vt10 manual-Vertex
vt10 manual-Vertex
1. INTRODUCTION
This manual contains information for the installation and operation and tuning of our Vertex VT10 series auto-tuning
microprocessor based controllers. These controllers carry a one-year factory warranty.
The VERTEX microprocessor controllers are “proportional + integral + derivative” (PID) controllers that come in a variety of
standard DIN sizes. The input is configurable and allows selection or configuration of inputs between T/C, RTD, 4~20 and
other linear signals and outputs between relay, SSR, heat / cool, 4~20 mA or other linear signals. They have dual displays
that show the input (measured temperature) in the top digital display and the required set point in the lower. The controller
boasts a comprehensive range of other features that include auto/manual function, ramp feature, and comes standard with
two configurable alarms, (The VT4810 48 x 48 size only has one alarm). The controllers can be switched to manual and can
work as “time based ratio out-put controllers” in the event of thermocouple or input failures taking place.
2. INSTALLATION
Cut-out sizes are shown below. Panel width may be up to 10 mm thick. Do not tighten the mounting screws too tightly since
this can bow the controller housing.
2. Sensor Input
Do not run sensor input cables adjacent to power carrying conductors. The correct type of thermocouple extension
lead wire or compensating cable must be used for thermocouples. Ensure that the polarity of the thermocouple /
4~20 input is correct. When using 4~20 mA inputs the loop has to be powered externally by a 24 Vdc switch mode
power supply. PT100 inputs require three copper core wires and can be run for up to 50 meters. You can simply
select any thermocouple types in the parameter setups. To select PT100 or analog (4~20) inputs requires simple
hardware changes such as de-soldering a link for PT100 etc. It is easier to simply order the controller with the
correct input type.
3. Control Output
Different types of outputs are available in the controller. Be sure that the correct output type is selected for your
application. Also ensure that the correct cycle time is used with the appropriate out-put type.
Relay 5A / 240 Vac maximum, resistive load
Pulsed voltage to drive SSR (24 Vdc)
4~20 mA or 0~20 mA, Maximum load 500 ohms
Various other linear outputs ( 1~5Vdc, 0~5Vdc, 0~10Vdc )
Changes of out-put types are relatively simple but must be done by the supplier.
2
4. Alarm Output
The alarm output is a relay contact. Maximum contact rating is 10 Amps resistive load. The VT4810 has only one
alarm, but all other models have two alarms.
Although the relay out-put is rated at 5 amps it is always necessary to switch an interposing
relay, SSR or Contactor that will switch the load. This avoids damage to the controller in the
event of a fault short developing on the power out-put circuit.
Always use a separate fused supply for the “power load circuit” and do not take this from the
live and neutral terminals supplying power to the controller.
STANDBY
On some versions of software fitted to the VT4910 controller a standby function is available.
Please check the software version of your controller to see whether this function is fitted.
When this function is part of the software, in order to operate fully, a link must be made
between terminals 6 & 7. This disables STANDBY mode.
Opening this link puts the controller into STANDBY mode. This disables the heat output
(including the setting of manual output power) and, on version 2.A, disables the alarms. This
feature is to enable the remote disabling of the controller by a switch or PLC.
C: Degree C LED
LED lights when programmed for degree C.
F: Degree F LED
LED lights when programmed for degree.
Scroll Key
When in one of the parameter levels, you can move from one parameter to the next by pressing the Scroll Key
once.
Also to activate an autotuning session, press and hold this key for 5 seconds.
Up Key
Increases the setpoint value and changes the parameter data when programming.
Down Key
Decreases the setpoint value and changes the parameter data when programming.
Return Key
When in one of the programming levels, press this key to return to the normal operating status.
Pressing and holding this key for 5 seconds puts the controller into manual operation.
Pressing the Return Key during normal operation, allows the user to view the controller output in percentage
(0~100%).
4. PARAMETER DEFINITIONS
Press and hold these keys together for 5 seconds to enter the next level of parameters.
1. SP Set-Point Variable
This parameter is the desired target for control. It can be adjusted up and down using the up/down keys when
the controller is in its normal state, within the range defined by the “Low Limit” value and “High Limit” value.
4
2. rRñP Ramp Rate 0.0~100.0 °C/min
The controller can be configured to act either as a fixed set-point controller or as a single ramp on power up controller.
