Smart Junction Box
Smart Junction Box
February 2025
Eliminate I/O home run cables SJBs are factory tested products and ready for installation
in the field. Electronic Marshalling eliminates traditional
Significantly reduce SJB design engineering I/O design tasks and allows field wiring to start long before
control strategies are finalized.
Fully documented package
The SJBs are designed for safe or hazardous areas and
harsh environments, from extreme temperatures to
corrosive gases.
DeltaV SIS CTO Smart Junction Box February 2025
Eliminate I/O Home Run Cables: Field instrumentation For different environmental requirements:
wiring is reduced to the signal pair that connects the field Safe Area or Hazardous Area.
device to the SJB. Save on home run multi-core cables, cable European electrical codes/regulations.
trays, associated engineering, and documentations.
Each base model is further explained in the
Significantly Reduce SJB Design Engineering: coming sections.
The SJBs are pre-engineered, and factory tested. The I/O
flexibility allows the same design to serve a wide variety of Configurable options include the type of LS CHARMS
I/O signals, conditioned individually by the CHARM. Field (I.S. or non I.S.), network (Fiberoptic or Copper), enclosure
wiring design is complete at the terminal block. Material (SS304/SS316), cable entry, nameplate engraving,
injected power, heater, etc.
Fully Documented Package: Each SJB is supplied with
full documentation and engineering drawings showing
System Planning
internal lay-out, bill of materials, and internal wiring. They
are designed to meet local building code and industry Electronic Marshalling changes the game with respect to
best practices in order to deliver proven functionality with safety system I/O planning. The field I/O wiring can be
minimal costs. designed independently from the safety strategy design,
allowing engineers to determine the number and type of
The designs have considered specific requirements related Plan the power distribution and install the enclosures.
to outdoor installation in the field, including environmental Wire the field devices and commission them.
protection, heat dissipation, power and grounding
When control strategies and associated controller
requirements, and installation in hazardous areas.
hardware is finalized, simply assign the I/O signals to
All components are prewired and tested at the factory. the controllers as needed, no wiring changes. You can
Simply select the required DeltaV SIS Electronic Marshalling change controller I/O assignments with the click of a
equipment and the enclosure is ready to install, connect mouse, without touching a wired connection.
the field wiring, power, and network cables. Install needed
LS CHARMs to commission your loops and autosense the
hardware into your DeltaV SIS system.
www.emerson.com/deltav 2
DeltaV SIS CTO Smart Junction Box February 2025
DeltaV CTO SIS Smart Junction Box (SJB) Enclosure Material: Stainless Steel SS304 or SS316L.
Stainless steel provides protection for corrosive
All LS CHARM SJBs come with the following
environments (category NEMA 4X). SS316L provides
equipment installed:
superior corrosive protection and is typically applied in
AC power feeds with redundant AC/DC 24V DC bulk offshore applications (salt resistant).
power supplies. Pre-drilled bottom entry with cable glands for I/O, power,
Power distribution and isolation components for primary communications, and grounding cables.
and secondary 24V DC Power to LS CHARM I/O Cards. With standard drill pattern (with stop plugs) or cable
Halogen-Free Cable ducts. transit system with flexible cable gland blocks that are
installed in a cable entry frame.
Grounding bars for CG (Chassis Ground) and
DC Reference Ground. Name plate engraved with custom supplied cabinet
identification information.
Name Plate.
24V DC Power Distribution for Injected Power or
Removable Gland Plate (3mm thick).
4-wire Transmitter Power: 8 fused circuits, pre-wired to
SJBs designed for bottom entry for all cables all Non-IS base plates. (This option includes a redundancy
(power, network, and I/O signals). diode to bring primary and secondary power feeds to a
common injected power distribution).
The CTO CHARM SJBs support all available low voltage
CHARM I/O types with 24V DC bussed field power and all Heaters for extreme low temperature installations &
available CHARM terminal blocks. condensation management
CSLS I/O Cards, and LS CHARMs are not included and are Blue marking for Field Cable ducts for IS signals
to be ordered separately.
Breather: SS316L
Type of Non-IS Baseplate assembly – Can be selected upfront design and certification effort.
with 4 different types of CHARM terminals
The following sections provide a more detailed specification
No. of IS Baseplates – Can be selected from 0 to 8 for the SJBs and available options.
