0% found this document useful (0 votes)
71 views4 pages

Goodman CKL60

The CKL Series split system air conditioner operates at 60 Hz with a capacity range of 19,000 to 60,000 BTU/h and a SEER rating of 10. It features a durable design with a louvered metal guard, quiet operation, and various standard and accessory options for enhanced performance. The specifications include detailed electrical data, dimensions, and performance ratings for different models within the series.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
71 views4 pages

Goodman CKL60

The CKL Series split system air conditioner operates at 60 Hz with a capacity range of 19,000 to 60,000 BTU/h and a SEER rating of 10. It features a durable design with a louvered metal guard, quiet operation, and various standard and accessory options for enhanced performance. The specifications include detailed electrical data, dimensions, and performance ratings for different models within the series.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

PRODUCT SPECIFICATIONS

CKL SERIES
60 HZ
SPLIT SYSTEM
AIR CONDITIONER
10 SEER

NOMINAL CAPACITY:
19,000 TO 60,000 BTU/H

1½ TO 5 TON

The CKL split system air conditioner features an attractive louvered metal guard that protects the
coil from damage and strengthens the unit. Designed for ground-level or roof-top mount application,
the raised base pan elevates the unit above the slab for excellent water drainage.

Standard Features Cabinet Features


• Quiet operating top discharge • Unique Goodman® sound control design
• Copper tube/aluminum fin coil • Heavy-gauge, galvanized-steel cabinet properly
• Totally enclosed and permanently lubricated reinforced and braced
condenser motor • Steel louver coil guard
• Factory-installed liquid line filter dryer • Attractive architectural gray powder-paint finish
• Brass suction and liquid service valve with with 500-hour salt spray approval
sweat connections • Removable access panels
• Hermetically sealed compressor with internal Accessories
high-pressure relief • Standard room thermostat with 1-stage cool/
• Fully charged for 15’ of tubing length 1-stage heat (CHT18-60 or CHSATG)
• Contactor with lug connections • Digital room thermostat with 1-stage cool/
• Ground lug connection 1-stage heat (CH70TG)
• Tested for efficiency and performance under • Cooling-only room thermostat (CT18-60)
ARI Standards • Outdoor Thermostat (OT18-60)
• Low Ambient Kit (LA-01)

SS-GCKL60 www.goodmanmfg.com 10/06


Supersedes 8/06
PRODUCT SPECIFICATIONS
NOMENCLATURE

C KL 036 1 A

Category Revision
C = Split Systems

Electrical
Unit Type 1 = 208/230 V, 1 Phase, 60 Hz
E = Commercial Air Conditioner 2 = 220/240 V, 1 Phase, 50 Hz
K = Air Conditioner 3 = 208/230 V, 3 Phase, 60 Hz
P = Heat Pump 4 = 380/415 V, 3 Phase, 50 Hz

Nominal BTU/h
018 = 1.5 tons 048 = 4 tons
024 = 2 tons 060 = 5 tons
030 = 2.5 tons 070 = 5 tons
036 = 3 tons 090 = 7.5 tons
042 = 3.5 tons 120 = 10 tons

PERFORMANCE RATINGS
Cooling Capacity (BTU/h)
Model # Coil / Air Handler dBs
Total Sensible SEER¹ EER² kWI³
ARUF17291** 19,000 14,500 10.5 9.8 1.94 76
CKL18-1*
CA*F1824*6* 19,400 14,800 10.5 9.8 1.98 76
ARUF17291** 24,800 16,600 10.0 9.5 2.60 78
CKL24-1*
CA*F1824*6* 25,000 16,800 10.0 9.5 2.63 78
ARUF17291** 29,000 21,200 10.0 9.5 3.05 78
CKL30-1*
CA*F1824*6* 29,600 21,600 10.0 9.5 3.11 78
ARUF30301** 36,000 27,800 10.0 9.5 3.79 78
CKL36-1*
CA*F3030*6* 35,000 27,200 10.0 9.5 3.68 78
ARUF36421** 42,000 32,600 10.0 9.5 4.42 80
CKL42-1*
CA*F3642*6* 42,000 32,600 10.0 9.5 4.43 80
ARUF48601** 46,000 34,000 10.0 9.2 5.00 80
CKL49-1*
CA*F3642*6* 45,000 33,600 10.0 9.2 4.89 80
ARUF48601** 46,000 34,000 10.0 9.5 4.84 80
CKL49-3*
CA*F4860*6* 46,000 34,000 10.0 9.5 4.84 80
ARUF48601** 57,000 43,000 10.0 9.0 6.33 80
CKL60-1*
CA*F4860*6* 57,000 43,000 10.0 9.0 6.33 80
ARUF48601** 57,000 43,000 10.0 9.0 6.33 80
CKL60-3*
CA*F4860*6* 57,000 43,000 10.0 9.0 6.33 80
¹ Seasonal Energy Efficiency Ratio
² Energy Efficiency Ratio @ 80°F / 67°F / 95°F
³ kWI = Compressor + Indoor Blower + Outdoor Fan Watts
Note:
• When mix-matching outdoor and indoor units, the indoor unit check flowrator must match the outdoor unit size.

