earhing-1
earhing-1
lOMoARcPSD|53169336
A Seminar Report
On
Bachelor of Engineering
In
ELECTRICAL ENGINEERING
Submitted by
DEVRAJ KUMAR
21103156021
Certified that the Seminar work entitled “Earthing and Grounding Techniques” carried out by Mr.
Devraj Kumar, Reg No: 21103156021 a bonafied student of GOVERNMENT ENGINEERING
COLLEGE, BHOJPUR in partial fulfillment for the award of Bachelor of Engineering in Electrical
Engineering of the BIHAR ENGINEERING UNIVERSITY, Patna. It is certified that all
corrections/suggestions indicated for Internal Assessment have been incorporated in the report deposited
in the departmental library. The seminar report has been approved as it satisfies the academic
requirements in respect of seminar work prescribed for the said Degree.
External Viva
Signature with Date
Name of Examiners
1.
2.
i
lOMoARcPSD|53169336
Place: ARA
Date:
Signature:
Name: Devraj Kumar
Reg No: 21103156021
lOMoARcPSD|53169336
lOMoARcPSD|53169336
ACKNOWLEDGEMENT
The satisfaction and euphoria that accomplishes the successful completion of any task would be
incomplete without the mention of the people who make it possible.
I am thankful to The Management of GOVERNMENT ENGINEERING COLLEGE, BHOJPUR,
for their continuous support and encouragement for carrying out the seminar work.
I would like to thank The Principal, Dr. CV Mahto, for the encouragement and valuable
suggestions.
I would like to express our sincere gratitude to The Controller of Examination, MVJCE,
Bengaluru, for persistent guidance.
I would like to thank Prof. Anshul Shekhar, Assistant Professor and HOD, Department of
Electrical Engineering, GEC Bhojpur, for being a constant support and providing all the facilities that
was needed in the seminar work.
I avail this opportunity to express profound sense of gratitude and thank to our guide. I would like
to thank Prof. Jeetendra, Assistant Professor, Department of Electrical Engineering, GEC Bhojpur,
for her wholehearted support, suggestions, and invaluable advice throughout Technical Seminar and
for the help in the preparation of this report.
I am in debt to the support of all the teaching and non-teaching members of Department of EE,
GEC Bhojpur, for their kind help and co-operation, throughout the seminar.
lOMoARcPSD|53169336
ABSTRACT
We can assume that working in electrical system is similar to that of work in war field.
Those who are involved in electrical job they should be alert for each and every
second. Mistake or failure will not be any of any excuse. Electricity is blunt and
rude.In present paper I would like to enlighten some important areas which need
special attention and also create awareness among the people who are working or
using electrical power systems.
iv
lOMoARcPSD|53169336
Index:
Sl. No Title Page No:
1. Certificate i
2. Declaration ii
3. Acknowledgement iii
4. iv
Abstract
5. Introduction 1
6. Literature survey 3
12. References 8
lOMoARcPSD|53169336
List of Figures
1. INTRODUCTION
Safety should be defined as reduction of risk to a level that is as low as reasonable and as
practicable. It is a state of mind and environment that must become an integral part of each working
procedure. This is what we mean by built-in or integrated safety and permanently effective.
Electrical safety is more important, because we could not apparently realize that, what amount of
current a simple cable or a bare conductor carrying or at a glance we could not ascertain whether a
conductor is live or dead. This harmless appearance could misguide us. And this is the root cause of
most of electrical accident. Risk is chance of something happening that will have an impact and
could be counted by its consequence and likelihood.
Accident is an unexpected event causing loss of life or bodily injury and loss of property.
Accident is an unplanned event which hampers the process of production and adds miseries.
Accidents occur either due to unsafe act or unsafe action of work or both.
Safety Precaution means to strictly follow the prescribed rules for safety of self, working
personnel and tools to conduct electrical work, otherwise possibility of electric shock or hazards
could be experienced. Safety of an electrical installation could be ensured by proper insulation,
good earthing system and adopting adequate protection and control systems.
2. literature survey
1
lOMoARcPSD|53169336
2
lOMoARcPSD|53169336
Neutral Earthing In neutral earth, the system conductor neutral is directly connected to
the earth using a metal conductor wire. Neutral grounding is also known as system grounding.
This type of grounding is mainly provided to the star winding system. For example, generators,
transformers, motors, etc
3
lOMoARcPSD|53169336
4
lOMoARcPSD|53169336
Often we have seen people touching electrical cables and charges with wet
hands. Like, it happens quite a lot that at one moment you are doing the dishes
and suddenly you remember that you have to put your phone on charge and
during that you just forget that drying your hands is important before reaching
for the socket.
