Tolerance Table
Tolerance Table
Table 1-Tolerances
Item Tolerance
2. Voltage ratlo al no load on principal tapping The lower of the (ollowing values:
for a specified first palr of windings a) +0.5 % of declared ratlo
b) +1/10 of the actual percentage impedance on Ihe
principal tapping
To be agreed, but not less than the lesser of the values
Voltage ratio on other tappings, same pair
in a) and b) above
To be agreed, but not less than the lesser of the values
Vollage ratio for further pairs
in a) and b) above
3. Short-circuit impedance for:
aseparate-winding translormer with two windings.
or
b) any other tapping of the pair When the impedance value is 210%
+10 % of the declared value
When the impedance value is <10 %
+15 % of the declared value
NOTE 1 The loss tolerances of multi-winding transformers apply to every pair of windings unless the guarantee
states thal they apply to a given load condition.
NOTE 2 For certain auto-transformers and booster transformers the smallness of their impedance justifies more
liberal
require tolerance. Transíormers On
special consideration. having
the large
other tapping ranges.
hand, for particularly
example, when aif transformer
the range is isasymmetrical. may with
to be combined also
previously existing unils, il may be justified to specify and agree on narrower impedance tolerances. Matters of
special tolerances shall be brought lo atention at the tender stage, and revised tolerances agreed upon between
manufacturer and purchaser.
NOTE3 'Declared value' should be understood as meaning the value declared by the manufacturer.