Toepc71061776 Quick Setup

The document provides technical specifications and installation guidelines for the HV600 series drives, including safety procedures and wiring configurations. It includes details on motor specifications, voltage ratings, and recommended components for installation. Additionally, it emphasizes the importance of following the Installation & Primary Operation manual for proper setup.

Uploaded by

sergio rivero
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
35 views4 pages

Toepc71061776 Quick Setup

The document provides technical specifications and installation guidelines for the HV600 series drives, including safety procedures and wiring configurations. It includes details on motor specifications, voltage ratings, and recommended components for installation. Additionally, it emphasizes the importance of following the Installation & Primary Operation manual for proper setup.

Uploaded by

sergio rivero
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

4

HV60UXXXXCVA 18mm

HV60UXXXXCVAA-AAAAHA
MX X.X~X.X N•m 10mm
X.Xmm

HV
5.5mm
60
0D
RIV
E
https://www.yaskawa.com/hv600qsp1

HV600
ON-SITE
VIDEO
TOE TOE TOE
PC 7106 PC7106 PC
1732 1776 7106
1789
-92
(Recommended) *1*2 (Recommended) *1*2 (Recommended) *1*2
Read and follow the safety and installation procedures in the Installation & Primary Operation (TOEPC71061732)
R/L1, S/L2, T/L3 R/L1, S/L2, T/L3
manual packaged with the drive. U/T1, V/T2, W/T3
14 - 8 (14) N/A
U/T1, V/T2, W/T3
14 - 8 (8) N/A R/L1, S/L2, T/L3 8 - 2/0 (4) LCA4-56-L

2011 2031
-, +1 14 - 8 (14) N/A -, +1 14 - 8 (8) N/A U/T1, V/T2, W/T3 8 - 2/0 (3 or 2) LCA4-56-L/LCA2-56-Q
2075

1 14 - 8 (12) LCA10-14-L 14 - 8 (10) LCA10-14-L -, +1 8 - 2/0 (2) LCA2-56-Q

R/L1, S/L2, T/L3 14 - 8 (12) N/A R/L1, S/L2, T/L3 14 - 4 (8) N/A 8 - 2/0 (6) LCA6-56-L

≥ ≥
U/T1, V/T2, W/T3 14 - 8 (10) N/A U/T1, V/T2, W/T3 14 - 4 (6) N/A R/L1, S/L2, T/L3 8 - 2/0 (3 or 2) LCA4-56-L/LCA2-56-Q
2017

VOLTS VOLTS AMPS AMPS


HP
Induction Motor Nameplate

AMPS
RPM
DUTY
0.75
2.8
1765
Cont

40
VOLTS 230
HERTZ 60
3 PH
HP
Induction Motor Nameplate

AMPS
RPM
DUTY
0.75
2.8
1765
Cont

40
VOLTS 230
HERTZ 60
3 PH

-, +1 14 - 8 (10) N/A -, +1 14 - 4 (6) N/A U/T1, V/T2, W/T3 8 - 2/0 (2) LCA2-56-Q

14 - 8 (10) LCA10-14-L 14 - 4 (8) LCA8-14-L 2088 -, +1 8 - 2/0 (1) LCA1-56-E

R/L1, S/L2, T/L3


R/L1, S/L2, T/L3 14 - 8 (10) N/A 14 - 4 (4) N/A 8 - 2/0 (6) LCA6-56-L
U/T1, V/T2, W/T3

≥ ≥
2059 R/L1, S/L2, T/L3
U/T1, V/T2, W/T3 14 - 8 (8) N/A -, +1 14 - 4 (4) N/A 8 - 2/0 (1/0) LCA1/0-56-X
U/T1, V/T2, W/T3
HP HP HERTZ HERTZ
2024
Induction Motor Nameplate Induction Motor Nameplate
3 PH
3 PH
HP 0.75
HP 0.75
AMPS 2.8 VOLTS 230
AMPS 2.8 VOLTS 230
RPM 1765 HERTZ 60
RPM 1765 HERTZ 60
DUTY Cont
DUTY Cont
40
40