Never Use Broken Equipment
As said earlier, our charger cables are often broken, and we don’t even find it
necessary to fix it or get a new one. Now, this is again one big mistake, and the
wiser thing to do is to never deal with frayed cords, broken plugs, and damaged
insulations
Always Turn Off The Mains First
Never, we repeat, never make the mistake of leaving your mains on. We’ve heard of
some terrible incidents just because people forgot to turn off their mains. Also, make
sure that before plugging anything in the socket, turn it off first, then put the charger
inside and then turn it on. This will guarantee your electrical safety.
5
lOMoARcPSD|53169336
• Burns
When electricity comes in contact with our body, it can travel through our body.
When this happens, the electricity can damage tissues and organs.
• Irregular heartbeat
6
lOMoARcPSD|53169336
• Respiratory arrest
Call emergency number for help: Call the local emergency number immediately if
you encounter an Electric Shock accident. Do not touch the person directly, as he may
still be in contact with the electric current. Such incidents always require emergency
medical attention, even if the injured person seems fine afterward.
Separate the injured person from the electric current source: Try to turn off the
appliance's power by unplugging it or shut off the power through the circuit breaker,
or fuse box. If it is impossible to turn off the power, try to separate the person from the
current using a non-conductive object such as a plastic or wooden stick, broom, chair,
7
lOMoARcPSD|53169336
Do CPR, if required: If you can safely touch the injured person, do CPR
(cardiopulmonary resuscitation) if the person does not have a pulse or is not breathing.
To perform CPR, you should place one hand on top of the other in the middle of the
chest. Then administer two inches-deep compressions by pushing down hard and fast
using your body weight. The aim is to give 100 to 120 compressions in 60 seconds.
Then tilt the person’s head back, lift his chin, pinch his nose closed and blow into his
mouth to make his chest rise. Make sure the person’s mouth is clear before performing
the rescue breaths. Perform two rescue breaths followed by 30 compressions. Repeat
this until medical help arrives or the person starts breathing.
Check for other injuries: If the injured person is bleeding, then apply pressure and
elevate the wound if the arm or leg is bleeding. Also, if the shock made the person
fall, then he may have a fracture. Cover the burned areas with a clean cloth or
bandages if the person has sustained burn injuries.
.
What is Electrical Grounding?
Simply, "grounding" means a low-resistance path has been made for electricity to flow
into the ground. A "grounded" connection includes a connection between the electrical
equipment and a ground through a wire. Once wired properly, this provides your
devices and appliances a secure place to discharge excess electrical current. This will
potentially prevent electrical equipment from several risks. The ground wire in an
electric outlet is basically a safety valve.
8
lOMoARcPSD|53169336
In Low Voltage Networks i.e., the supply to residential and small industrial users, the
grounding arrangement can be TN, TT or IT.
Here, the first letter indicates the connection between transformer and earth (T – direct
connection to earth and I – No connection with earth). The second letter indicates the
connection between the electrical equipment at the consumer and earth (T – Local
earth connection and N – electricity supplier provides the earth connection).
TN Grounding
In TN earthing system, the star point of the transformer (neutral) is connected to earth
and at the consumer side, the ground wire of electrical appliances is connected with
this connection. There are three types of TN Systems.
• TN-S: The ground and neutral conductors are separate and are connected at
the transformer.
• TN-C: Ground and neutral conductors are the same.
TN-C-S: Separate ground and neutral conductors but only near the consumer
side.
TT Grounding
In this type of grounding, the grounding at the transformer and at the consumer are
independent i.e., the star point (neutral) at the transformer is connected to earth and a
local ground electrode acts as a grounding point at the consumer. These two points
have no connection.
IT Grounding
9
lOMoARcPSD|53169336
Power generation stations, Substations etc. form the high voltage network that are
quite different from the low voltage distribution transformers and consumers. In these
high-voltage systems, there are three main types of grounding.
• Ungrounded Systems
• Resistance Grounding
• Solidly Grounded Systems
Ungrounded Systems
An important point about ungrounded systems is that even though the line-to-line
ground fault currents are very low, it is very difficult to identify the line-to-ground
fault.
In solidly grounded or directly grounded systems, the star point of the transformer
(neutral) is connected directly to ground without any added resistance to limit the
current.
10
lOMoARcPSD|53169336
Resistance Grounding
You might have guessed what this type of grounding is. In resistive grounding, there is
a resistor (known as Neutral Earthing Resistor) between the star point (neutral) of the
transformer and the ground. This resistor limits the fault current flowing through the
neutral conductor.
