Product datasheet
Specifications
medium voltage variable speed
drive ATV1200 - 10 kV - 700 kVA
ATV1200A7001010
Main
Range of product Altivar 1200
Product or component type Medium voltage variable speed drive
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Device short name ATV1200
Product destination Asynchronous motors
Product specific application Fan, pump, compressor, conveyor
Assembly style In floor-standing enclosure with separate air flows
Complementary
product composition 2 x plinth
Phase-shifting transformer
Medium voltage arrestors
Cooling fans
Human machine interface
24 x power cells
EMC filter Integrated
Network number of phases 3 phases
Input type 48 pulse diode rectifier bridge
[Us] rated supply voltage 10 kV +/- 10 %
Supply voltage limits 2970…3630 V
[Uc] control circuit voltage 220 V
Motor power kW 585 kW
Line current 65 A
drive efficiency with transformer 96 % (standard efficiency)
(including fan power)
total losses at 100 % load 23 kW (standard efficiency)
including fan power
Apparent power 700 kVA
Prospective line Isc 31.5 kA for 150 ms
Overload withstand 1.2 In, standard overload, 60 s
1.5 In, standard overload, 3 s
1.5 In, high overload, 60 s
1.85 In, high overload, 3 s
Continuous output current 40 A (standard overload)
32 A (high overload)
Maximum transient current 48 A for 60 s
Speed drive output frequency 0.5…120 Hz voltage/frequency ratio (V/f)
0.5…70 Hz vector control with/without speed feedback
Nominal switching frequency 600 Hz
Feb 27, 2025 1
Speed range 20…100
Asynchronous motor control Vector control with sensor, optional
profile Voltage/frequency ratio (V/f)
Closed-loop control with encoder
Sensorless flux vector control
Synchronous motor control profile Closed-loop control with encoder
Voltage/frequency ratio (V/f)
Overvoltage category II conforming to EN/IEC 61800-5-1
Output voltage <= power supply voltage
Isolation Electrical between power and control
Electrical connection Bar - screw type M10, clamping capacity: 6 x 40 mm² (L1/R, L2/S, L3/T) entry from
the bottom or from the top
Supply External supply for control at 220 V AC, 3 kVA
Internal supply for cooling fan at 380 V AC
External supply for control at 220 V AC/DC (optional)
External supply for cooling fan at 380 V AC (optional)
Analogue input number 4
Analogue input type software-configurable current: 0...20 mA/4...20 mA, 24 V max, impedance: 250 Ohm
Analogue output number 2
4 (optional)
Analogue output type software-configurable current: 0...20 mA/4...20 mA DC, impedance: 250 Ohm
Discrete output number 10
14 (optional)
Discrete input number 6
10 (optional)
Acceleration and deceleration Linear from 0...3200 s
ramps
Protection type Ground fault protection: drive
Dielectric strength 28 kV AC between earth and power terminals
Communication port protocol Human machine interface: Modbus with 2-wire RS485(1) - SUB-D 9
Human machine interface: Modbus TCP with (1) - RJ45
Human machine interface: EtherNet/IP with (1) - RJ45
Human machine interface: Profibus with (1) - SUB-D 9
Human machine interface: DeviceNet with (1) - SUB-D 9
Operating position Vertical +/- 10 degree
Colour of enclosure Grey (RAL 7032)
Width 3960 mm (standard efficiency)
Depth 1600 mm (standard efficiency)
Height 2670 mm standard efficiency
Net weight 4400 kg (standard efficiency)
Environment
IP degree of protection IP41
IP31
IP42
Standards EN/IEC 60204-11
EN/IEC 60529
EN/IEC 61800-3
EN/IEC 61800-4
EN/IEC 61800-5-1
Marking CE
Pollution degree 2 conforming to EN/IEC 61800-5-1
2 Feb 27, 2025
Noise level 80 dB
Vibration resistance 4.9 m/s² (f= 10…50 Hz)
Relative humidity 0…90 %
0…95 % optional
Ambient air temperature for 0…40 °C
operation 40…50 °C (with current derating of 2 % per °C)
Ambient air temperature for -10…60 °C
storage
Volume of cooling air 19800 m3/h (standard efficiency)
type of cooling Forced convection
Operating altitude <= 1000 m without derating
1000...2000 m with current derating 0.6 % per 100 m
Feb 27, 2025 3
Environmental Data
Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity
via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.
Environmental Data explained
How we assess product sustainability
Use Better
Materials and Substances
Packaging made with recycled cardboard No
Packaging without single use plastic No
Use Again
Repack and remanufacture
Take-back No
4 Feb 27, 2025
Product datasheet ATV1200A7001010
Dimensions Drawings
Dimensions
Standard Efficiency
Feb 27, 2025 5
Product datasheet ATV1200A7001010
Mounting and Clearance
Clearance
6 Feb 27, 2025
Product datasheet ATV1200A7001010
Connections and Schema
Connections and Schema
Standard Wiring Diagram
(1) Integrated power supply
(2) Control power supply
(3) 4-20mA speed setpoint
(4) Input reserved
(5) VFD is ready
(6) Local 1 remote control
(7) VFD running
(8) Alarming
(9) Detected fault
(10) 4-20mA Output current
(11) 4-20mA Output speed
(12) Stop
(13) Start
(14) Main circuit breaker enable to close
(15) Trip main circuit breaker
(16) Undervoltage release module of circuit breaker
(17) 4-20mA reserved inputs
(18) Reserved outputs
(QF1) Main circuit breaker
Feb 27, 2025 7
Product datasheet ATV1200A7001010
Performance Curves
Power Derating of Output Current
Temperature Derating
(x) Ambient temperature
(y) Derating
Altitude Derating
(x) Altitude
(y) Derating
8 Feb 27, 2025