Power Systems Lecture 5
Power Systems Lecture 5
3 - phase
short circuit
2 - phase
short circuit
1 - phase
earth fault
The nature of short circuit current
i
90 I=?
is
2 I k' ' R L
U
2 I k' ' 2 Ik
t / ms
i 0
2 I k' '
2 I k' 2 Ik X d' ' X d' X d
t I k' ' I k' I k
The nature of short circuit current
u 2 U sin(t )
= switching time after the voltage zero crossing,
the time t is computed since this moment
di
Ri L 2 U sin(t )
dt
2U
Z
R t
sin(t ) e L sin( )
L
Z R 2 (L) 2 :: tan
R
I S H 2 I K' '
R
H f attenuation factor
X
I K' ' subtransient short circuit current
At transmission voltages:
R
H 1,8 0,07
X
Note: Ik’’ is rms value
IS 2,5 I K' ' Is max instantaneous value
Example: 3-phase short circuit in a power plant
Sk' ' 1100 MVA
One line diagram:
Sk 800 MVA
ZTh
110 / 10 kV, 16 MVA
'' u x 10 %, u r 1 %
X SV Xt
3. The motors zm
z m R t j (x t x m )
U2 U2 U2
ur j u x
St St I s / I n Sm
0,125 j 2,833 2,836 87,5
10
u Th 0 kV
3
u
I k ' ' Th 11,69 86,1 kA
z Th
Example: 3-phase short circuit
S ''
k ; SkT S 160 MVA M M M 8 MVA
Sk ' ' SkT
k,sv ux IS / I n 6
1100 160
MVA 139,7 MVA
1100 160
1
2. Generator : Sk,' 'g S g 28,1 MVA
xd ''
3. Motors :
Skm Is / I n Sm 48 MVA
S S
S ''
kT km ;
Sk, t
1
S
8
133,3 MVA
SkT Skm
k, m
ux 0,06
133,3 48
MVA 35,3 MVA
133,3 48
Example: 3-phase short circuit
Sk Sk,sv Skg
Sk SkT 1
Sg
Sk SkT xd
800 160 1
16 MVA 149,3 MVA
800 160 1,0
Sk
Ik 8,62 kA
3U
Example : MV-distribution line & 3-ph vs. 2-ph faults
16 MVA
10 % z j R j j Xj 8 j6
r + jx = 0,4 + j 0,3 km
212
21 kV
20 km XT u x 2,76
Sk = 900 MVA 16
U 2 212
Xv&Xt grid&transformer reactance Xv 0,49
Xj&Rj line reactance&resistance S 900
~ Uv Iv
Uv Uv Up 21
Ik ; Uv
z R j j(x v x T x j ) 3 3
21
kA
3 12,23 49
0,99 49 kA
2-phase fault current
ER Z
R
ES Ik Z
S T
ET Z
T
Ik 3 1
1
U Th E S E T
1
ZTh 2 Z S R
ES E T 3 E R 90
Ik
2Z 2Z
3 ER 3
Ik 0,99 kA ( 0,86 kA)
2 Z 2
3
I k2v I k3v
2
(holds, when Z1 Z 2 )
Symmetrical components
The relation between phase quantities and symmetrical components:
U L1 1 1 1 U 0
U 1 a 2 a U1
L2
U L 3 1 a a U 2
2
The left hand vector includes the phase voltages, the right hand vector zero-,
positive- and negative sequence voltages. The transformation matrix is defined
using the phase shift operator a = 1120. The inverse transformation is:
U 0 1 1 1 U L1
1
a U L 2
2
U 1
3 1 a
U 1 a 2 a U L 3
2
U2,L2 U2,L1
UL3 U1,L3
UL1 U0,L1
U0,L2 U1,L1 U2,L3
U0,L3
UL2
U1,L2
An example case of phase voltages
And the corresponding symmetrical components
Symmetrical components
Positive sequence system includes the normal symmetric three phase system.
Computations can be done using a one line diagram.
The negative sequence components are similar to positive ones, but they rotate in
An opposite order. For passive components, the impedance Z1 and Z2 are equal, but
not for rotating machines.
The zero sequence component is similar in all the three phases. It causes a current, which
has to return through neutral wire, where the current I0 is hence three-fold. For this
reason the impedance of the neutral wire is also taken three fold.
