines and induction
motors and give them experimental skill.
LIST OF EXPERIMENTS
TOTAL: 60 PERIODS
2
OUTCOMES:
S.NO TITLE
Regulation of three phase alternator by EMF and MMF methods.
1
3
Ex. No: 1 Date:
AIM:
APPARATUS REQUIRED:
PRECAUTIONS:
PROCEDURE:
O.C. TEST:
1. Using the 200 Ω potential divider, current in field circuit is increased in steps
of 0.1A and at each step the alternator induced voltage indicated by voltmeter
and the corresponding field current (If) are noted in tabular column.
4
2. This procedure is continued until the alternator voltage is 120% of its rated
voltage.
3. After completing O.C. Test, the potential divider and motor field rheostat are
brought to its minimum position.
4. After completing the experiment, calculate Synchronous Impedance,
Synchronous Reactance & Regulation using the formulae given.
5. Using the data, Plot the graph between EoVs If.
S.C. TEST:
1. The alternator terminals are short circuited by closing TPST switch through
anammeter.
2. The rated current is made to flow through the armature of the stator windings
by carefully adjusting 220 ohms potential divider from the minimum position.
3. After completing the experiment, calculate the Load current, Field Current
and Regulation.
4. Using the data, Plot the graph IscvsIf and % Regulation vs Power Factor for
both the EMF and MMF methods.
CIRCUIT DIAGRAM:
5
TABULATION:
O.C. TEST
S.C TEST
FORMULAE USED:
EMF Method:
6
E0 = Induced EMF per Phase, V=Rated voltage per phase, Ra = Armature
resistance in Ω, Ia = Armature current in A; ‘+’ for lagging p.f. load. ‘-‘for
leading p.f. load.
MMF Method:
Where ‘+’ for lagging p.f. load, ‘-‘for leading p.f. load.
EMF METHOD:
Power Factor
Induced emf (Eo)
Sl. No. (Cosϕ) Reg. (%)
in (V)
0.8 lag
1
unity
2
0.8 lead
3
7
MODEL CALCULATION: (EMF method)
MODEL GRAPH:
MMF METHOD:
Power Factor
Induced emf (Eo)
Sl. No. (Cosϕ) Reg. (%)
in(V)
1
2
3
8
RESULT:
Thus, the regulation of the given three phase alternator is predetermined by
using EMF and MMF methods.
9
Ex. No: 2 Date:
AIM:
To conduct OC and SC and ZPF tests on the given 3-Φ alternator and to
predetermine the regulation by (i) ZPF method and (ii) ASA method
APPARATUS REQUIRED:
PRECAUTIONS:
PROCEDURE:
O.C. TEST:
1. Using the 200 Ω potential divider, current in field circuit is increased in steps
of 0.1A and at each step the alternator induced voltage indicated by voltmeter
and the corresponding field current (If) are noted in tabular column.
10
2. This procedure is continued until the alternator voltage is 120% of its rated
voltage.
3. After completing O.C. Test, the potential divider and motor field rheostat are
brought to its minimum position.
4. After completing the experiment, calculate Synchronous Impedance,
Synchronous Reactance & Regulation using the formulae given.
5. Using the data, Plot the graph between EoVs If.
S.C. TEST:
1. The alternator terminals are short circuited by closing TPST switch through
anammeter.
2. The rated current is made to flow through the armature of the stator windings
by carefully adjusting 220 ohms potential divider from the minimum position.
3. After completing the experiment, calculate the Load current, Field Current
and Regulation.
ZPF test:
CIRCUIT DIAGRAM:
11
TABULATION:
12
PROCEDURE TO DRAW THE VECTOR DIAGRAM (ZPF METHOD)
FORMULAE USED
MODEL CALCULATIONS
13
1. Join the points O and D, which will be equal to the air gap voltage (Eair).
2. Find out the field current (Ifc) for the corresponding air gap voltage (Eair) from
the OCC curve.
3. Draw the vector OF with the magnitude of Ifc which should be perpendicular
to the vector OD.