-, +1 14 - 8 (8) N/A 14 - 4 (6) LCA6-14-L 2114 -, +1 8 - 2/0 (2/0) LCA2/0-56-X

14 - 8 (10) LCA10-14-L 8 - 2/0 (6) LCA6-56-L

HV60UXXXXCVA
CIPR-HV60UXXXXCVAA-AAAAHA AC3PH 200-240V (Recommended) *1*2 (Recommended) *1*2 (Recommended) *1*2

Uin AC3PH 380-480V


R/L1, S/L2, T/L3 R/L1, S/L2, T/L3

Uin (nameplate)
14 - 8 (14) N/A R/L1, S/L2, T/L3 14 - 8 (10) N/A 14 - 4 (4) N/A
U/T1, V/T2, W/T3 U/T1, V/T2, W/T3
+10% MAX

-15% MIN
4005
L1 4008 -, +1 14 - 8 (14) N/A U/T1, V/T2, W/T3 14 - 8 (8) N/A -, +1 14 - 4 (4) N/A
4027
L2
L3 50/60Hz 14 - 8 (14) LCA10-14-L -, +1 14 - 8 (8) N/A 14 - 4 (6) LCA6-14-L

R/L1, S/L2, T/L3


14 - 8 (14) N/A 14 - 8 (10) LCA10-14-L R/L1, S/L2, T/L3 8 - 2/0 (4) LCA4-56-L
U/T1, V/T2, W/T3

4011 R/L1, S/L2, T/L3


-, +1 14 - 8 (14) N/A 14 - 8 (8) N/A U/T1, V/T2, W/T3 8 - 2/0 (3 or 2) LCA4-56-L/LCA2-56-Q
U/T1, V/T2, W/T3 4077
14 - 8 (12) LCA10-14-L 4034 -, +1 14 - 8 (8) N/A -, +1 8 - 2/0 (2) LCA2-56-Q

R/L1, S/L2, T/L3 14 - 8 (14) N/A 14 - 8 (10) LCA10-14-L 8 - 2/0 (6) LCA6-56-L

2 U/T1, V/T2, W/T3 14 - 8 (12) N/A


R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
14 - 4 (8) N/A R/L1, S/L2, T/L3 8 - 2/0 (2) LCA2-56-Q
4014
IP55/UL Type 12 -, +1 14 - 8 (12) N/A 4040 -, +1 14 - 4 (6) N/A U/T1, V/T2, W/T3 8 - 2/0 (1) LCA1-56-E
? 14 - 8 (10) LCA10-14-L 14 - 4 (8) LCA8-14-L -, +1 8 - 2/0 (1) LCA1-56-E
+40 °C
(104 °F) 95 RH R/L1, S/L2, T/L3
14 - 8 (10) N/A
R/L1, S/L2, T/L3
14 - 4 (6) N/A 8 - 2/0 (6) LCA6-56-L
U/T1, V/T2, W/T3 U/T1, V/T2, W/T3
Pollution

%
4021 4052
Degree 2 -, +1 14 - 8 (10) N/A -, +1 14 - 4 (4) N/A R/L1, S/L2, T/L3 8 - 2/0 (1/0) LCA1/0-56-X

III
14 - 8 (10) LCA10-14-L 14 - 4 (8) LCA8-14-L U/T1, V/T2, W/T3 8 - 2/0 (2/0) LCA2/0-56-X
-10 °C 4124
(14 °F) 0 RH ≤ 1000 m*1 -, +1 8 - 2/0 (2/0) LCA2/0-56-X

(3281 ft) • 10 Hz to 20 Hz: 8 - 2/0 (4) LCA4-56-L


1 G (9.8 m/s², 32.15 ft/s²) Overvoltage
*1 For use with Panduit Corp. heat-shrinkable tubing HSTT series or an equivalent UL-recognized-heat shrinkable tubing rated 600 V minimum.
• 20 Hz to 55 Hz: Category 3 *2 Refer to the Installation & Primary Operation (TOEPC71061732) for possible Panduit Type P and Type S crimp terminal alternatives.
2011 to 2031, 4005 to 4034:
0.6 G (5.9 m/s², 19.36 ft/s²)
2046 to 2114, 4040 to 4124: Install one of the types of short circuit protection devices listed here to comply with UL 508C.
0.2 G (1.96 m/s², 6.43 ft/s²) Semiconductor protective type fuses are recommended, but the tables also show alternative short circuit protection devices.
*1 Derate the output current by 1% for each 100 m (328 ft) to install the drive in altitudes between 1000 m to 4000 m (3281 ft to 13123 ft).
Refer to the Technical Reference (SIEPC71061732) for derating information.
2011 2017 2024 2031 2059 2075 2088 2114