In high resistance grounding, the fault current is relatively low, about 10A or the
current that is equivalent to the capacitive charging current.
In low resistance grounding, the fault current is relatively high, about 50A in some
areas. The fault current value varies from area to area.
11
lOMoARcPSD|53169336
• Grounding Plates
• Grounding Pipes and Rods
Grounding Plates:
Grounding plates are made up of copper or Galvanized Iron (GI) and placed
vertically into the ground in a pit (filled with charcoal and salt layers) over
10 feet deep. For a higher electrical grounding system, the earth moisture
condition must be maintained around the grounding plate system.
The National Electric Code requires that ground plates have at least 2 ft
of surface area exposed to the surrounding soil. Ferrous materials must be
at least .20 inches thick, while non-ferrous materials (copper) need only
be .060 inches thick.
12
lOMoARcPSD|53169336
A galvanized steel pipe (mixture of salt and charcoal) is placed vertically into the soil
through drilling for connecting the grounding wires. The length and diameter of the
pipe size mainly depends on the type of soil and electrical installation (magnitude of
current). The soil moisture will decide the pipe's length to be placed in the ground.
A copper rod with galvanized steel pipe is placed upright into the ground. This is very
similar to pipe grounding. Here, rods are in the form of electrodes therefore
decreasing the resistance of earth to a specific value. The National Electric Code
(NEC) requires that driven rods be a minimum of 8 feet in length and that 8 feet of
length must be in direct contact with the soil.
13
lOMoARcPSD|53169336
FUTURE SCOPE
The future of electrical safety holds immense potential for a safer and more sustainable world.
Smart grids, IoT integration, enhanced personal protective equipment, AI, and advanced training
programs are just a few of the many innovations set to transform electrical safety. By embracing
these technology-driven advancements, we can create an environment where electrical hazards are
minimized, accidents are prevented, and the security of individuals and communities is prioritised.
CONCLUSIONS
It is suggested that the priority should be given for high risk related factors. Until people are not
taking it cautiously, we will face many electrical hazards in indoor and outdoor also. We should
follow proper Rules and Regulations to avoid accident and there should be trained personnel so that
they can work with proper Rules and Regulations. Electrical hazards can cause burns, shocks and
electrocution (death). Overhead wires are energized at lethal voltages. Repair of electrical cords or
equipment is not recommended unless authorized. Qualified electricians are recommended to
inspect electrical equipment. In damp locations, inspect electric cords and equipment in order to
ensure they are in good condition; use a ground-fault circuit interrupter (GFCI). Precaution must be
taken when working near electricity or with electrical equipments.
Electrical grounding system ensures personal and equipment safety while working on the line.
Remember, a line that's de-energized will simply become energized in the blink of an eye, therefore
electrical system should be kept safely grounded in all times.
The proven expertise of our team of certified professional engineers will aid in the evaluation of
your system and deliver state-of-the-art grounding solutions for your power system's protection. We
work closely with our clients in collecting the data, modeling the system, simulating the worst case
conditions and abnormalities, plotting the step and touch potentials & offering recommendations in
compliance with the latest industrial standards.
14
lOMoARcPSD|53169336
REFERENCES
Mark A. Cook, Richard S. Reines, (2003): History and Interpretation Of Electrical
Grounding In Wisconsin,Public Service Commission of Wisconsin PSC White Paper
Series May 2003 Pp 1 -16
International Journal of Engineering Research & Technology (IJERT)
http://www.ijert.org ISSN: 2278-0181 IJERTV9IS050858 (This work is licensed
under a Creative Commons Attribution 4.0 International License.) Published by :
www.ijert.org Vol. 9 Issue 05, May-2020.
Doughty, R. L., Epperly, R. A., and Jones, R. A. (1991), ‘Maintaining Safe Electrical
Work Practices in a Competitive Environment’, Industry Applications Society Annual
Meeting, 1991., Conference Record of the 1991 IEEE, Vol. 2, 28 Sep 1991-04 Oct
1991, IEEE, pp. 1275 – 1283.
Barrett, J.S.; Chisholm, W.A.; Kuffel, J.; Ng, B.P.; Sahazizian, A-M.; and de Tourreil,
C. (2003), “Testing and Modelling Hollow-Core Composite Station Post Insulators under Short-Circuit Conditions,”
IEEE PES General Meeting, Vol. 1, 13–17 July 2003, pp. 211– 218.
15