4. Draw the vector FG from F with the magnitude Ifa in such a way it is parallel
to the current vector OB.
5. Join the points O and G, which will be equal to the field excitation current (If).
6. Draw the perpendicular line to the vector OG from the point O and extend CD
in such a manner to intersect the perpendicular line at the point H.
7. Find out the open circuit voltage (Eo) for the corresponding field excitation
current (If) from the OCC curve.
8. Find out the regulation from the suitable formula.
14
RESULT:
Thus, the regulation of the given three phase alternator is predetermined by
using ZPF and ASA methods.
15
Ex. No: 3 Date:
AIM:
To conduct the slip test on the given 3-Φ alternator and to predetermine the
regulation.
APPARATUS REQUIRED:
PRECAUTION
1. All the switches should be kept open at the time of starting the experiment.
2. There should be no load at the time of starting the experiment.
3. The motor field rheostat should be kept at minimum resistance position.
PROCEDURE
16
CIRCUIT DIAGRAM:
TABULAR COLOUMN
For calculation of Xd and Xq
SL. MAXIMUM MINIMUM MAXIMUM MINIMUM
No. VOLTAGE VOLTAGE CURRENT CURRENT
(V) (V) (A) (A)
FORMULAE USED
17
Model Calculation :
18
RESULT
The direct axis and quadrature axis component of the three-phase alternator
have been calculated.
19
Ex. No: 4 Date:
APPARATUS REQUIRED
SL. Name of the apparatus Range Type Quantity
No.
1 Voltmeter (0 – 300 V) M. I. 1
2 Voltmeter (0 – 150 V) M. I. 1
3 Ammeter (0 – 20 A) M. I. 1
4 Ammeter (0 – 10 A) M. I. 1
5 Ammeter (0 – 2 A) M. I. 1
6 Wattmeter 300 V, 10 A UPF 1
7 Rheostat 220 Ω, 2 A - 1
8 Single phase Auto (0 – 270 V) - 1
Transformer
9 Tachometer (0 – 10000 rpm) Digital 1
PROCEDURE
4. Connections are made as per the circuit diagram.
5. The motor should be started with the help of three-point starter.
6. The motor speed should be made equal to the alternator synchronous speed
with the help of field rheostat of the motor.
7. The D. P. S. T. switch on the alternator field side should be closed.
8. The alternator field potential divider must be varied in steps.
9. At each step, all the meter readings should be noted down.
10. The above procedure should be repeated till the ammeter reads the rated
alternator current.
20
CIRCUIT DIAGRAM
CIRCUIT DIAGRAM
21
A) For Negative Sequence Reactance:
FORMULAE USED
MODEL CALCULATION:
PRECAUTION
1. All the switches must be kept open at the time of starting the experiment.
2. The auto transformer should be kept at minimum potential position.
PROCEDURE
1. Connections are made as per the circuit diagram.
2. The auto transformer should be varied in steps.
3. At each step the meter readings should be noted down.
4. The above procedure should be repeated till the ammeter reads rated
current of the alternator.
22
TABULAR COLOUMN
MODEL CALCULATION:
RESULT
Thus the negative sequence reactance and zero sequence reactance have been
determined.
23
Ex. No: 5 Date:
AIM:
To draw V and inverted V curves for the given three phase synchronous motor
APPARATUS REQUIRED:
SL. Name of the Range Type Quantity
No. apparatus
1 Voltmeter (0 – 600 V) M. I. 1
2 Ammeter (0 – 10 A) M. I. 1
3 Ammeter (0 – 2 A) M. C. 1
4 Wattmeter 600 V, 10 A UPF 1
5 Tachometer (0 – 10000 rpm) Digital 1
PRECAUTION
1. All the switches should be kept open at the time of starting the experiment.
2. The potential divider in the field circuit of synchronous motor should be
kept at minimum potential position.
PROCEDURE
1. Connections are made as per the circuit diagram.
2. Close the T. P. S. T. switch.
3. The auto transformer is varied gradually to start the motor.
4. The auto transformer is adjusted till the voltmeter reads the rated voltage of
the synchronous motor.
