02/11/2015 www.crouzet.
com
DIN Rail Mount 22,5 mm ENR Part number 84870200
Regulation of 1 or 2 levels (min / max)
Monitoring filling (UP) or emptying (DOWN) selected by a switch on the front panel
Probes supplied with AC current
Time delay preventing wave effect adjustable from 0.1 to 5s (ENRM)
Sensitivity adjustable on front panel from 250 Ω to 1 M Ω (ENRM)
Sensitivity adjustable on front panel from 5 KΩ to 100 k Ω (ENR)
Part numbers
Type Characteristics Voltages
84 870 200 ENR Monitoring filling (UP) Monitoring emptying (DOWN) 24 →240 V AC/DC
Specifications
Operating range 24 →240 V AC/DC
Operating range 20,4 →264 V AC/DC
Maximum power consumption AC 5 VA, DC 1,5 W
Adjustable sensitivity 5 KΩ→100 KΩ
Measurement accuracy (at maximum sensitivity) ± 30 %
Electrode voltage (max) 12 V
Electrode current (maximum) 1 mA
Maximum cable capacity 10 nF
Response time high level 300 ms
Response time low level 500 ms
Output relay (according to AC1 resistive load) 1 changeover relay 8 A AC max.
Isolation of contacts and electrodes from power supply 2,5 kV AC
Operating temperature range (°C) -20 →+50 °C
Storage temperature range (°C) -40 →+70 °C
Weight (g) 91
Principles
Operating principle
Monitoring maximum and/or minimum levels of conductive liquids (tap water, sea water, waste water, chemical solutions, coffee, etc).
The principle is based on measuring the apparent resistance of the liquid between two submerged probes. When this value is lower than the preset threshold displayed on the unit's front panel, the
output relay changes state. To prevent any occurrences of electrolysis, an AC current is passed through the probes. Areas of application include the agri-food, chemical and other industries.
Adjusting two levels : Minimum/Maximum
The output relay changes state when the level of liquid reaches the maximum electrode, with the minimum electrode submerged. It returns to its initial state when the minimum probe is no longer in
contact with the liquid.
Note
If the power break T lasts for 1 second or more, the relay reenergises instantly when in "UP" mode and is de-energised when in "DOWN" mode.
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
02/11/2015 www.crouzet.com
No Legend
Maximum level
Minimum level
Output relay : Down or Up
Dimensions (mm)
ENR
Connections
ENR
A1-A2 : power supply
Connections
CA ENR
CA ENR
A1-A2 : power supply
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected