PART 1 – GENERAL
1.1 DESCRIPTION
A. Provide fire detection and alarm system in accordance with the Contract Documents.
B. The fire detection and alarm system shall be a stand-alone system operating
independently of other control systems. It shall have an automatic dial-up feature to Local Fire
Station.
C. Related work specified in other divisions of these specifications:
1. Sprinkler water flow and tamper switches.
2. Magnetic door holders and electric door locking hardware.
3. Installation of fire alarm speaker and firefighter's phone jack in elevator
cabs.
4. Public Address Emergency Announcement
D. Movement of devices and equipment +3-5m away from location in the plan should not
incur additional cost or variation orders.
A. All work specified in this Section is subject to the provisions of Section 16001 –
General Provisions.
B. Refer to the following Sections of related work in connection with the Fire
Detection and Alarm System:
Section 16490 - Fire Barrier
Section 16112 - Raceways
Section 16170 - Grounding
Section 17726 - Background Music (BGM) and Public Address (PA) System
1.4 STANDARDS
1.5 ABBREVIATIONS
1.6 SUBMITTALS
A. Wiring shall be inspected and tested for continuity and short circuits. The minimum
allowable insulation resistance between any two conductors or between conductors and
ground is ten mega-ohms measured with a 500 volt megger.
B. Field Test Reports:
1.8 IDENTIFICATION
H. The main control panel will consist of a central processing unit, printer and colour LCD
unit annunciator with a complete graphics package identifying all fire zone status.
I. The printer shall be as an event and status printer, it shall be laserjet type with a
minimum speed of 200 characters per second at 10 characters per inch.
1.10 SYSTEM ZONING (TO BE FURTHER COORDINATED WITH THE FIRE AND LIFE SAFETY
CONSULTANT)
Damper switches each with open close and auto functions as well as positive indication shall be
provided at each floor and are to be provided at the main control panel.
1.11 TRAINING
A. The Contractor shall provide appropriate training for the operation and maintenance of the fire
detection and alarm system, in accordance with the requirements of Section 16001.
PART 2 – PRODUCT
A. Provide sufficient battery (NiCd) capacity to operate the entire system upon loss of
power under maximum normal load for a minimum period of 24 hours with a minimum
of 5 minutes of alarm operation at the end of this period.
B. The system shall automatically transfer to the standby batteries upon power failure.
Battery charging and recharging shall be automatic.
A. Solid state, microprocessor based, modular design, fully supervised and intelligent
addressable. Steel enclosure in standard finish, with hinged, locking door. Integral
power supply, standby batteries, and battery charger.
B. Provide power on LED, power failure LED, system trouble LED, system reset switch,
alarm silence switch, trouble silence switch, manual evacuation switch, alarm
acknowledge switch, trouble acknowledge switch, supervisory service acknowledge
switch, lamp test button, tone alert, battery supervision LED, auxiliary relays, and other
system indicators and controls necessary for processing alarm and signaling functions.
Indicating lamps shall be LED type.
C. Provide appropriate permanent identification labeling of control and indicating
functions.
D. Annunciation:
Serial annunciator with back lit, alphanumeric, 80 character liquid crystal display indicating
clear language information as to the type of alarm (device type), point status (alarm or trouble),
number of alarms on the system, and a custom location label. Ability to scroll back through prior system
actions.
E. System shall utilize analog type smoke detection with alarm verification, self test
feature, individual sensor automatic timed sensitivity adjustment, individual smoke
sensor field adjustable sensitivity set from FACP, and automatic maintenance alarm
feature.
F. With Lon Bus or Lon Works interface.
A. General:
1. Intelligent Addressable type.
2. Provide auxiliary relays where required to satisfy system operational
requirements.
3. Smoke detectors shall be intelligent analog type.
B. Manual Pull Stations:
1. Furnish and install where indicated on plan.
2. All manual pull station shall be single action non-coded break glass type.
3. Manual station shall be constructed of Red Lexan or Die Cast Metal with clearly
visible operating instruction.
4. Station shall be suitable for surface mounting on matching back box.
5. Pulling the alarm handle shall activate the toggle switch which shall cause the
station n alarm position.
6. Push button type manual station shall not be acceptable.
C. Smoke Detectors:
1. Photoelectric smoke detector:
a. LED light source, silicon photodiode receiving element. Line filter and
time delay circuitry to prevent transient false alarms.
b. 360o smoke entry, locking tamper screw, pulsating on power LED
indicator, UL 268.
c. Adjustable obscuration/smoke detection levels.
d. Provides maintenance identification alarm.
e. Provides two LED function/working indication.
D. Device Monitoring Module
1. The device monitoring module shall permit the use of conventional detecting
devices including sprinkler flow switches and supervisory switches on the
addressable system. The module can be mounted together in the fire alarm
cabinet or be in the standard outlet boxes located near the device being
monitored.
E. Control Module
1. Interfaces a controlled device to the addressable system. This enables the fire
alarm panel to direct an instruction only to the intended device by addressing
to its control module.
F. Sounder (Horn) - Strobes
1. Fire lights shall be a xenon-strobe type or equivalent. It shall be low-voltage
(24 VDC).
• The maximum pulse duration shall be 2/10ths of one second (0.2
second with a maximum duty cycle of 40%). A pulse duration is defined
as the time interval between initial and final points of 10% of maximum
signal.
• The intensity shall be minimum of 75 candela.
• The flash rate shall be minimum of 1 Hz and a maximum of 3 Hz.
2. The color shall be clear or nominal white (i.e. unfiltered or clear filtered white
light).
3. Electric, utilizing solid state electronic technology operating on a nominal 24
VDC, with a nominal rating of 82 dBA at 3m.