5. Close the D. P. S. T. switch and increase the field current.
6. At no load condition, increase the field current in steps and note down the
corresponding armature current.
7. The potential divider is brought to the minimum potential position.
8. Repeat the same procedure for different load conditions.
9. Reduce the load on the motor.
10. Reduce the field current to zero value.
11. Reduce voltage by varying auto transformer.
12. Open all the switches.
24
CIRCUIT DIAGRAM:
25
TABULAR COLOUMN
No Load Test
Half Load:
SL. No. Armature Field Power
current Ia current factor
(A) If (A)
GRAPH
Field current, If Vs Armature current, Ia
Field current, If Vs Power factor, cosф
26
RESULT
Thus, the V and inverted V curves of the given synchronous motor have been
drawn.
27
Ex. No: 6 Date:
AIM:
To conduct the direct load test on the given 3-phase induction motor and plot
the different performance characteristics curves of the machine.
APPARATUS REQUIRED:
PRECAUTIONS:
PROCEDURE:
29
NAME PLATE DETAILS:
Voltage - 415V
Current – 7.5A
Speed - 1430 rpm
Capacity – 3.7 kw or 5HP
TABULAR COLUMN:
Spring
Li balance
Spee
Line ne Input reading
S d Torqu Output
voltag cu powe
L. S1 S2 S1 e power %Sli
e rre r P.F %
N (K (K ~ p
VL nt
o. (RPM g) g) S2 (Nm) (W)
(V) IL (W)
) (Kg
(A)
)
MODEL GRAPHS:
30
FORMULAE USED:
1.
2.
3.
4.
5.
6.
7.
MODEL CALCULATION:
RESULT:
Thus the load test on given three phase induction motor is conducted and the
performance characteristics curves are plotted.
31
Ex. No: 7 Date:
AIM:
APPARATUS REQUIRED:
SL.
Apparatus Type Range Quantity
No.
3 Ф Induction Motor Set
1 - - 1 No
up
(0-600 V)
2 Voltmeter AC MI (0-150 V) 1 each
(0-10 A)
3 Ammeter AC MI (0-2 A) 1 each
12.41 kVA/
Three phase auto
4 - 415 1 No
transformer
(0-470 V)
Double Element
5 - 150 V,10 A 1 No
Wattmeter
6 Wattmeter LPF 600 V, 10 A 2 No
- As
7 Connecting wires -
Required
PRECAUTIONS:
1. Remove the fuse carriers before wiring and start wiring as per the circuit
diagram.
1. Fuse calculations: This being a load test, the required fuse ratings are 125
% of rated current.
2. The auto transformer should be kept in minimum position.
3. Replace the fuse carrier with appropriate fuse wires after the circuit
connections are checked by the staff-in-charge.
32
CIRCUIT DIAGRAM:
NO LOAD TEST:
33
PROCEDURE:
TABULATION:
34
FORMULAE USED:
MODEL CALCULATIONS:
35
EQUIVALENT CIRCUIT:
36
RESULT: The No-load and blocked rotor test was conducted on the given three-
phase induction motor & the equivalent circuit is drawn.
37
Ex. No: 8 Date:
AIM:
To separate the no load losses of the given 3 phase squirrel cage
induction motor as iron losses and mechanical losses.
APPARATUS REQUIRED:
S.NO NAME OF THE RANGE TYPE QUANTITY
APPARATUS
1 Ammeter (0-5) A MI 1
2 Voltmeter (0-600) V MI 1
3 Wattmeter 600V,5A LPF 2
4 3 Ф Auto transformer 415/(0-470)V -- 1
5 Tachometer -- Digital -- 1
6 Connecting wires -- As required
PRECAUTIONS:
i. The autotransformer should be kept in minimum voltage position.
ii. The motor should not be loaded throughout the experiment.
PROCEDURE:
i. Connections should be made as per the circuit diagram.
ii. Start the motor by giving three phase supply.
iii. Vary the autotransformer till rated speed is attained and note the inputpower,
voltage and current.
iv. Repeat the same procedure for and tabulate the reading.
v. Find the stator copper loss and constant loss by respective formulas.
vi. Draw the suitable graph to find the mechanical losses.
vii. Obtain the core los by separating the mechanical loss from constant losses.
