rc642_cs_r4_hires
rc642_cs_r4_hires
Room Controller
RC642D
RC642
Automated Logic’s RC642 Room Controller provides unprecedented power and flexibility to control a variety of
packaged HV-ac equipment. Attractively packaged, the RC642 mounts directly on interior walls and provides local
setpoint adjustment, schedule and override capabilities. The Room Controller has a large high contrast LCD and
easy-to-use occupant controls. Additional remote RS sensors can easily be networked to the Room Controller for
large spaces.
BACnet® Support: Conforms to the Advanced Application Controller (B-AAC) Standard Device Profile as defined in
ANSI-ASHRAE Standard 135-2004 (BACnet) Annex L. Tested to Protocol Revision 9
Communication: The following ports are available on the RC642 module: EIA-485 port for ARCNET 156 Kbps or MS/TP (9600
bps – 76.8 Kbps). Local access port for system start-up and troubleshooting.
RC642D Rnet port: Supports up to four RS sensors for averaging or high/low.
RC642 Rnet port: Supports up to four RS sensors and one RS Pro sensor for averaging or high/low.
Digital Outputs: Six digital outputs, relay contact rated at 1A max @ 24V-ac, configured normally open.
Universal Inputs: Four universal inputs with 10 bit A/D resolution. Two are configurable for dry contact or thermistor; and two
for either dry contact, thermistor or 0-5 V-dc.
Analog Outputs: Two analog outputs, 0-10V-dc with 8-bit resolution, 10mA maximum.
Microprocessor: High speed 16-bit microprocessor with ARCNET communication co-processor.
Memory: 512 Kbyte non-volatile battery-backed RAM, 1 MByte Flash memory, 16-bit memory bus.
Battery: 7 year Lithium BR325 battery provides minimum 10,000 hours of data retention during power outage.
Status Indicators: LED status indicators for EIA-485 communication, running, error and power.
Module Addressing: Rotary dip switches for intuitive network addressing of modules.
Protection: Built in surge and transient protection circuitry for power, communications and I/O.
Listed by: UL916 (Canadian Std C22.2 No. 205-M1983), CE, FCC Part 15 – Subpart B – Class A, CE EN50082-1997
Environmental Operating Range: 0ºF to 130ºF (-17.8ºC to 54.4ºC); 10 -90% relative humidity, non-condensing.
Power Requirements: 24V-ac ± 10%, 26V-dc (25 V min, 30 V max), 50-60Hz, 12VA
Physical: Plastic enclosure, removable screw-type terminal blocks.
Weight: 10.6 oz. (.03 Kg)
Dimensions:
Overall Mounting
Width: 6.8 inches (17.3 cm) 2 inches x 4 inches electrical box U.S.
Height: 4.3 inches (10.9 cm) 4 inches x 4 inches electrical box U.S.
Depth: 1.3 inches (3.3 cm) 35mm BS4662 single gang electrical box
RC642
Automated Logic Corporation . 1150 Roberts Boulevard . Kennesaw, Georgia 30144 . 770/429-3000 . Fax 770/429-3001 . www.automatedlogic.com
© United Technologies Corporation 2013. All rights reserved. Copyright Policy
BACnet is a registered trademark of ASHRAE. All other trademarks are the property of their respective owners. Specifications are subject to change without prior notice.
Automated Logic is a part of UTC Climate, Controls & Security, a unit of United Technologies Corp
Made in the USA RC642_CS_r4