dnet-qr001_-en-e
dnet-qr001_-en-e
Quick Reference
DeviceNet System Quick Reference
Solid state equipment has operational characteristics differing from those of electromechanical
equipment. Safety Guidelines for Application, Installation, and Maintenance of Solid State
Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or
online at http://literature.rockwellautomation.com) describes some important differences
between solid state equipment and hard-wired electromechanical devices. Because of this
difference, and also because of the wide variety of uses for solid state equipment, all persons
responsible for applying this equipment must satisfy themselves that each intended application
of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential
damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes.
Because of the many variables and requirements associated with any particular installation,
Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the
examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with
respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of
Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety
considerations.
SHOCK HAZARD Labels may be on or inside the equipment, for example, a drive or
motor, to alert people that dangerous voltage may be present.
BURN HAZARD Labels may be on or inside the equipment, for example, a drive or motor,
to alert people that surfaces may reach dangerous temperatures.
Table of Contents
Topic Page
Design 3
Select 4
Install 5
Configure 6
193-DNCT Handheld Configuration Device 6
Node Commissioning on Your DeviceNet Network 6
Starting the 193-DNCT Terminal 7
Change Node Number 63 to Node Number 1 8
Create the 1756-DNB and 1769-SDN Scanlist by Using AutoScan 9
Example: Configure the E1 Overload 12
Maintain 13
Diagnostics and Troubleshooting 13
Design
For this manual, we are looking at a system with these constraints. They do not represent network
maximums. The DeviceNet network has these capabilities:
• Cable length of 100 m (328 ft)
• Maximum of 64 nodes
• Power supply limited to 4 A (Class 2)
Select
Use this table to select the appropriate media for your system. For other media choices, refer to
Chapter 6 in the On-Machine Connectivity Catalog, publication M116-CA001.
Install
Locate and mount the modules. Follow these steps to crimp the connectors.
For thin round media, refer to the DeviceNet Media Design Installation Guide,
publication DNET-UM072.
1. Set the center of the connector cover (see arrows) in the center of the crimp block of the crimp tool.
2. Crimp the connector until you hear the connector lock into place.
Configure
193-DNCT Handheld Configuration Device, Revision 2.1 or Later
The 193-DNCT DeviceNet configuration terminal is a handheld device that can configure, program,
retrieve historical data, and monitor DeviceNet components, while directly connected to the network.
Commissioning is made simple with the capability to upload, store, and download complete device
configurations, while online with the network. This tool also aides in troubleshooting by providing
physical layer diagnostics and network bandwidth statistics.
Important: The factory default for each device is 125 Kbps, set to node number 63 with autobaud
enabled.
Attach and connect the 193-DNCT terminal to the DeviceNet network. This display appears for
10 seconds.
DEVICENET HIM
Baud: 125K Auto: 62
After 10 seconds, a Network Who dialog box similar to the one shown below appears with all nodes
and associated devices on the network.
Notice that the node number in the upper right corner constantly changes. This shows the node number
that the 193-DNCT terminal is currently scanning during the active network browse it is performing.
If the Network Who dialog box does not appear after 10 seconds, the 193-DNCT terminal is set to
Autobaud Enabled and cannot determine a communication rate as no communication is currently
occurring on the network.
Follow these steps to disable Autobaud.
1. On the 193-DNCT keypad, press the Down Arrow to scroll through the list and select ‘63 – No
Product Name’.
4. Press Enter .
A dialog box appears with NodeComm selected.
Node Commissioning
--------------------------------------
BaudRate: 125K
Address: 63
Tip: You can use the Up Arrow and Down Arrow to scroll through the node numbers.
The DeviceNet network AutoScan feature allows a scanner to automatically map a network of slave
devices into its scanlist without the use of RSNetWorx for DeviceNet software. This greatly improves
the ease of setting up a DeviceNet network, especially networks comprised of simple devices.
When you enable AutoScan, the 1756-DNB or 1769-SDN scanner module searches for devices on the
network that are not yet mapped. Once a qualifying device is found, the scanner adds the device to its
scanlist and maps its I/O data into a predefined location in the scanner’s I/O memory table. This
location is based on the device’s node address and the mapping size.