GRAPH:
The graph drawn between constant losses (watts) and input voltage(volts).
FORMULAE USED:
1. Input power (W) =(W1+W2)in watts
2. Stator copper loss =3I2Rs in watts
3. Constant loss/phase (Wc)= (W-3I2Rs)/3 in watts
4. Core loss/phase (Wi)= (constant loss/phase)-mechanical loss
FUSE RATING:
No load: 10% of rated current (full load current).
38
CIRCUIT DIAGRAM:
39
TABULTAION:
Constant Core
Stator Loss per Loss
SL.No V I W1 W2 W Cu Phase per
Loss (Wc) Phase
(Wi)
MODEL CALCULATIONS:
40
RESULT:
Thus, the no load losses of 3-phase squirrel cage induction motor was
separated as core losses and mechanical losses
41
Ex. No: 9 Date:
AIM:
To draw the load characteristics of a single-phase induction motor by
conducting the load test
APPARATUS REQUIRED:
S. No. Apparatus Range Type Quantity
1 Single phase induction - - 1
motor
2 Single phase auto (0 – 270 V) 1
transformer
3 Voltmeter (0-300) V MI 1
4 Ammeter (0-20) A MI 1
5 Wattmeter 300 V, 10 A, 1
UPF
6 Connecting wires - - As
required
PRECAUTIONS:
1. Motor should be started and stopped under no load condition.
2. Brake drum should be cooled with water when it is under load.
PROCEDURE:
1. Connections are made as per the circuit diagram.
2. The DPST switch is closed. The autotransformer is adjusted to get rated
voltage and corresponding no load readings are noted down.
3. Gradually increase the load upto the rated current and for each load the
corresponding meter readings are tabulated
1. Then load is removed and autotransformer reduced to zero. Then DPST
switch opened.
FORMULAE
1.
2.
3.
4.
5.
6.
42
CIRCUIT DIAGRAM
FUSE RATING
125% of rated current (full load current).
43
TABULAR COLUMN:
MODEL CALCULATION
44
MODEL GRAPH
RESULT: Load test on given single phase induction motor is conducted and the
performance curves are plotted.
45
Ex. No: 10 Date:
AIM:To draw the equivalent circuit of the given three phase induction motor by
conducting no load and blocked rotor test.
APPARATUS REQUIRED
S. No. Apparatus Range Type Quantity
1 Single phase induction - - 1
motor
2 Single phase auto (0 – 270 V) 1
transformer
3 Voltmeter (0-300) V MI 1
(0 -150) V
4 Ammeter (0-10) A MI 1
(0-10) A
PRECAUTION
1. All the switches should be kept open at the time of starting the experiment.
2. The single phase auto transformer should be kept at minimum potential
position at the time of starting the experiment.
3. For the blocked rotor test, the load is applied on the rotor and the rotor is
not allowed to rotate.
4. During the blocked rotor test, the single phase auto transformer should be
adjusted carefully and the current should not exceed the rated current of
the motor.
PROCEDURE
NO LOAD TEST
46
CIRCUIT DIAGRAM
NO LOAD TEST
47
BLOCKED ROTOR TEST
FORMULAE
48
TABULAR COLOUMN
OPEN CIRCUIT TEST
MODEL CALCULATION
RESULT
Thus, the equivalent circuit of single phase induction motor has been drawn
using no load and blocked rotor tests.
49
Ex. No: 11 Date:
STUDY OF AC STARTERS
APPARATUS REQUIRED
This will link and cut the rotor conductors which in turn will induce a current in
the rotor conductors and create a rotor magnetic field. The magnetic field
created by the rotor will interact with the rotating magnetic field in the stator
and produce rotation.
There are many methods in use to start 3-phase induction motors. Some of the
common methods are;
The starting torque is likely to be 0.75 to 2 times the full load torque. In order to
avoid excessive voltage drops in the supply line due to high starting currents,
the DOL starter is used only for motors with a rating of less than 5KW.