www.emerson.com/deltav 3
DeltaV SIS CTO Smart Junction Box February 2025
Overview of DeltaV CTO SIS Smart Junction Boxes (SJB) – Base Models
Power Permitted
No. of LS
CTO Base Model No. Description Requirements Location /
CHARM I/Os
(Prim and Sec) World Area
The CTO CSLS base model reference for Smart Junction Boxes uses the following naming convention: EU-FE-96-XX-CSLS-ZZ, where:
EU = Europe Design Standards and Regulations
FE = Field Enclosure (Smart Junction Box)
96 = Maximum I/O’s count in this CTO model
XX = Incoming Power, AC: 220 to 240V AC / 100 to 120V AC
CSLS = CHARM Smart Logic Solver
ZZ = SA: for use in Safe Area, HA: for use in Hazardous Area (ATEX/IECEx, Zone 2)
www.emerson.com/deltav 4
DeltaV SIS CTO Smart Junction Box February 2025
EU-FE-96-AC-CSLS-HA
EU-FE-96-AC-CSLS-SA
Default option setting
o Configure to option setting SJB Base Model
(Different from Default)
NA Option setting not possible
for SJB Base Model
Certification A 1 ATEX/IECEx NA
1 -20°C to +50°C NA
1 220 to 240V AC
Input Voltage E
2 100 to 120V AC o NA
1 Feedthrough Terminals
Incoming Power Landing F
2 Disconnect Switches o NA
1 Eaton 1
NA
MCB Make G
2 Appleton o
1 No
Heaters H 2 Single Heater (for condensation) o o
3 Two Heaters7 o NA
1 No
Enclosure Light K
2 Yes 2 o o
1 No
Enclosure Fan L
2 Yes 8 o o
www.emerson.com/deltav 5
DeltaV SIS CTO Smart Junction Box February 2025
LEGENDS:
EU-FE-96-AC-CSLS-HA
EU-FE-96-AC-CSLS-SA
Default option setting
o Configure to option setting SJB Base Model
(Different from Default)
NA Option setting not possible
for SJB Base Model
5 Copper Ethernet o o
1 No3 NA
Door Opening Alarm O
2 Yes o
1 No
CHARMS I/O Gateway Assembly P
2 Yes o o
1. Eaton MCB is rated for -20°C at lower side, hence it is disabled for selection for ambient temperature range of -40°C to +50°C.
2. For ATEX/IECEx certified SJB, when ”Enclosure Light” option is selected, it will be provided with “Door Switch”. Light will be operated through the door switch.
3. Door Opening Alarm will be available by default for ATEX/IECEx certified SJB, when “Enclosure Light” option is selected.
4. Selection of required CHARM Baseplate (CBP) quantity and type is possible. The Max. CBP quantity is dependent on:
Ambient Temperature selection
24VDC for injected power or 4-wire transmitters
External 12 LS CHARM I/O Junction BOX 24VDC Supply (Consumes space for 2 CBP)
CHARMS I/O Gateway Assembly (Consumes space for 1 CBP)
5. Min. 1 CBP (IS / Non-IS) selection is mandatory for connecting SJB alarms to the CHARMs on 1st CBP.
6. In case of all Non-IS CBP or IS/Non-IS mix CBP selection, Non-IS type CHARMs will be selected for alarm connection. When all IS CBPs are selected,
IS CHARMs will be selected for alarm connection. Total installable CHARMs qty. in SJB will be reduced by 2 as 2 CHARMs are required for alarm connection of
that SJB.
7. Two heater option is applicable for ambient temperature range of -20°C to 50°C and -40°C to 50°C only.
8. Enclosure fan option is default “Yes” for ambient selection of “-20°C to +55°C”.
www.emerson.com/deltav 6
DeltaV SIS CTO Smart Junction Box February 2025
www.emerson.com/deltav 7
DeltaV SIS CTO Smart Junction Box February 2025
CHARM Baseplate Flexibility The selection is available for Non-IS CHARM Baseplates with 4 different types of
CHARM Terminals blocks.
Even is case of 55°C ambient temperature Injected power to the CHARM Baseplate
option is available with the restriction on no. of Non-IS CHARM baseplates.
Mix of Non-IS and IS CHARM Baseplates in a same column is possible.
(Non-IS CHARM Baseplates followed by IS CHARM Baseplates)
CHARMS I/O Gateway Assembly The selection is available for LS CHARM I/O Gateway Assembly with 2 different types of
networking topologies (Star / Ring).
Supply Includes Mounting plate, Halogen-Free wire ducts, external wall mounting brackets,
door clamps, ground bars, external grounding bolt, drip edge, breather-drain.
(*) For available configurable options refer to respective base SJB model & option table.
(**) IP64 – with wing knob for padlock.
www.emerson.com/deltav 8
DeltaV SIS CTO Smart Junction Box February 2025
915mm (W) x 1220mm (H) x 475mm (D) (without lifting pads and mounting brackets)
EU-FE-96-AC-CSLS-HA
OR
EU-FE-96-AC-CSLS-SA
This SJB has possible options for system
Hardware assembly as below:
1 x CSLS Carrier with redundant Copper
Ethernet connectors
Max. 8 No. of Non-IS and IS CHARM Base
Plate as per user selection
1 X CHARMS I/O Gateway Assembly
24VDC Redundant Power distribution
for up to 7 External 12 LS CHARM
I/O Junction boxes
www.emerson.com/deltav 9
DeltaV SIS CTO Smart Junction Box February 2025
Design Considerations
EU-FE-96-AC-CSLS-HA
60°C*
EU-FE-96-AC-CSLS-SA
Caution: Operating any electronics at the higher end of its temperature range for long periods of time will shorten its
expected lifetime, see Effects of Heat and Airflow Inside an Enclosure White Paper for more information.
The CTO SJBs are configurable. The type of hardware configured and IO quantity which can be accommodated depends on
ambient temperature and acceptable internal temperature rise within SJB.
For each SJB, a heat and power calculation must be done to assess whether internal temperature rise is acceptable for the
IO quantity considered and configured options considered. Appropriate safety margin may be kept. A CTO Heat and Power
calculation Template is available to assist this.
www.emerson.com/deltav 10