TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-04, Rev.
7.0 DATA SCHEDULE
11kV,13.8kV, 33kV & 34.5kV Medium Voltage Power Cables
SEC Enquiry No. Date:
SEC Purchase Order Date:
No.
or Contract No.
SEC PTS No./Project Title with J.O. No.
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
3.0 APPLICABLE CODES AND STANDARDS
Reference Manufacturing Standard ICEA/IEC
4.0 DESIGN AND CONSTRUCTION REQUIREMENTS
4.2 Design Criteria/Rating
As per SOW
a. Cable Nominal Voltage, kV
b. System Short Circuit Current, kA 25
c. Maximum conductor short circuit current
250
temperature, °C
d. Maximum permissible continuous
90
conductor temperature, °C
e. Emergency Loading
x Maximum emergency conductor
105
loading temp,°C
x Permissible Load in Amps, A *
x Allowable loading duration; hrs
i) During any 12 months 72
ii) During the life of the cable 1500
'A'- SEC SPECIFIED DATA/PARAMETER.
'B'- BIDDER/SUPPLIER/VENDOR/CONTRACTOR PROPOSED DATA/PARAMET
'C'- REMARKS SUPPORTING THE PROPOSED DEVIATION IN COLUMN 'B'.
(*)- DATA/PARAMETER TO BE PROVIDED/PROPOSED BY THE
BIDDER/SUPPLIER/VENDOR/CONTRACTOR IN COLUMN 'B'.
11TMSS04R0/HKG Date of Approval: December 12, 2011 PAGE NO. 13 OF 17
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-04, Rev. 0
7.0 DATA SCHEDULE
11kV,13.8kV, 33kV & 34.5kV Medium Voltage Power Cables
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.3 Materials
4.3.1 Conductor
a. Material (Al or Cu) Cu
b. Size, mm² As per SOW
c. Number of cores (1C or 3C) As per SOW
d. Number of strands *
e. Diameter of strand prior to compaction *
f. Cross sectional area (mm²) *
g. Diameter, mm *
h. Temperature co-efficient at 20°C, /°C *
i. Skin effect loss factor (ks) *
j. Proximity effect loss factor (kp) Short circuit
capability of conductor in kA for 1 sec starting
with 90°C conductor temperature upto
*
maximum short circuit current temperature.
k. Water blocking material between strands *
4.3.2 Conductor Shield
Extruded
a. Material
SEMICON
b. Average thickness, mm *
(70 and 95 mm2) 0.38
(120 to 240 mm2) 0.51
(400 and 500 mm2) 0.63
c. Minimum thickness, mm
(70 and 95 mm2) 0.304
(120 to 240 mm2) 0.408
(400 and 500 mm2) 0.504
d. Diameter over conductor shield, mm *
e. Thermal resistivity, k-m/W *
4.3.3 Insulation
a. Material XLPE
b. Average thickness, mm 8.76
c. Minimum thickness, mm 7.884
d. Diameter over insulation, mm *
e. Thermal resistivity, k-m/W *
f. Dielectric constant () *
g. Loss factor () *
11TMSS04R0/HKG Date of Approval: December 12, 2011 PAGE NO. 14 OF 17
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-04, Rev. 0
7.0 DATA SCHEDULE
11kV,13.8kV, 33kV & 34.5kV Medium Voltage Power Cables
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.3.4 Insulation Shield
a. Material SEMICON
b. Min/Max thickness, mm
(70 to 240 mm2) 1.02/2.16
(400 to 500 mm2) 1.4/2.54
c. Average thickness, mm
(70 to 240 mm2) 1.275
(400 and 500 mm2) 1.75
d. Diameter over insulation shield, mm *
e. Thermal resistivity, k-m/W *
4.3.5 Metallic Shield
a. Material Wires/Tapes
b. Tape thickness, mm. *
c. Tape width, mm. *
d. No. of tapes *
e. Percent overlap *
f. Wire size, mm² *
g. No. of wires *
h. Effective cross-sectional area, mm² *
i. Diameter over metallic shield, mm *
j. Temperature co-efficient at 20°C, /°C *
k. Short circuit capability in kA for 1 sec of the
metallic shield compound per ICEA publication
P-45-482 starting with 90°C conductor
*
temperature.
4.3.6 Moisture impervious layer Material
Material *
Minimum average thickness, mm *
Diameter over impervious layer, mm *
4.3.7 Inner covering & fillers requirements
Material *
Average thickness, mm *
Minimum thickness, mm *
Cable overall diameter *
Thermal resistivity, k-m/W *
Max. permissible continuous temp. (°C) *
11TMSS04R0/HKG Date of Approval: December 12, 2011 PAGE NO. 15 OF 17
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-04, Rev. 0
7.0 DATA SCHEDULE
11kV,13.8kV, 33kV & 34.5kV Medium Voltage Power Cables
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.3.8 Armour Tapes
Material *
Nominal thickness *
4.3.9 Outer Jacket
Material (PVC or LLDPE) PVC
Nominal thickness *
Average thickness *
4.4.4 Graphite Coating
Average thickness of coating on outer jacket
0.01
of cable, mm
6.0 PACKING AND SHIPPING
a. Total quantity required, m *
b. Are matched sets of cable reel length required YES/ No
c. If ‘Yes’ how many reels are required per set *
d. Tolerance in cable length of matched reel sets *
e. Conductor weight, kg/km *
f. Cable weight, kg/km *
g. Reel and cable weight, kg *
h. Cable length per Reel, m *
i. Cable reel diameter, mm *
j. Cable reel width, mm *
OTHER REQUIRED INFORMATION
a. Life expectancy of cable, years Over 30
b. 3-Phase inductance in trefoil formation, mH/km *
c. 3-Phase inductance in flat formation, mH/km *
d. 3-Phase capacitance in trefoil arrangement, *
F/km
e. 3-Phase capacitance in flat formation, F /km *
f. Maximum permissible overload in % of 3
cables in underground cable duct trefoil
formation at 40°C soil temperature for 1/2/3 (I1-
hour/I2-hours/I3-hours) starting with prior
loading of
*
50%
75%
100%
g. Maximum pulling tension (kN) *
h. Maximum sidewall pressure, kN/m *
i. Minimum bending radius (mm) *
j. Meets strippability requirements of AEIC CS8 *
11TMSS04R0/HKG Date of Approval: December 12, 2011 PAGE NO. 16 OF 17
TRANSMISSION MATERIALS STANDARD SPECIFICATION 11-TMSS-04, Rev. 0
7.0 DATA SCHEDULE
11kV,13.8kV, 33kV & 34.5kV Medium Voltage Power Cables
A. ADDITIONAL TECHNICAL INFORMATION OR FEATURES TO BE FURNISHED
BY SEC:
B. ADDITIONAL SUPPLEMENTARY DATA OR FEATURES PROPOSED BY
BIDDER/VENDOR/SUPPLIER/CONTRACTOR:
C. OTHER PARTICULARS TO BE FILLED UP BY BIDDER/VENDOR/SUPPLIER/
CONTRACTOR:
Actual Manufacturer Vendor/Supplier/
of Equipment/Material Contractor
Name of the Company
Location and address
Name and Signature of
authorized epresentative
and date
Official Seal/Stamp
of the Company & Date
11TMSS04R0/HKG Date of Approval: December 12, 2011 PAGE NO. 17 OF 17