rdc485Enet-um10
rdc485Enet-um10
Making Industrial Data Flow Like Water ... Safely, Silently, & Sanely
USA & Singapore
www.robustdc.com
PS/(MAIN)
Isolated
0v-
Rx/485
Bk/485
3. Isolation
2.5 KV optical isolation between RS-485
port and network port (RJ45)
2.5 KV galvanic isolation between RS-485
port, RJ45 Port and the power supply 8 1
(i) Go to the dos prompt. For normal operation, the Rdc485Enet has
8 jumpers installed on board to terminate
(ii) Use the ARP command to set the and bias the RS-485 interface. These are
desired IP address using the MAC only removed when more than two units of
address of the unit, which is printed on rdc485Enet are connected to the same RS-
the product label. 485 wire pair. For example, if 4 units of
Rdc485Enet are connected to a wire pair,
For example, with a MAC address of then at least 2 of them must have all TT &
00-40-9d-23-62-03 and a desired IP of RT jumpers removed (see the application
192.168.2.33, the command is: note for details).
For DOS systems, Note: The unit can be selected for 2-wire or
Arp –s 192.168.2.33 00-40-9d-23-62- 4-wire communication mode using the 2w &
03 4w jumper.
Device Hub
3. Grounding
Straight-through cable
TX+ 1 1 RX+
It is also critical that the signal ground be
TX- 2 2 RX-
properly connected. If a 5th ground wire is
unavailable, then the signal ground should
RX+ 3 3 TX+ be connected to the nearest device’s digital
ground or the shield drain wire. The unit will
RX- 6 6 TX-
be damaged over time if this ground is not
Fig. 1. Straight-through connection properly connected.
4. Jumper settings
Device PC
Crossover cable Each RS-485 segment requires a
TX+ 1 1 TX+
terminating resistor at each end. The
TX- 2 2 TX- rdc485Enet assumes that the cable has a
characteristic impedance of 120 Ohms.
RX+ 3 3 RX+ Therefore a RS-485 system will require at
RX- 6 RX-
least 2 terminating resistors enabled (see
6
the application note for details).
Fig. 2. Cross-Over Connection
The biasing resistors will help to pull the
wire pairs to a known state. Do take note
Note: A pair of twisted wires must be used however, that biasing voltages among
to connect a set of transmitter pins to their different vendors could be different. Hence
corresponding receiver pins. DO NOT use a the rdc485Enet has the option to disable
wire from one pair and another wire from a the biasings if required.
different pair.
Below is a drawing of the rdc485Enet that
2. Serial Connections shows the location of the jumpers for the
RS-485. Those that are labeled “B” are the
In 4-wire mode, the master device transmits bias jumpers, while those labeled “T” are
on the transmit wire pair to the receive the terminating resistors.
terminals of ALL slave device. The “T+” and
“T-“terminals of the master should be
connected to the “R+” and “R-“ terminals of
all the slaves respectively. All slave devices
will share a common receive wire pair to
respond to the master device. The “T+” and
TB+
RB+
4W
2W
RB-
TT
RT
2W
RB-
4W
TB-
RT
loop.
TT
on on on on on on off on
On the Rdc485Enet, the removable
terminals are labeled as “T+”, “T-“, “R+”, “R-
“, “G”. Due to space limitations, only the Shorting enables the terminating/biasing
transmit signals are echoed on the top while unshorting disables them. By default,
terminal as “D+”, “D-“, “Gnd”. If 2-wire mode all terminations and biasings are enabled.
is selected, only T+, T- and Gnd on the
removable terminals will work. Note: Either 4W (default) or 2W should be
shorted at one time.
•
EN 50 035
Embedded web server with support for EN 50 022 - 15mm