AutoScan is not enabled initially. You must enable AutoScan so that devices are automatically added to
the scanlist whenever the scanner module is in Idle mode. The mapping size provides the scanner
module with the number of bytes per node to allocate in the I/O tables. Set the mapping size so that it is
higher than the maximum input or output size of every device on the network. If a device found on the
network has an input or output size larger than the mapping size you set, it will not be added to the
scanlist.
In this example, the mapping size is set to 32 bytes per node. The 193-DNCT terminal configures and
originates AutoScan from a special menu, created specifically for that purpose.
1. Turn the key on the front of the 1756-L63 controller (in slot 2) completely clockwise.
This puts the ControlLogix controller into Program mode, which also puts the scanner module into
Idle mode.
2. In the Network Who dialog box, press the Up Arrow to navigate to and select the first line
(0 – 1756-DNB DeviceNet Scanner).
4. Press the Down Arrow to navigate to and select Scanner and press Enter .
5. Press the Down Arrow to navigate to and select AutoScan and press Enter .
AutoScan Setup
AutoScan: Disable
Mapping: 32
Idle Mode
Active Nodes: 0
6. If AutoScan is selected and set to Disable, press the Up Arrow to change to Enable.
10. Press SEL twice and then press Enter to save your changes.
AutoScan is disabled in the scanner.
11. Press ESC three times to return to the Network Who dialog box on the 193-DNCT terminal.
12. Turn the key on the front of the 1756-L63 controller (in slot 2) completely counter-clockwise.
This puts the ControlLogix controller back into Run mode, which will also put the scanner module
into Run mode, provided that the scanner run bit is set by the logic or data table.
1. In the Network Who dialog box, press the Up Arrow to navigate to and select the first line
(0 – 1756-DNB DeviceNet Scanner).
3. Press the Down Arrow to navigate to and select Scanner and press Enter .
4. Press the Down Arrow to navigate to and select ScanList and press Enter .
This ScanList dialog box appears.
ScanList
0 -- DeviceNet Scanner
2 -- 100-DNY42
5 -- E1 Plus
6 -- Parker Valve
7 -- E1 Plus
8 – 100-DNY42
62 – This DeviceNet HIM
5. Press the Down Arrow to navigate to and select 5 – E1 Plus and press Enter .
A dialog box appears with the mapping details of the E1 Plus devices scanlist entry. You can
temporarily disable the 1756-DNB scanner scanlist entry.
8. Press ESC four times to return to the Network Who dialog box on the 193-DNCT terminal.
1. In the Network Who dialog box, press the Down Arrow to navigate to and select 5 – E1 Plus.
3. Press the Down Arrow to navigate to and select Params and press Enter .
4. Press the Down Arrow to navigate to and select Num List and press Enter .
The 193-DNCT terminal now displays parameter 1, the Average %FLA parameter.
Important: Additional information is provided at the bottom of the display for each parameter
display, including the parameter description (that scrolls continuously), minimum and
maximum values, and if the parameter is read only.
5. Press 1, then 7, and press Enter to display parameter 17 (the OL Warning Level configuration).
The OL Warning Level parameter 17 displays with a value of 80%.
6. Press the SEL , then press 9, 0, and Enter to change the value to 90%.
Notice how the configuration value changes to 90% on the display. This value was actually written
to the E1 Plus and has been stored into nonvolatile memory within the device.
Maintain
Diagnostics and Troubleshooting
The 193-DNCT terminal has some diagnostics built in that can be used to troubleshoot a DeviceNet
network. These diagnostics include bus voltages, bandwidth utilization percentage, and CAN error
counts.
3. Press the Down Arrow to navigate to and select the Network group and press Enter .
This dialog box, with similar values, appears on the 193-DNCT terminal.
The Max Bus % Load and CAN Errors/Sec parameters are not easily measured by other means
and are valuable for troubleshooting the network. The Max Bus % Load parameter shows the
maximum network bandwidth that has ever been used. If this value goes too high, communication
anomalies could occur on the network due to devices being ‘starved’ for bandwidth. The CAN
Errors/Sec parameter is generated if packets are being corrupted on the network, such as due to
electrical noise or a bad device. This value, which should be zero on a healthy network, is a good
barometer of the general health of the DeviceNet packet-delivery mechanism.
Allen-Bradley, Rockwell Automation, PowerFlex, ControlLogix, CompactLogix, and RSNetWorx for DeviceNet are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.