How To Find An Earth Fault On Board Ships
How To Find An Earth Fault On Board Ships
Ships?
Earth fault is considered very critical on board a ship. Some ships
which operate at 440 V do not have any trip devices attached for a
single earth fault. However when the operating voltage exceeds
3000V, it is mandatory to have a protection system which isolates
when a machinery suffers an earth fault.
When a 220V earth fault alarm sounds, as said earlier, the trueness
of the alarm is checked by pressing the test button and then
investigation can be started on each and every 220V circuit.
Alternate Idea: Instead of turning off breakers one by one for the
lighting circuit, I followed a method where I turned off all lighting
circuit of a particular doubted area. This method helps usually when
there are two or more earth faults in 220V lighting circuit. By turning
off all the breakers of a particular area, then switching on the
breaker one by one will eliminate multiple earth faults.
When I turned off lighting switches one by one, it was difficult for me
to identify multiple earth faults.
An insulated system is one that is completely electrically isolated from the earth
or in our case the hull of the vessel.
The supply neutral point is connected to earth in an earthed system and main
low voltage (LV) (440 V AC) systems are generally shielded from the ship’s hull.
Ashore, similar systems are earthed to the ground. To limit earth fault current,
high voltage systems (>1000 V) are normally earthed to the ship’s hull through
a neutral earthing resistor or a high impedance transformer.
Exam
ple of earth fault indication diagram
The key requirement on board ship is to keep the electrical supply to critical
equipment running in the case of a single earth fault, while ashore immediate
isolation of the faulty circuit is a priority and where this can be achieved by an
automatically earthed system.
In order to safeguard against the danger of electric shock or fire that may result
form an earth fault, the electrical systems must be earthed, through a conductor
which connects the metal enclosure to the ship’s hull. This will prevent to attain
a dangerous voltage with respect to earth, as such earth connection of
equipment ensures that it always remain 0 V.
Exam
ple of a grounded metallic enclosure
Onboard vessels, if a single earth fault occurs on the live line of an earthed
distribution system, this would be an equivalent to a short circuit fault across
the generator through vessel’s hull. The large earth fault current that would
result from this, would immediately cause the protective device to trip the faulty
circuit and that particular electrical circuit would be immediately isolated from
the supply . However, this would lead to loss of power that could create a
hazardous situation, especially on the essential equipment (steering gear,
emergency fire pump, emergency compressor etc.) and more than that, the
large fault current could cause arcing damage at the fault location.
Therefore, if a single earth fault occurs on the line of an insulated system will
not cause any protective equipment to operate and the system will continue to
normally operate with a single earth fault as it doesn’t provide a complete
circuit so no earth fault current will flow.
If the second earth fault occurs on another line in the insulated system, the two
earth fault together would be similar to a short circuit fault, via the ship’s hull,
and the resulting large current will operate the protection devices and cause
disconnection of the system involved, creating a risk for the ship’s safety if this
is an essential system.
Therefore, an insulated system requires two earth faults on two different lines to
cause an earth fault current. As opposite, an earthed system requires only one
earth fault on the line conductor to create an earth fault current which will trip
the faulty circuit.
For that reason, onboard vessels, an insulated system is more effective than an
earthed system in maintaining the essential services supply continuity.
The High Voltage (HV) systems onboard vessels are normally earthed via a
resistor connecting the generator neutrals to earth.
Each earthing resistor’s ohmic value is typically chosen to limit the maximum
earth fault current to no more than the generator’s full load current. Such a
Neutral Earthing Resistor (NER) is usually assembled from metallic plates.
When using an earthed HV system, a single earth fault causes current to flow in
the neutral connection wire, which is monitored by an earth fault relay, which
can activate an alarm and/or trip functions.
Certain critical loads (steering gear) can be supplied by a transformer with the
secondary unearthed to ensure supply security in the case of a single earth
failure.
SOLAS and Class regulations requires that tankers have only insulated
distribution systems as is intended to reduce the danger from earth fault
currents circulating in the hull within hazardous areas which may cause an
explosion of the flammable cargo. Exception by regulation is where tanker has a
3.3 kV earthed system which doesn’t extend forward of the engine room
bulkhead and into the hazardous area.
Regulations require that an earth fault monitor is fitted to the main switchboard
to indicate the presence of an earth fault on each isolated section of a
distribution system and can be either a set of indicator lamps or an instrument
to show the system insulation resistance value to earth.
Earth indication lamps have been the most common method used for many
years, being an inexpensive installation and easy to understand, but unable to
indicate the presence of high impedance earth fault.
The most simple and practical method is to open the circuit breakers feeding the
loads, one at a time, and by monitoring the the earth fault instrument while
observing which circuit breaker, when tripped, clears the earth fault. The earth
fault must be on that particular circuit.
The method of tracing the earth fault is essentially that of continuously breaking
down the circuit into smaller and smaller sections until is finally located.
In real life, circuits cannot be randomly disconnected, as some vital service may
be interrupted causing the important equipment or even main engine to stop. It
is advisable to do this when the vessel is in port or anchorage in safe waters.
Tracing and repairing the earth fault must be carefully coordinated with the
operational requirements of the vessel’s electrical services.
When located, the damaged insulation must be repaired and the method
depends upon the cause of the earth fault and this is determined by visual
examination.
If you like my posts, please don’t forget to press Like and Share. You can also
Subscribe to this blog and you will be informed every time when a new article is
published. Also you can buy me a coffee by donating to this website, so I will
have the fuel I need to keep producing great content! Thank you!
Ship Earth Fault Indicators
Working With simple
Diagram
Earth Fault Indicators
Ships 440V and 220V isolated system should have insulation indicators in order to
indicate the presence of earth fault in the system. Generally two types of earth fault
indicators are fitted onboard, Earth fault indication Lamps and An instrument showing
Insulation with respect to the earth (Ohm meter).
> Explain working principle of earth fault indication lamps with diagram
Short circuit