This function enables the user to set a predetermined ramp rate to allow the process to gradually reach set-point
temperature thus producing a “soft start” function. This parameter is activated by selecting the appropriate parameter
lock level that will allow access to the rAnP function, ie: 1, 3, 5, 7 etc. The ramp function is also automatically engaged
when making set-point changes. This means that the controller will ramp the temperature from the current value to the
new set-point value in accordance with the ramp setting. The ramp rate is determined by “rRñP” parameter, which can
C/minute. The ramp function is disabled when the rRñP parameter is set to zero.
be set in the range 0.0 to 100.0
Note that if the LoLt is set above 0ºC the output will be governed by the failure mode selected in
EroP and will not ramp or control at all until the measured variable has exceeded the LoLt.
3. oPoF Output offset Value for Manual Reset 0~100 % of full scale
This is in essence a “manual reset” function. It can be used to alter the PV reading by introducing a fixed off-
set. This can be used to correct the relationship between the PV reading and the SV reading.
Under normal circumstances this should be set to “0”.
This sets the value at which alarm 2 will operate if “A1Fu” 0 or 5, 1 or 5, 2 or 6, 3 or 7 is selected for alarm
function.
This parameter sets the “time value” to be used in the “A1Fu” time based alarm function. (“A1Fu” set to 8, 9, 10
or 11).
This parameter is available only in the case that the “A1Fu” is set to timer function.
The range available is from 0 to 9999 minutes.
This value is the proportional band setting for the “cooling out-put” if that option is available on the controller.
It is set as a multiplication factor of the main out-put Pb value.
The default value is 1.0 which means that the C Pb value will equal the main Pb setting
C Pb = Pb x factor
This function sets the dead-band between the heating and cooling out-puts.
Setting range from -10.0% to 10.0% of Pb.
5
Permits the user to lock (prevent changes) for different levels as shown in the table below.
The levels can be adjusted wherever there is a
Other parameters can be locked using other means (see Item 5 below)
5. OPERATIONAL FEATURES
2. The function is unlocked by pressing the and keys together for 5 seconds.
3. Once this feature is unlocked, to change from auto to manual and back again, press the key for five
seconds.
4. Automatic Control
In auto mode, the controller automatically adjusts the output variable in accordance with the PID algorithm to
reach and maintain the desired set-point. Auto mode is the normal mode of operation. It is normally PID control
(depending on the parameters you select for the P, I, + D parameters)
5. Manual Control
Manual control allows the operator to control the out-put by forcing it up or down using the keys.
With a 4~20 mA out-put controller the out-put can be increased or decreased by manually adjusting it using the
up and down keys.
With a relay out-put controller, when in manual you are able to vary the relationship between the on and off times,
thereby adjusting the power fed to the load. This is measured in % of cycle time in seconds. So 40 % would
cause the load to be on for 40 % of the cycle time and off for 60%. (Cycle time for a relay out-put controller is
usually set at 15 seconds). This is a useful feature that can be used in the event of a T/C break to keep
production running.
5.2 AUTOTUNE
The auto-tune feature will work when it should depending on the “tune” parameter selected below.
This is normally set at “1” which means the controller requires an instruction to perform an auto-tune operation.
This is best as in most cases once the controller has been set up one does not wish to keep changing the
parameters.
To affect an auto-tune operation you need to allow the controller to reach the set-point and then press and hold
the scroll key for 5 seconds until the auto-tune dot in the right extreme of the PV display starts to flash.
The controller will then perform an auto-tune operation until the light stops flashing.
Normally this will be two or three cycles of control.
5.3 RAMP
The controller can be configured to act either as a fixed set-point controller or as a single ramp controller on power up.
This function enables the user to set a predetermined ramp rate to allow the process to gradually reach set-point
temperature thus producing a “soft start” function. This parameter is activated by selecting the appropriate parameter
lock level that will allow access to the rAnP function, ie: 1, 3, 5, 7 etc
The ramp function is also automatically engaged when making set-point changes. This means that the controller will
ramp the temperature from the current value to the new set-point value in accordance with the ramp setting. The ramp
8
rate is determined by “rRñP” parameter, which can be set in the range 0.0 to 100.0
C/minute. The ramp function is
disabled when the rRñP parameter is set to zero.
5.4 RAMP AND DWELL
A dwell timer is incorporated within the controller when used with certain alarm functions. Alarm 1 can be configured by
setting “A 1Fu” = 9 to provide a dwell function or a soak function to be used in conjunction with the ramp function. To
achieve this you must wire the contactor output through the alarm contact. After setting the “A 1Fu” = 9 you will find the
tiñE function activated in the user level. This is where you will set the soak time in minutes. On turning the controller
on the alarm contact will be on, allowing the controller to control the temperature. Once the SV = SP the timer will be
started. The alarm light will flash to indicate that the soak timer is running. At the end of the pre-set time, the alarm
relay will switch off and the output will be disabled. This time alarm function can be used without the ramp, simply to set
a soak time for the controller and then switch iot off. To deactivate the timer function temporarily just set the time to –1
minutes or remove the function from the “A 1Fu” settings.