E Z0
Z I1 Z1 I2 Z2 I0
Z
E1 E2 E0
Z 3ZN
ZN
E Z
R
Ik IR = 0
S
IT = - IS
T
Ik
I0 1 1 1 IR 1.
1 a = 1120
I1
2
1 a a IS 2.
3 2
I2 1 a a IT 3.
1. I 0 0
2. & 3. & I T IS I 2 I1
Voltage source is symmetric:
E1 E R ; E 2 0 ; E 0 0
2-phase short circuit using symmetric components
One line diagram:
I1 I2 I0 0
Z1 ER
I1
Z2 Z1 Z 2
E1 I 2 I1
IR 1 1 1 I0
IS 1 a
2
a I1
2
IT 1 a a I2
I S a I 1 a I2
2
a E R a ER 3 E R 90
2
Z 1 Z2 Z1 Z 2
IF Z1 Z 2 Z , then
3 E R 90
IS
2Z
Single phase earth fault
One phase conductor is connected into the ground. The fault is
unsymmetric. The zero sequence system strongly depends on how
Neutral is grounded.
The earth fault differs clearly from the short circuit faults. In ungrounded
or compensated neutral systems, the fault current is small. The voltage
between sound phases and ground rises (up to the line voltage).
EL1 Z UL1
EL2 IL1
Z UL2
EL3 Z UL3
Zf
ZM
EL2 IL1
Z UL2
EL3 Z UL3
Zf
ZM
It follows: U 0 U1 U 2 Zf I L1 a = 1120.
I 0 a 2 I1 a I 2 0
I 0 I1 I 2
I 0 a I1 a I 2 0
2
U 0 Z0 I 0
U1 E1 Z1 I1
U 2 Z2 I 2
Z0 I 0 E1 Z1 I1 Z 2 I 2 3 Zf I 0
One phase earth fault
U1 U2 U0
I1 I2 I0
~
E1 Z1 Z2 Z0
3Zf
I0 = I 1 = I 2
The total fault current is three times the zero sequence current:
3 E1 E1
If 3 I0
Z0 Z1 Z 2 3 Zf Z Z M Zf
Transformer windings in zero sequence networks
Winding Zero sequence network
connection
(Δ) in Primary (Δ) in Secondary
3ZL 3ZL
ZL
Zm0
3ZL Zm0
ZL
Solution for 1-phase earth fault :
ZT EP Zi
ZT
C
C = capacitance
between phases
Zm Zi
Rf Ce = capacitances
Zm Ce Rf phase to earth
I0 = I 1 = I 2
3E P EP
I f 3I 0 Z0
Z0 Z1 Z 2 3R f 3 ( Z 0 Z1 Z 2 ) R f
1
3Rf
Z1
Z0T
Z0 Ce Z1 C1 ZkT Z2 C2 ZkT C1 = Ce + 3C
3Zm C1 = C 2
Comparison of 1-ph, 2-ph, 3-ph faults
for fault currents (Thevenin’s method) :
EP
1-ph: If
3 ( Z 0 Z1 Z 2 ) R f
1
3EP
2-ph: If
Z1 Z 2 R f
EP
If
3-ph: Z1 R f
1
Z0
jC e
Z0 Z1 & Z0 Z 2
Rf
If
EP 3Ce U0
EP
f I
1
R
j 3C e
f
U0 1
E P 1 (3 C e R f ) 2
Voltages during an earth fault :
T
UT
UT
US
UR
S R
US
In sound network
U R US U T U P
Rf > 0
U 0 Ie R f U P
S
T
US UT
U0
R
IeRf
UT 3 UP ?
Max. voltage for UT, when
1
R f 0,37
j C 0
And UT = 1,05 3 UP
Compensated neutral systems : Zm = Le
Inductance Le is selected such that
the current of Ce is cancelled
1
Y 0 j C e 0
j 3L e
R0 is the network
leakage resistance
EP 3Ce U0
R0 Le
If 100 % compensation :
E
I
f R R
f 0
U0 R0
E R0 Rf
Earth fault currents in an ungrounded system
The current measured at the substation (I0) includes the current in the
fault location less the current which flows through the earth capacitances
of the faulty line:
C 0 C 01
I0 C0
I ef
4
IE4
3
IE3
2
IE2 IE2 + IE3 + IE4
IE1
1
IE1 4
IE = IEi
1
Earth fault currents in a compensated system
4
IE4
3
IE3
IL
2
IE2
IE
1
IE1
IL IE + IL = If
IE
If
U0