The document presents reliability analysis metrics for the Guder Substation, including key system indexes such as SAIFI, SAIDI, CAIDI, ASAI, ASUI, EENS, and AENS. The values indicate the frequency and duration of interruptions, service availability, and expected energy not supplied. These metrics are essential for assessing the reliability of the electrical system.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
12 views
base case output
The document presents reliability analysis metrics for the Guder Substation, including key system indexes such as SAIFI, SAIDI, CAIDI, ASAI, ASUI, EENS, and AENS. The values indicate the frequency and duration of interruptions, service availability, and expected energy not supplied. These metrics are essential for assessing the reliability of the electrical system.
Contract: SN: 1 Engineer: Fraol Study Case: Reliability Analysis Revision: Filename: Base case Config: Normal
SUMMARY
System Indexes
SAIFI 355.0820 f / customer.yr
SAIDI 335.9636 hr / customer.yr
CAIDI 0.946 hr / customer interruption
ASAI 0.9616 pu
ASUI 0.03835 pu
EENS 2851.479 MW hr / yr
AENS 32.4032 MW hr / customer.yr
SAIFI System Average Interruption Frequency Index
SAIDI System Average Interruption Duration Index CAIDI Customer Average Interruption Duration Index ASAI Average service Availability Index ASUI Average Service Unavailability Index EENS Expected Energy Not Supplied AENS Average Energy Not Supplied