240206-Bbpl-El-Sld-P0-404-Dg Synchronization Panel Singlel Line Diagram

The document outlines the specifications and configurations for a Diesel Generator Synchronization Panel, including details on cable entry, relay locations, and electrical ratings for multiple generators. It specifies the types of circuit breakers, transformers, and communication systems required, as well as safety features like a CO2 flooding system. Additionally, it includes general notes on compliance with IEC standards and the construction requirements for various electrical panels.

Uploaded by

Supriyo Mondal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
171 views1 page

240206-Bbpl-El-Sld-P0-404-Dg Synchronization Panel Singlel Line Diagram

The document outlines the specifications and configurations for a Diesel Generator Synchronization Panel, including details on cable entry, relay locations, and electrical ratings for multiple generators. It specifies the types of circuit breakers, transformers, and communication systems required, as well as safety features like a CO2 flooding system. Additionally, it includes general notes on compliance with IEC standards and the construction requirements for various electrical panels.

Uploaded by

Supriyo Mondal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

DG SYNC.

PANEL
CABLE ENTRY : TOP WOODWARD RELAY
LOCATION : ELECTRICAL ROOM
TYPE : FREE STAND EASYGEN 3200XT
DG 1-2000KVA 3Ph, 4WIRE DG 2-2000KVA 3Ph, 4WIRE DG 3-2000KVA 3Ph, 4WIRE DG 4-500KVA 3Ph, 4WIRE
INDOOR TYPE IP43 415V, INCOMING 0.8PF 415V, INCOMING 0.8PF 415V, INCOMING 0.8PF 415V, INCOMING 0.8PF
CL : -- -- KW WITH PCC3.3 WITH PCC3.3 WITH PCC3.3 WITH PCC3.3

REF CT SCADA REF CT SCADA REF CT SCADA REF CT


PLC/HM1 PLC/HM1 PLC/HM1

4000A 4P FIXED TYPE 4000A 4P FIXED TYPE 4000A 4P FIXED TYPE 800A 4P FIXED TYPE
ACB MOUNTED ABOVE ACB MOUNTED ABOVE ACB MOUNTED ABOVE ACB MOUNTED ABOVE
ALTERNATOR ALTERNATOR ALTERNATOR ALTERNATOR

4000A TPN+E SANDWICH. 4000A TPN+E SANDWICH. 4000A TPN+E SANDWICH. 800A TPN+E SANDWICH.
CO2 flooding system with side
BUSDUCT ENTRY OUTDOOR BUSDUCT ENTRY OUTDOOR BUSDUCT ENTRY OUTDOOR BUSDUCT ENTRY OUTDOOR
mounted cylinder required & CT-11,12,13 CT-11,12,13 CT-11,12,13
CT-11,12,13 IP65 WITH CANOPY & INDOOR55 IP65 WITH CANOPY & INDOOR55 IP65 WITH CANOPY & INDOOR55 IP65 WITH CANOPY & INDOOR55
entire panel tubing arrangement ,14,CL-PS ,14,CL-PS ,14,CL-PS
required for all compartment. ,14,CL-PS 4000/5A 4000/5A 800/5A
4000/5A 87G 87G 87G 87G
Vk>=260V Vk>=260V Vk>=260V
#.All Meters Shall be EMns Compabilities & Vk>=260V
Each Panel Shall Have one common CT-7,8,9,10 CT-7,8,9,10 CT-7,8,9,10
CT-7,8,9,10 CL-PS CL-PS CL-PS 800/5A
Communication through Gateway.
CL-PS
64R 64R 64R 64R
4000/5A 4000/5A Vk>=260V
#.All TPN ACB's Shall be External 4000/5A Vk>=260V
27 59 81 86 95 27 59 81 86 95 Vk>=260V 27 59 81 86 95 27 59 81 86 95
NCT Provide. Vk>=260V
PCC3.3 PCC3.3 MCB PCC3.3 PCC3.3

ACB (EDO) ACB (EDO) ACB (EDO) ACB (EDO)


4000A TPN 4000A TPN 4000A TPN 800A TPN
LSING A LSING B LSING D LSING E

433V/433V

433V/433V

433V/433V

433V/433V
500VA

500VA

500VA

500VA
TRAFO

TRAFO

TRAFO

TRAFO
CT-1,2,3 CT-1,2,3 CT-1,2,3 CT-1,2,3
CL-1,10VA CL-1,10VA CL-1,10VA CL-1,10VA
4000/5A 4000/5A 4000/5A 800/5A

32A TP MPCB

32A TP MPCB

32A TP MPCB

32A TP MPCB
CT-4,5,6 Transduser CT-4,5,6 Transduser CT-4,5,6 Transduser CT-4,5,6 Transduser
to PLC to PLC to PLC to PLC
CL-1,10VA 4-20mA CL-1,10VA 4-20mA CL-1,10VA 4-20mA CL-1,10VA 4-20mA

