Coduri Erori Sungrow
Coduri Erori Sungrow
Sungrow Error Codes – If the Wi-Fi module is equipped, an error icon will be shown in the App once a
fault occurs. For details, see the related manual. At the same time, the “Error” state will be shown on the
main screen of the inverter.
1. Check the voltage of the grid.
Grid under-voltage. The grid voltage is 2. If the fault persists, please contact
below the protective value, which is lower Sungrow Service Dept.
005 than the protective value of error 004.
Grid under-frequency. The grid frequency is 3. If the grid frequency is within the
below the protective permissible range, contact Sungrow Service
value. Dept.
009
DC injection over-current.
1. Wait a moment for inverter recovery.
The DC current injection of AC current
2. If the fault occurs repeatedly, contact
exceeds the upper limit. Sungrow Service Dept.
011
The average grid voltage exceeds the 4. If the fault occurs repeatedly, contact
permissible range for over 10 minutes. Sungrow Service Dept.
014
The transient bus voltage exceeds the 2. If the fault occurs repeatedly, contact
protective value. Sungrow Service Dept.
019
The bus voltage exceeds the protective 2. If the fault occurs repeatedly, contact
value. Sungrow Service Dept.
020
021 PV1 input over-current. Check the layout and the wiring of PV1 input.
022 PV2 input over-current. Check the layout and the wiring of PV2 input.
044 Open-loop inverter self-test fault. 1. Wait a moment for inverter recovery.
045 PV1 boost circuit fault. 1. Wait a moment for inverter recovery.
059 Communication alarm between master 1. Wait 1 minute for inverter recovery.
DSP
2. If the fault persists, contact Sungrow
and slave DSP. Service Dept.
The inverter is not grounded. Neither the Check whether there is a reliable inverter
PE terminal on the AC connection block grounding line, if there is access to the ground,
nor the second PE terminal on the and the fault persists, please contact Sungrow
106 enclosure is reliably connected. Service Dept.
200 Bus hardware over-voltage fault. 1. Wait for inverter recovery after bus voltage
lower.
The bus voltage exceeds the protective
2. If the fault occurs repeatedly, contact
value. Sungrow Service Dept.
The PV input voltage exceeds the bus Check the functionality of the PV connection
203 voltage. terminals.
Input and output power mismatching If the fault occurs repeatedly, contact Sungrow
306 fault. Service Dept.
Both the ambient temperature sensor and If the fault occurs repeatedly, contact Sungrow
409 the radiator temperature sensor fail. Service Dept.
Ambient temperature sensor open circuit If the fault occurs repeatedly, contact Sungrow
503 warning. Service Dept.
514 Abnormal communication warning of the 1. Check whether the power cable
connections of the meter are correct.