50
There are safety mechanisms inside the DOL starter which provides protection
to the motor as well as the operator of the motor.The power and control circuits
of induction motor with DOL starter are shown in figure.
The DOL starter consists of a coil operated contactorK1M controlled by start and
stop push buttons. On pressing the start push button S1, the contactor coil
K1M is energized from line L1. The three mains contacts (1-2), (3-4), and (5-6) in
fig. (1) are closed. The motor is thus connected to the supply.
When the stop push button S2 is pressed, the supply through the contactor
K1M is disconnected. Since the K1M is de-energized, the main contacts (12), (3-
4), and (5-6) are opened. The supply to motor is disconnected and the motor
stops.
Star-Delta Starter
The star delta starting is a very common type of starter and extensively used,
compared to the other types of the starters. This method used reduced supply
voltage in starting. Figure shows the connection of a 3phase induction motor
with a star – delta starter.
The method achieved low starting current by first connecting the stator winding
in star configuration, and then after the motor reaches a certain speed, throw
switch changes the winding arrangements from star to delta configuration.
By connecting the stator windings, first in star and then in delta, the line
current drawn by the motor at starting is reduced to one-third as compared to
starting current with the windings connected in delta.
51
At the time of starting when the stator windings are start connected, each stator
phase gets voltage , where is the line voltage. Since the torque developed
by an induction motor is proportional to the square of the applied voltage, star-
delta starting reduced the starting torque to one – third that obtainable by direct
delta starting.
When the star delta method is considered, voltage can be adjusted only by factor
of .
Figure (3) shows the connection of a 3phase induction motor with auto
transformer starter.
52
I.M. with auto transformer starter
The rotor impedance starting mechanism is usually very bulky and expensive
when compared with other methods. It also has very high maintenance costs.
Also, a considerable amount of heat is generated through the resistors when
current runs through them.
The starting frequency is also limited in this method. However, the rotor
impedance method allows the motor to be started while on load. Figure (4)
shows the connection of a 3phase induction motor with rotor resistance starter.
53
54
Rotor resistance starter
55
Ex. No: 1 Date:
APPARATUS REQUIRED:
PROCEDURE:
1. The DPST-1 is closed and the motor field rheostat is adjusted to make the
alternator run at rated speed.
2. The DPST-2 is closed and by keeping the TPST open, adjusts the alternator
field rheostat to supply the voltage equal to infinite bus bar.
3. The phase sequence of the alternator is made as same as that of the infinite
bus bar by observing the sequence of glowing of synchronizing lamps. If the
phase sequence is not same, any of the two phases are interchanged.
4. The field rheostat is adjusted to bring the frequency of the alternator to
same frequency of infinite bus bar. When the phase sequence of the two
sides are same all the lamps will begin to glow bright and dark
simultaneously. In this condition, when the frequencies are equal, the
variation of lamps bright to dark is lowest.
5. At the dimmest point the TPST switch is closed thereby synchronizing the
alternator to the bus bar.
56
RESULT: Thus the incoming alternator is successfully synchronized with the
infinite bus bar.
57
Ex. No: 2 Date:
ROTOR RHEOSTAT SPEED CONTROL OF SLIP RING INDUCTION MOTOR
AIM: To vary the speed of the slip ring induction motor using rotor
rheostat control.
APPARATUS REQUIRED:
PROCEDURE:
1. The Connection are made as per circuit diagram
2. The TPST switch is closed and three phase supply is given.
3. The motor is started with rotor rheostat starter.
4. The rotor resistance is varied and corresponding values of speed, voltage
and current are noted down.
CIRCUIT DIAGRAM
58
MODEL GRAPH:
Speed vs resistance
s 1480
1470
p 1460 1460
1450
e 1440 1440
1430
1420
e 1400
1390 Speed (rpm)
d( 1380
rp 1360
1340
46.6 32.2 21.8 12.12 5.88
Resistance (W)
resistance(ohm)
RESULT: Thus the speed of the given three phase slip ring induction motor is
varied successfully.
59