2 SS-GCKL60
PRODUCT SPECIFICATIONS
SPECIFICATIONS
CKL18-1 CKL24-1 CKL30-1 CKL36-1 CKL42-1 CKL49-1 CKL49-3 CKL60-1 CKL60-3

Capacities
Nominal Cooling (BTU/h) 19,000 24,800 29,600 36,000 42,000 46,000 46,000 57,000 57,000
SEER¹ 10.5 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0
EER² 10.5 9.5 9.5 9.5 9.5 9.5 9.5 9.0 9.0
Decibels 76 78 78 78 78 80 80 80 80
Compressor
RLA 8.6 9.8 13.7 14.4 17.0 18.2 12.5 17.9 7.4
LRA 49 56 75 82 105 102 61 97.4 50
Condenser Fan Motor
Horsepower 1/6 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4
FLA 1.1 1.5 1.5 1.5 1.5 1.5 0.9 0.9 0.8
Outdoor Nominal CFM 2,000 2,200 2,200 2,200 2,200 2,800 2,800 3,000 3,000
Rows Deep/ Fins per Inch 1/19 1/19 1/19 1/19 1/19 1/19 1/19 1/19 1/19
Fin Type Rippled
Coil No. of Tubes 22 22 22 22 22 22 22 24 24
Coil Tube Diameter (in.) 0.375 0.375 0.375 0.375 0.375 0.375 0.375 0.375 0.375
Refrigeration System
Liquid Valve Size (“O.D.) 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Suction Valve Size (“O.D.) 3/4 3/4 3/4 3/4 7/8 7/8 7/8 7/8 7/8
Valve Type Sweat
Refrigerant Charge 106 107 101 112 120 124 88 89 113
Shipped with Orifice Size 0.052 0.059 0.065 0.071 0.076 0.080 0.080 0.093 0.093
Electrical Data
Voltage-Phase 208/230-1
Min. Circuit Ampacity ³ 11.9 13.8 18.7 19.5 22.8 24.3 16.6 23.3 10
Max. Overcurrent Protection 4
20 amps 20 amps 30 amps 30 amps 35 amps 40 amps 25 amps 40 amps 15 amps
Min / Max Volts 197/253
Power Supply Conduit Size 1/2 or 3/4
Ship Weight (lbs) 175 176 179 179 184 211 211 231 231
¹ Seasonal Energy Efficiency Ratio
² Energy Efficiency Ratio
³ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
Notes:
Must use time-delay fuses or HACR-type circuit breakers of the same size as noted.
Always check the S&R plate for electrical data on the unit being installed.

SS-GCKL60 3
PRODUCT SPECIFICATIONS
DIMENSIONS

Model Width Depth Height


CKL18-1* 26” 26” 29¾”
CKL24-1* 26” 26” 29¾”
CKL30-1* 26” 26” 29¾”
CKL36-1* 26” 26” 29¾”
CKL42-1* 26” 26” 29¾”
CKL49-1* 29” 29” 29¾”
CKL49-3* 29” 29” 29¾”
CKL60-1* 29” 29” 32¼”
CKL60-3* 29” 29” 32¼”

QUALITY MAKES THE DIFFERENCE!


All of our systems are designed and manufactured with the same high-quality standards, regardless of size or efficiency. We have designed these units to significantly
reduce the most frequent causes of product failure. They are simple to service and forgiving to operate. We use quality materials and components. Finally, every unit
is run-tested before it leaves the factory. That’s why we know...there’s no better quality.
Visit our website at Goodman Manufacturing Company, L.P.
www.goodmanmfg.com for information on: 2550 North Loop West, Suite 400
Goodman Products • Customer Services • Parts Houston, Texas 77092 USA

Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specifications or designs without notice or without incurring obligations.
Copyright © 2003 Goodman Manufacturing Company, L.P. • Houston, Texas • Printed in the USA. • Goodman products are made proudly in the USA.

4 SS-GCKL60