It is not always necessary to use proportional control for cooling as often cooling is done with some type of refrigeration
equipment or fan, that cannot be turned on and off on a frequent basis. In this case you use the standard off the shelf
controller that comes complete with an alarm. By configuring the alarm as a deviation alarm “A Ifu=0” it links the
alarm to the set-point by a fixed deviation, and the alarm out-put can then be used for cooling. The alarm setting in level
1 then dictates the gap between the heating setpoint and the “alarm” cooling setpoint. The alarm also has its own
hysteresis setting thereby allowing you to set a band on the cooling set point (alarm setting) that will dictate how far the
temperature must drop before cooling (alarm) switches off again. This is the “A Ihy” setting. In addition to this since
the alarm is linked to the main set point as you change the set point the cooling parameters follow and do not need to be
readjusted each time. This method is often used for “fan” cooling on extrusion barrel heaters
An option is available in these controllers is a second proportional control output that can be used for cooling. This
means you will have PID control on the heating output, and proportional control on the cooling. Note: A second
proportional cooling output is not available on the 48 x 48 size. This type of proportional control can be used when you
have liquid cooling on a barrel, where you are switching a solenoid valve to control the cooling.
TABLE 2
The Alarm function can be locked by pressing the and keys for 5 seconds.
The Alarm function can be unlocked by pressing the and keys for 5 seconds.
Select the type of alarm function required from the table below. Use AISP to set values as required.
TABLE 1
A Ifu A 2Fu ALARM OPTION SETTINGS
0 or 4 0 or 4 Deviation Alarm High
Alarm output on when PV >(SV+A1SP)
1 or 5 1 or 5 Deviation Alarm Low
Alarm output on when PV <(SV+A1SP)
2 or 6 2 or 6 High Alarm
3 or 7 3 or 7 Low Alarm
8 - Timer Function
Timer on when PV=SV alarm on when timer off
9 - Timer Function
Alarm on when power on, off when timer OFF
10 - Timer Function
Alarm output ON when timer on
11 - Timer Function
Alarm On when power on, off when timer ON
12 or 14 - Band Alarm
13 or 15 - Band Alarm
7. SPECIFICATIONS
1. INPUT
Thermocouple J, K, T, E, B, R, S, N (IPTS68/DIN 43710)
RTD Pt100 ohms RTD (DIN 43760/BS 1904 or JIS)
Linear Voltage (Current) 0~20 mA and 4~20 mA
Range User configurable (To best suit application)
Accuracy ± 0.1% + 1 LSD
Cold Junction Compensation 0.1% (ambient typical)
Input Impedance 10M ohms for T/C, 100K ohms for Linear Voltage,
2.7 ohms for 4~20mA
Excitation Current for RTD 0.2mA Maximum
Sample Rate 250 mS
Common Mode Rejection 120 dB
Normal Mode Rejection 60dB
2. CONTROL
Proportional Band 0.0 ~ 100.0% (of full scale)
Integral (Reset) 0 ~ 3600 Seconds
Derivative (Rate) 0 ~ 3600 Seconds
Anti Rest Windup Inhibits integral action outside Proportion Band
Ramp Rate 0.0 ~ 100.0 °C/ minute
Dwell 0 ~ 9999 minutes
On-Off With adjustable hysteresis
Cycle Time 0 ~ 99 Seconds
10
Control Action Configurable for Direct (Cooling) or Reverse (Heating)
Alarm functions 16 configurable different functions available
3. OUTPUT
Relay 5A/240 VAC resistive
Pulsed Voltage SSR Isolated 24 VDC 100mA Maximum
Current 4~20 mA Isolated 0 (4)~20mA Maximum load 500 ohms
Alarm Relay out. Form A contact (SPST) 10A/240 VAC resistive
4. POWER
Rating 85 ~ 265 VAC 50/60 Hz
Consumption 5 VA maximum
5. ENVIRONMENTAL
Operating Temperature -10 ~ 55°C
Humidity 0 ~ 90%
Insulation 20M ohms minimum @ 500 VDC
EMC Emission EN 50081-1:1992, EN 55022:1994
EMC Immunity EN 50082-1:1992, IEC 801-2, IEC801-3, IEC 801-4:1988
Weight VT4810 -180g, VT9410, VT4910 & - 240g,
VT7210 - 230g