3 *1
FWH-40B FWH-45B FWH-80B FWH-125B FWH-125B FWH-175B FWH-200B FWH-225A FWH-225A

17.5 25 40 50 80 100 125 150 200

25 40 60 75 110 125 175 200 250

36030M71 36030M71 36050M72 36050M72 36100M73 36100M73 36150M74 36150M74 36150M74

3
) 3056 3056 3056 3056 5520 5520 5520 5520 5520

x2
x2
4005 4008 4011 4014 4021 4027 4034 4040 4052 4077 4124

FWH-25A14F FWH-30A14F FWH-40B FWH-45B FWH-60B FWH-80B FWH-100B FWH-125B FWH-150B FWH-200B FWH-225A FWH-225A FWH-225A

*1
8 12 17.5 20 35 45 60 70 90 110 125 150 200

x2 15 15 25 35 50 60 80 100 125 150 175 225 300

x2 36030M71 36030M71 36030M71 36030M71 36030M71 36050M72 36050M72 36100M73 36100M73 36100M73 36100M73 36150M74 36250M75*2

3056 3056 3056 3056 3056 3056 3056 5520 5520 5520 5520 5520 5520
When you use non-metric hardware to install the drive, use Type B narrow washers or equivalent and make sure that the size of the screw head and washer are applicable 3
) 3056 3056 3056 3056 3056 3056 3056 5520 5520 5520 5520 5520 5520
for your drive before installation.
*1 Class T fuses are fast-acting (non-time-delay) only. You can substitute a Class J time-delay fuse for a Class J non-time-delay fuse.
*2 The MCP part number for model 4124 is JLLxxxxxxxx.

HV600 Quick Setup Procedure TOEPC71061776D Published in Japan Sheet 1


5 9
3 PHASE INVERTER DUTY AC INDUCTION MOTOR NAMEPLATE EXAMPLE
MODEL XX 123AAAA123XX-X0 X FRAME 123AX Home Menu
POLES X ENC XXX CODE X DES A TYPE ABC INS X0
FL FL A
VOLTS XXX RPM
XXXX AMPS
XX/XX
MAX TEMP.
SF 1.0 DUTY CONT
AMB °C
XX SENSORS
T-STATS
SERIAL N.L. AMPS XX.X/X.X
MAX S.E. O.S.E. ROTOR Parameters Parameters
RPM
4200 BRG. 309 BRG.
XXX WK²
X.X A Initialization Parameters E1 V/f Pattern for Motor 1
B Application E2 Motor Parameters
HZ HP RPM
TORQUE VOLTS AMPS C Tuning
(LB FT) (HIGH CONN) (HIGH CONN) d References
E Motor Parameters
1 - 0 XX.X - XX.X F Options
Back Home Back Home
60 XX XXXX XX.X XXX XX.X
120 XX XXXX XX.X XXX XX.X
OHMS
PH. R1: .XXX R2: .XXX X1: X.XX X2: X.XX XM: XX.X
Parameters Parameters Parameters
P/N XXXXXXX Motor Rated Current (FLA) Motor Rated Current (FLA)
E2-01 40.0 (40.0)A
Motor Rated Slip
E2-01
A
E2-02 1.700 (1.700)Hz 0040.0 A Entry Accepted
Motor No-Load Current Default :40.0A
E2-03 9.2 (9.2)A Range :4.0~80.0
Back Home Back Home

10
Parameters Parameters
HAND HAND Frequency Reference HAND Frequency Reference
Home S5-05
0
000.00 Hz S5-05
1
000.00 Hz
R/L1
S/L2