100kA

100kA

100kA

100kA
4000/5A I
4000/5A I
4000/5A I
800/5A I

V
C
6300A, 415V,50Hz, AL. 6300A, 415V,50Hz, AL.
BUSBAR(85KA FOR 1SEC) BUSBAR-A BUSBAR-B BUSBAR(85KA FOR 1SEC)
52-5
ACB(EDO)
4P, 6300A,80KA
BUS COUPLER
Type 1+ 2 SPD 6300A 4P,ACB, R Y B 6300A 4P,ACB, R Y B
Busbar mounted Strikesorb 40C
Iimp =12.5KA, Imax140KA
EDO 80KA µP EDO 80KA µP
TOV withstand 528V for 120 mins based O/C,S/C, SPRING based O/C,S/C, SPRING
Earth Bus
Cape :Make
E/F Release RETURN E/F Release RETURN
LSING SWITCH LSING SWITCH

6300A,4 CONDUCTOR, 6300A,4 CONDUCTOR,


ALUMINIUM SANDWITCH ALUMINIUM SANDWITCH
TYPE BUS DUCT TYPE BUS DUCT
(OUTDOOR IP65 WITH (OUTDOOR IP65 WITH
CANOPY/ INDOOR IP55) CANOPY/ INDOOR IP55)

OUTGOING-1 OUTGOING-2
1050BPM CSD 800BPM ASEPTIC
SPARKING LINE
PET LINE
LEGEND :-
SYMBOL DESCRIPTION
MOTORISED DRAWOUT TYPE
VACCUM CIRCUIT BREAKER.

ELECTRICALLY OPERATED AIR CIRCUIT BREAKER WITH


O/C,S/C,E/F RELEASES & S/T, U/V COIL (DRAW OUT TYPE) ABBREVIATION :- NOTE:
NAME DISCRIPTION
MANUALLY OPERATED AIR CIRCUIT BREAKER (ACB) 1. All PCC Panels , DG Sync.Panel & SUB Panels
WITH O/C,S/C,E/F RELEASES & U/V COIL (DRAW OUT TYPE) MPCC MAIN POWER CONTRO CENTER PANEL Construction shall be Provided as per GENERAL NOTES:
MANUALLY OPERATED AIR CIRCUIT BREAKER (ACB) DG DIESEL GENERATOR
WITH O/C,S/C RELEASES & U/V COIL (DRAW OUT TYPE) IEC 60439 / CPRI Standards.
APFCR AUTOMATIC POWER FACTOR CORRECTION REALY 2. CO2 gas flooding system shall be Provided with
MANUALLY OPERATED MOULDED CASE CIRCUIT BREAKER
WITH O/C, S/C & S/T RELEASES MLP MAIN LIGHTING PANEL Automatic switch along with Hooter and fire Detection
MPDB MEDIUM POWER DISTRIBUTION PANEL tubing arrangement inside breaker & busbar Chamber
MOTOR PROTECTION CIRCUIT BREAKER

I
V

SLP SUB LIGHTING PANEL for all Pcc panels, APFC Panels & DG Sync.Panel .
MOULDED CASE CIRCUIT BREAKER. SRP SUB RAW POWER PANEL 3. EB & DG I/C side MFM Shall be Provided THD
SPD SURGE PROTECTION DEVICES Indicator.
MINIATURE CIRCUIT BREAKER. ACB AIR CIRCUIT BREAKER NO.s ISSUED TO DATE BY REMARKS
MCCB MOULDED CASE CIRCUIT BREAKER.
CONTROL TRANSFORMER.
MCB MINIATURE CIRCUIT BREAKER.
CURRENT TRANSFORMER (RESIN CAST)
CBCT CORE BALANCE CURRENT TRANSFORMER
FACIA WINDOW ANNUNCIATOR COMPLETE
WITH ACCEPT, RESET & TEST FACILITIES MPCB MOTOR PROTECTION CIRCUIT BREAKER
TPN TRIPLE POLE(TP)+NEUTRAL(N) REV NO.s DESCRIPTION DATE CHKD
DISTRIBUTION TRANSFORMER
TP/3P TRIPLE POLE
CLOSE-NEUTRAL-TRIP BREAKER CONTROL SWITCH 4P TRIPLE POLE(TP)+NEUTRAL(N) ISOLATION
LED TYPE INDICATING LAMP DP DOUBLE POLE
AUTOMATIC POWER FACTOR CORRECTION RELAY SP SINGLE POLE
MCC MOTOR CONTROL CENTER
MASTER TRIPPING RELAY (NUMERICAL)
PCC POWER CONTROL CENTER
IDMT UNDERVOLTAGE RELAY (NUMERICAL)
AHF ACTIVE HARMONIC FILTER
INSTANTANEOUS OVER CURRENT 1POLE (NUMERICAL) P0 PRELIMINARY DRAWING 06.02.2024 BR
LBS LOAD BREAK SWITCH
AC TIME OVER CURRENT RELAY (NUMERICAL) AL ALUMINUM PURPOSE:
TRIP CONTROL SYNC RELAY (NUMERICAL) Cu COPPER PRELIMINARY DRAWING
LOTO LOCKOUT TAGOUT
TRANSFORMER AUXILIARY RELAY (NUMERICAL)
NCT NEUTRAL CURRENT PROTECTION(EXTERNAL NCT) CLIENT :
REVERSE POWER RELAY (NUMERICAL)
O/C OVER CURRENT RELEASE BENGAL BEVERAGES PVT. LTD.,
RESTRICTED EARTH FAULT RELAY S/C SHORT CIRCUIT RELEASE WEST BENGAL
ELECTRICALLY OPERATED DRAW OUT ACB S/T SHUNT TRIP RELEASE

