Fire Pump Head Calculations

This document outlines the fire pump head calculation for a project, detailing abbreviations, parameters, static head, residual pressure, friction loss in pipes, and fittings. The calculations indicate a total head requirement of 264.26 ft (80.55 m) or 120 Psi for the fire pump. The document is structured into two sheets, providing a comprehensive overview of the necessary calculations and values.

Uploaded by

shaik.jakeer
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
61 views3 pages

Fire Pump Head Calculations

This document outlines the fire pump head calculation for a project, detailing abbreviations, parameters, static head, residual pressure, friction loss in pipes, and fittings. The calculations indicate a total head requirement of 264.26 ft (80.55 m) or 120 Psi for the fire pump. The document is structured into two sheets, providing a comprehensive overview of the necessary calculations and values.

Uploaded by

shaik.jakeer
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 3

Design calculation sheet

Project no: Date: 20-09-07 Sheet No. 1 of 2 Computed by: ASF


Subject: Fire pump Head Calculation Checked by:
Approved by:

1- Abbreviations:
Hs = Static Head (m)
Hr = Residual Head (m)
HL = Friction Loss Head (m)
Q = Flow rate (gpm)
C = Hazen-Williams C value
d = Diameter of pipe (inches)
P = Frictional resistance (psi /ft of pipe)

2- Parameters:
Q1 = 1250 gpm
Q2 = 750 gpm
Q3 = 500 gpm
d1 = 8 inch
d2 = 6 inch
d3 = 6 inch
L1 = 50 m
= 164.04 ft
L2 = 90 m
= 295.28 ft
L3 = 100 m
= 328.08 ft
C = 120 (see NFPA13 - Table 22.4.4.7)
P = 4.52 * (Q) /C
1.85 1.85
*d 4.87
(see NFPA13 - Enc# 22.4.2.1.1)
3- Static Head:
Hs = 0 m
= 0.00 ft

4- Residual Pressure:
Hr = 6.9 bar
= 230.86 ft

5- Friction Loss Head:


1- Friction Loss in Pipes:
P1 = 0.01380 Psi/ ft
P2 = 0.02177 Psi/ ft
P3 = 0.01028 Psi/ ft

HL1 = 2.26383 Psi


HL2 = 6.42906 Psi
HL3 = 3.37393 Psi

HLT = 12.07 Psi


= 0.8320071 bar
= 27.84 ft
Design calculation sheet
Project no: Date: 20-09-07 Sheet No. 2 of 2 Computed by: ASF
Subject: Fire pump Head Calculation Checked by:
Approved by:

2- Friction Loss in Fittings and valves:

HLF = 5.57 ft (20% of pipes)

6- Head of fire pump:

H = Hs + Hr + HLF + HLP
= 264.26 ft
= 80.55 m
= 7.90 bar
= 114.55 Psi

H= 120 Psi