4 (KPD)
T/L3

Default : 0.00 Hz Default : 0.00 Hz


Range : 0.00~400.00 Range : 0.00~400.00

IM Home Min/Max Home Min/Max

Parameters
Refer to the Technical Reference HAND

(SIEPC71061732) for information HAND


(KPD)
10.00
about GFCIs. Entry Accepted 10.00
10.00
(KPD)

10.00

/T1
U/T1 R/L1 U/T1 Cable tray
Line

R/L1
Motor

U/T1
B
READY
L1 V/T
R/L1 V/T2 W/T3 S/L2 T/L3 V/T2 W/T3
OR S/L2 T/L3 V/T2 W/T3
S/L2 T
T/L3

Conduit or
shielded motor Spacing per local electrical codes
cable

7 A
Parameters Parameters Parameters Parameters
C Tuning H1 Digital Inputs Drive Node Address Communication Speed Selection
d References H2 Digital Outputs H5-01 H5-02
E
F
Motor Parameters
Options
H3
H4
Analog Inputs
Analog Outputs 1F 3
H Terminal Functions H5 Serial Communication Default : 1F 9600 bps
L Protection Functions H7 Virtual Inputs / Outputs Range : 0~FF Default : 3
Back Home Back Home Back Default Min/Max Back Default

Set to unique node (MAC) Set to your network speed


address for your network (Hex)

8
Parameters Parameters Parameters Parameters
Communication Protocol Selection BACnet Device Obj ID LOW BITS BACnet Device Obj ID HIGH BITS Communication Parameters Reload
H5-08 H5-14 H5-15 H5-20 1
3 0001 00 Reload Now
BACnet Default : 0001 Default : 00
Default : 0
Default : 0 Range : 0000~FFFF Range : 00~3F
Back Default Back Default Min/Max Back Default Min/Max Back Default

Set to 3: BACnet Set to 1: Reload Now


READY Set the Device Object ID numbers together to make a
unique value for your installation (Hex)

TB6
AC D+ D-
OFF ON

EF3 OFF ON
External Fault (terminal S3)
2017/01/01 10:00 READY
Reset

Signal Comm. Comm.


HV600 Quick Setup Procedure TOEPC71061776D Sheet 2 Ground input/ input/
output + output -
U
U/T1
R/L1 V
V/T2 M S1 MFDI 1 Forward RUN (2-Wire) H1-01 | 40
S/L2 W
T/L3 HV600 W/T3 S2 MFDI 2 Not Used H1-02 | F
External Fault (NO-
S3 MFDI 3 H1-03 | 24
Always-Coast)
DC Power +1
Supply Input S4 MFDI 4 Photocoupler Fault Reset H1-04 | 14
-
ON ON 24 V, 6 mA
H1-01 Multi-Step Speed
SW1 SW2 S5 MFDI 5 H1-05 | 3
Reference 1
Fwd RUN (2-Wire) S1
OFF OFF Multi-Step Speed
MFDI 6 H1-06 | 4
Reference 2
EMC Filter
S2 Jog Reference
H1-02 S7 MFDI 7 H1-07 | 6
Selection
MFDI power 0 V - -
S3
H1-03 MA SC MFDI common - -
24 V, 150 mA maximum

C H1-04
S4 MB
Fault Relay
Output
MFDI power +
24 VDC
- -

MC H1 Safe disable input 1 - -


TB1 S5
Photocoupler
H1-05 H2 Safe disable input 2 24 V, 6 mA - -
M1 HC Safe disable common - -
Default:
≤ 0.4 mm S6 H2-01 M2 During Run Frequency setting
H1-06 10.5 V (20 mA maximum) - -
power supply
(0.01 in)
0 V ~ 10 V/100%
5.5 mm (0.21 in) S7 M3 A1 MFAI 1 Frequency Reference H3-01 | 0
≤ 2.5 mm (0.1 in) H1-07
H2-02 M4 4 mA ~ 20 mA/100%
0 mA ~ 20 mA/100%
TB2