MANUALLY OPERATED DRAW OUT ACB


E/F EARTH FAULT RELEASE PROJECT :
U/V UNDER VOLTAGE RELEASE
ELECTRICAL INTERLOCKING
SDB SUPPLY DISTRIBUTION BOARD
BENGAL BEVERAGES PVT. LTD. DURGAPUR
MECHANICAL INTERLOCKING
SLRP SUB LIGHTING & RAW POWER PANEL EXPRESS WAY DANKUNI HOOGHLY DANKUNI
ON
OFF
ILLUMINATED PUSH BUTTON ON AND OFF MEDB MAIN EMERGENCY DISTRIBUTION BOARD COAL COMPLEX WEST BENGAL-712310
CAPACITOR BANK. KWH ELECTRONIC KILOWATT HOUR METER
EFR EARTH FAULT RELAY TITLE : DG SYNCHRONIZATION PANEL
DIESEL GENERATOR.
VSR VOLTAGE SENSING RELAY
A/M
AUTO/MANUAL SWITCH
SINGLE LINE DIAGRAM
BCU BATTERY CHARGER UNIT
LOCAL/REMOTE SWITCH SL1 DC CONTROL SUPPLY ON NORTH : DRAWN : ABHISHEK JOB NO : B-23-24/119
CBCT
ELR CORE BALANCE CT WITH ELR. SL2 DG ON
SL3 LOAD ON DG
DESIGN : BR SCALE : NTS
RESIDUAL CURRENT CIRCUIT BREAKER
WITH OVERLOAD CURRENT SL4 COMMON WIRING CHECKED : BR REVISION : P0
MDM DIGITAL MULTI DATA METER WITH COM PORT (RS485) SL5 COMMON SHUTDOWN
MFM DIGITAL MULTI FUNCTION METER COM PORT (RS485) SL6 EARTH FAULT TRIP DATE : 06.02.2024 DRG NO : BBPL-EL-SLD-404
PQM DIGITAL POWER QUALITY MANAGER COM PORT (RS485) SL7 MAINS ON
VAF DIGITAL VOLT AMP FREQUENCY METER COM PORT (RS485) SL8 BATTERY CHARGER ON
AUXILLARY CONTACTS FOR EMS (METER+BREAKER
PB1 EMG.TRIP(STAYPUT TYPE)
ON/OFF/TRIP STATUS)
KILOWATT HOUR METER(COUNTER TYPE) PB2 HOOTER ACCEPT
KWH

U/V,O/V,P/S,PL COMBINED UNDER VOLTAGE,OVER VOLTAGE, PB3 FAULT RESET


PHASE SEQUENCE & PHASE LOSS RELAY
SW1 24V DC CONTROL SUPPLY ON/OFF
VSR VOLTAGE SENSING RELAY
CHANGE OVER SWITCH
ISOLATION TRANSFORMER
SW2
SW3
DG AUTO/TEST WITHOUT LOAD SELE,SWITCH
REMOTE DG START/STOP SEL.SWITCH
AEDBM Consultants Pvt.Ltd.
GSR GENERATOR SYNCHRONIZING RELAY AMF AUTO MAINS FAILURE 6-1-280/F,1st Floor,Above SBI,
V DIGITAL VOLT METER SOP STANDRAD OPERATING PROCEDURE Padmarao Nagar,Secunderabad - 500025.