Product data sheet
Specifications
Arc Fault Detection Circuit Breaker,
Acti9, iDPN N VigiARC C 20A
6000A 30mA Type A 20A
A9T26620
Main
Range Acti9
product name Acti9 iDPN N VigiARC
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product or component type Arc fault detection RCBO
Product specific application Arc fault detection
Standards EN/IEC 62606
AS/NZS 61009.1
Device short name iDPN N VigiARC
Poles description 1P + N
Number of protected poles 1
Curve code C
Breaking capacity 6000 A at 240 V AC 50 Hz conforming to AS/NZS 61009.1
Rated breaking and making Idm 500 A at 240 V AC 50 Hz conforming to AS/NZS 61009.1
capacity
Neutral position Left
network type AC
Earth-leakage protection time Instantaneous
delay
Earth-leakage protection class Class A
Suitability for isolation Yes
Residual current tripping Voltage dependent
technology
Trip unit technology Thermal-magnetic
Earth-leakage protection Integrated
Complementary
[In] rated current 20 A
Network frequency 50 Hz
[Ue] rated operational voltage 230/240 V AC 50 Hz conforming to AS/NZS 61009.1
230/240 V AC 50 Hz conforming to IEC 62606
Device location in system Outgoer
Magnetic tripping limit 5...10 x In
Limitation class 3 conforming to AS/NZS 61009.1
[Ui] rated insulation voltage 250 V AC 50 Hz between phase and neutral
400 V AC 50 Hz between phases
Threshold tripping voltage 275 V for +/- 5 V
11/02/2025 1
[Uimp] rated impulse withstand 4 kV conforming to AS/NZS 61009.1
voltage
Contact position indicator Yes
Control type Toggle
Local signalling ON, OFF, fault trip
Mounting mode Clip-on
Mounting support DIN rail
Colour White
Mechanical durability 20000 cycles
Electrical durability 20000 cycles 240 V AC 50 Hz conforming to AS/NZS 61009.1
overvoltage category III
Locking options description Padlocking device
cable entry Top and bottom
Connections - terminals Tunnel type terminal for 2 cable(s) 2.5 mm² rigid
Tunnel type terminal for 1 cable(s) 16 mm² rigid
Tunnel type terminal for 2 cable(s) 2.5 mm² flexible
Tunnel type terminal for 1 cable(s) 10 mm² flexible
Wire stripping length 14 mm
Tightening torque 2 N.m
Comb busbar and distribution YES
block compatibility
9 mm pitches 4
Height 91 mm
Width 36 mm
Depth 75 mm
Product weight 205 g
Environment
Heat dissipation 4.62 W at 240 V - 20 A
IP degree of protection IP20 conforming to IEC 60529
Pollution degree 2 conforming to AS/NZS 61009.1
2 conforming to IEC 62606
Tropicalisation Severity B conforming to IEC 60068-2-30 for 28 d
Relative humidity 95 % at 55 °C
Operating altitude 2000 m
Ambient air temperature for -25…60 °C
operation
Ambient air temperature for -40…80 °C
storage
Quality labels RCM
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 7.5 cm
Package 1 Width 3.6 cm
2 11/02/2025
Package 1 Length 9.1 cm
Package 1 Weight 237.0 g
Contractual warranty
Warranty 24 months
11/02/2025 3
Environmental Data
Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity
via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.
Environmental Data explained
How we assess product sustainability
Environmental footprint
Environmental Disclosure Product Environmental Profile
Use Better
Materials and Substances
Packaging made with recycled cardboard No
Packaging without single use plastic No
EU RoHS Directive Compliant with Exemptions
SCIP Number B078722f-7853-4e1e-a05b-29638f57b0ab
REACh Regulation REACh Declaration
China RoHS Regulation China RoHS declaration
PVC free No
Use Again
Repack and remanufacture
Circularity Profile End of Life Information
Take-back No
4 11/02/2025