MV Skid Compact DS 1.
Turn-key solution.
Fastest connection with HEMK.
Installation cost reduction.
Flexible plant distribution.
MV Skid Compact
Power range @ 40 °C 1910 kVA - 4390 kVA
RATINGS
Power range @ 50 °C 1775 kVA - 4075 kVA
6.6 kV / 11 kV / 13.2 kV / 13.8 kV / 15 kV / 20 kV / 22 kV / 23 kV
MV voltage range
/ 25 kV / 30 kV / 33 kV / 34.5 kV
LV voltage range 600 V /615 V /630 V / 645 V / 660 V / 690 V
Transformer cooling ONAN
Transformer vector group Dy11
Protection relay for pressure, temperature (two levels) and gassing
MEDIUM Transformer protection Monitoring of dielectric level decrease
VOLTAGE PT100 optional
EQUIPMENT Transformer index of protection IP54
Transformer losses IEC standard or IEC Tier-2
Oil retention tank Galvanized steel. Integrated with hydrocarbon filter. Optional
Switchgear configuration Double feeder (2L)
Switchgear protection Circuit breaker (V)
Switchgear short circuit rating [1] 16 kA 1 s (optionally 20 kA or 25 kA)
Switchgear IAC [1] A FLR 16 kA 1 s
LV-MV connections Close coupled solution (plug & play)
CONNECTIONS LV protection Motorized circuit breaker included in the inverter
HV AC wiring MV bridge between transformer and protection switchgear prewired
Ambient temperature range [2] -25 °C… +50 °C (T > 50 °C power derating)
ENVIRONMENT Maximum altitude (above sea level) [1] Up to 1000 m
Relative humidity 4% to 95% non condensing
AUXILIARY User cabinet Integrated in the inverter (by default). Optionally, LV cabinet in the skid
SERVICES UPS system [1] 1 kVA/1 kW (12 minutes). Optional
Safety mechanism Interlocking system
OTHER EQUIPMENT
Fire suppression system Transformer oil tank retention accessory. Optional
STANDARDS Compliance IEC 62271-212, IEC 62271-200, IEC 60076, IEC 61439-1
NOTES [1] Consult with Power Electronics for other options.
[2] For lower temperatures, consult with Power Electronics.