SN A2 MFAI 2 Frequency Reference H3-09 | 2


M5
TB3 AC Common 0V - -
SC H2-03 M6
DC Out
Connect
24 V PS - - -
SP SINK shielded cable
150 mA
+24 V Fault (N.O) Fault
+P Fault relay output 30 VDC, 10 mA ~ 2 A
S1 250 VAC, 10 mA ~ 2 A Fault (N.C) Fault
E (G) Minimum load: 5 V, 10 mA
V Analog Input FM H4-01 Common - -
Voltage/Current
[A1: V, A2: I] - + MFDO During Run H2-01 | 0
I FM
+V
A1 A2 0-10 V 30 VDC, 10 mA ~ 2 A
H3-01
A1 0-10 V MFDO 250 VAC, 10 mA ~ 2 A Zero Speed H2-02 | 1
S5 V I Minimum load: 5 V, 10 mA
H3-09 AM
A2 4-20 mA MFDO Speed Agree 1 H2-03 | 2
AM H4-04
FM
AC AC - + MFAO 1 0 V ~ 10 V/0% ~ 100% Output Frequency H4-01 | 102
AM
MFAO 2 4 mA ~ 20 mA Output Current H4-04 | 103
TB4 DC 0V 0V 0-10 V
24 V PS (120 , 1/2 W) AC Common 0V - -
700 mA
PS External power supply 24 V (150 mA maximum) - -
OFF ON E (G)
D+ External 24 V PS input 21.6 VDC ~ 26.4 VDC, 700 mA - -
S2
D- External 24 V PS
RS-485 AC 0V - -
ground
TB5 AC
Communication + APOGEE FLN, BACnet, - -
H1 0V MEMOBUS/Modbus, Metasys N2
RS-485
H2 Communication - 115.2 kbps maximum - -
TB6 TB7
HC AC Common 0V - -

SN

Parameters
TB1 Run Command Selection 1
From HOA Keypad
Parameters Cable
b1-02 1
Frequency Reference Selection 1 TB1 shield Digital Input
Cable
b1-01 0 shield Black: Default : 7
Keypad
Default : 1
_ Input
4 ~ 20 mA (2)
Back Default

Analog input voltage/


Back Default + 2-Wire Control 3-Wire Control
current selection
(Factory Default) (A1-03 = 3330)

TB2
[A1: V, A2: I]
TB3 TB3
TB3 Stop Start
From External Terminals
Switch Switch

TB2
Parameters
Frequency Reference Selection 1

Install Wire Link (AC-SN)


Forward

When Using Transducer


b1-01 1 0 ~ 10 VDC

Use for momentary contacts


Use for maintained contacts
Analog Input
Default : 1 Normally
TB1 Normally Open
Analog monitor voltage/ Back Default Cable
Closed
current selection [V] shield
TB1
_
Reverse
TB4
+
Brown

D+ D- Termination resistor +
or Red TB4 TB4
+Power (1)
TB2

2-Wire/4 ~ 20 mA
Potentiometer 2 kΩ 4 ~ 20 mA Transducer

HV600 Quick Setup Procedure TOEPC71061776D Sheet 3


H

EF3
External Fault (terminal S3)

HAND
HAND
2017/01/01 10:00
Reset

READY
(KPD)

READY
You have access to the paper copy of the manual that was packaged with the drive. This manual lists all drive

Parameters
HAND HAND Frequency Reference
Home
(KPD)
S5-05
0
000.00 Hz Installation & Primary Operation https://www.yaskawa.com/toepc71061732

Default : 0.00 Hz
Range : 0.00~400.00
Home Min/Max PDF download

Parameters Parameters
HAND Frequency Reference You want to use your smartphone or tablet and use the embedded help to look up the full complement of causes
and solutions to all drive faults and alarms.
S5-05
1
000.00 Hz Entry Accepted
Default : 0.00 Hz
Range : 0.00~400.00
Home Min/Max

DriveWizard Mobile App https://www.yaskawa.com/dwm


Home
HAND
(KPD)

10.00
(KPD)

READY
10 Hz
10.00 App download

You want to download a PDF of the manual to your smartphone or tablet.


