0% found this document useful (0 votes)
12 views

DPS

The document details the specifications and components for a differential pressure indicating switch used in the ACW supply lines to coolers in a thermal power project. It includes applicable tags, service details, and a bill of materials with descriptions, sizes, and quantities for various components. Additionally, it outlines the responsibilities for supply and installation, along with notes on construction and fabrication approvals.

Uploaded by

chhandak bera
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
12 views

DPS

The document details the specifications and components for a differential pressure indicating switch used in the ACW supply lines to coolers in a thermal power project. It includes applicable tags, service details, and a bill of materials with descriptions, sizes, and quantities for various components. Additionally, it outlines the responsibilities for supply and installation, along with notes on construction and fabrication approvals.

Uploaded by

chhandak bera
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

DIFFERENTIAL PRESSURE INDICATING SWITCH

APPLICABLE TAG

SL NO. TAG NO. SERVICE PID NO.

1 P11PAB03CP200 High Differential Pressure across STRAINER


TCE.6428A-613-
in ACW supply line to coolers Unit#1
FD-1128

2 P21PAB03CP200 High Differential Pressure across STRAINER [SH 02 OF 03]


3 Valve Manifold
(Supplied with
in ACW supply line to coolers Unit#2
DP Switch)

HP LP
510 510

530A 530A
510 514
577A 577A 514
510 577A 522A
522A 1:
12 12
1: 577A

BOM

522A
522A
SR. ITEM DESCRIPTION SIZE MATERIAL UNIT TOTAL
522A 522A

NO NO QTY QTY

518A 518A
BY INST BY INST
CS as per IS 1239 4 8
1 530A HEX PLUG, 3000# 1/2" NPT(M)
Part 2
BY MECH BY MECH
530A 530A
FORGED EQUAL TEE CS as per
2 577A 1/2" NPT(F) 4 8
3000# IS 1239 Part 2

1/2" NPT(F), 1/2" NPT(F),


MANUAL GLOBE VALVE ASTM B62/ LTB-2
GLOBE VALVE GLOBE VALVE
3 518A 1/2" NPT(F) of IS 318/ A182 2 4
OF 800# RATING WITH
3000# END CONNECTION F316L

BOTH SIDE THREADED


1/2" NPT(M) CS as per
4 522A SEAMLESS NIPPLE 6 12
X 3" Long IS 1239 Part 1
HEAVY SCH 3" Long

1/2" O.D. X
5 514 SEAMLESS TUBE SS304 10 M 20 M
1.6mm THICK
UPSTREAM DOWNSTREAM
MALE CONNECTOR 1/2" NPT(M)
6 510 WITH DOUBLE 4 8
(SUITABLE
SS304, 3000#
COMPRESSION TYPE FOR 1/2"
FERRULES & NUT OD TUBE)

DO NOT SCALE
OWNER.

HEL HALDIA ENERGY LIMITED

NOTE: OWNER’S CONSULTANT.

LAHMEYER LAHMEYER INTERNATIONAL (INDIA) PVT. LTD.


INTERNATIONAL
1. INSTRUMENT WILL BE FREE SUPPLIED BY PLL. INDIA CONSULTING ENGINEERS, GURGAON, INDIA

BOP CONTRACTOR.
2. 3-WAY VALVE MANIFOLD (1/2 "NPTF) WILL PUNJ LLOYD LIMITED
BE SUPPLIED ALONG WITH THE INSTRUMENT. GURGAON

BOP CONTRACTOR’S CONSULTANT.

TATA CONSULTING ENGINEERS LIMITED


KOLKATA

PROJECT.
FOR R0 ISSUE ONLY CLEARED
ISSUE REVISIONS DRN APPD DATE FILE NAME :
2 x 300 MW COAL BASED THERMAL
CLEARED CHEM CIVIL ELEC I&C MECH POWER PROJECT AT HALDIA
DEPT SIGNATURE DATE R1 REVISED AS PER CLIENT’S COMMENTS AB SN SB 18-10-2012 ‘P’ (PRELIMINARY) ISSUES ARE NOT TO BE
APPROVED BY
USED FOR CONSTRUCTION / FABRICATION TITLE
BUT ARE ISSUED FOR LIMITED PURPOSES SCALE:NTS
CHEM SB
-- ONLY AS INDICATED IN THE SMALL BLOCK
AT THE TOP RIGHT HAND CORNER OF
HOOK-UP FOR DIFF. PRESS. INDCATING SWITCH
THE TITLE BLOCK. OFFICE-DISC: PROJECT MANAGER
CIVIL -- CONSTRUCTION / FABRICATION WORK IS (ACW SERVICE)
PERMITTED ON ‘R’ (RELEASED) ISSUES DK-IC SB
ONLY.
ELEC -- INFORMATION CONTAINED WITHIN ’HOLD’
DATE (R0 ISSUE)
IS NOT RELEASED FOR CONSTRUCTION / SHEET DRAWING NO. REV.
FABRICATION. FIELD MUST GET
DRN:AB 16-08-2012
I&C SUJAY NANDI 16-08-2012 DESIGN OFFICE TO CLEAR ’HOLDS’ IN
TIME BEFORE PROCEEDING WITH ANY DATE(CURRENT ISSUE)
MECH --
CONSTRUCTION / FABRICATION WORK
RELATED TO ‘HOLDS’.
CHD:SN
18-10-2012
19 OF 33 TCE.6428A-IC-613-IN-1701 R1

SIZE-A3