This manual lists the full complement of causes and solutions to all drive faults and alarms and also includes
detailed information about drive maintenance, wiring, and programming.

A1 Initialization d1 Frequency Reference H1 Digital Inputs n1 Hunting Prevention T0 Tuning Mode Selection
A2 User Parameters d2 Reference Limits H2 Digital Outputs n3 High Slip/Overexcite Braking T1 InductionMotor Auto-Tuning
d3 Jump Frequency H3 Analog Inputs n7 EZ Drive T2 PM Motor Auto-Tuning
TOEPYAIXXX001.pdf
b1 Operation Mode Selection d4 Freq. Ref. Up/Down & Hold H4 Analog Outputs n8 PM Motor Control Tuning T4 EZ Tuning

b2
DC Injection Braking and Short
d6 Field Weakening H5 Serial Communication
Drive
Circuit Braking Maintenance & Troubleshooting XXX00 https://www.yaskawa.com/toepyaihv6001
Manual
b3 Speed Search d7 H7 Virtual Inputs/Outputs o1 Keypad Display Y1 Application Basics XXX00

b4 Timer Function o2 Keypad Operation Y2 PID Sleep and Protection


XXX00
b5 PID Control E1 V/f Pattern for Motor 1 L1 Motor Protection o3 Copy Keypad Function Y4 Application Advanced
PDF download
b8 Energy Saving E2 Motor 1 Parameters L2 Power Loss Ride Through o4 Maintenance Monitors Y9 Network Multiplex Options
XXX00

E3 V/f Pattern for Motor 2 L3 Stall Prevention o5 Log Function YA Preset Setpoint
C1 Accel & Decel Time E4 Motor 2 Parameters L4 Speed Detection YC Feedback Features
C2 S-Curve Characteristics E5 PM Motor Settings L5 Fault Restart YF PI Auxiliary Control
C3 Slip Compensation E9 Motor Setting L6 Torque Detection
C4 Torque Compensation L7 Torque Limit S1 Dynamic Noise Control

C5 Auto Speed Regulator (CSR) F6 Communication Option L8 Drive Protection S2 Sequence Run Timers

C6 Carrier Frequency F7 Ethernet Options L9 Drive Protection 2 S3 PI2 Control


S5 HAND/OFF/AUTO Operation
S6 Protection
Comments or questions about this document? Please consider following us on social media:
Fill out our online form:
www.youtube.com/yaskawayea
A1-06 | Application Preset 0 | No Preset Selected b3-24 | Speed Search Method Selection 2 | Current Detection 2 E1-01 | Input AC Supply Voltage
b1-01 | Frequency Reference Selection 1 1 | Analog Input C1-01 | Acceleration Time 1 30.0 s E2-01 | Motor Rated Current (FLA) www.linkedin.com/company/18822
Mobile App Product Manuals
b1-02 | Run Command Selection 1 7 | AUTO Command + Term Run C1-02 | Deceleration Time 1 30.0 s L5-01 | Number of Auto-Restart Attempts 0 | No Restart Attempts

b1-03 | Stopping Method Selection 1 | Coast to Stop d2-01 | Frequency Reference Upper Limit 100.0% L5-04 | Interval Method Restart Time 10.0 s
www.twitter.com/yaskawa
b3-01 | Speed Search at Start Selection 0 | Disabled d2-02 | Frequency Reference Lower Limit 0.0% S1-01 | Dynamic Noise Control 1 | Enabled

or
Email us: [email protected]
Call us: 1-800-YASKAWA (927-5292)
DriveWizard® Mobile •PDFs www.yaskawa.com/DRV-F-0006
2121 Norman Drive South
Commissioning •Online HTML5-Searchable
Waukegan, IL 60085
Smartphone App •Manuals App
USA
https://www.yaskawa.com/dwm https://www.yaskawa.com/hv600manuals
© 2020 YASKAWA Electric Corporation
DriveWizard is a registered trademark of Yaskawa MANUAL NO. TOEP C710617 76D <3>-1
America, Inc. and is registered in the U.S. Patent and Published in Japan October 2022

HV600 Quick Setup Procedure TOEPC71061776D Sheet 4