Manual de Instalación y Mantenimiento Cxaj065
Manual de Instalación y Mantenimiento Cxaj065
TÍTULO
Especialidad: P
MANUAL DE INSTALACIÓN Y
PROVEEDOR/N° DE DOC. MANTENIMIENTO CXAJ065
TAMAÑO: A4
-
PROVEEDOR/N° DE OBRA
ESCALA: N/A
PK-0616
REEMPLAZA A: DOC. REV.
HOJA: 1 de 63 TRA-MNL-P-MOP-0001
- N° CIT A
Installation, Operation and
Maintenance
690134220001
Safety Warning
Only qualified personnel may install and maintain the unit. The installation, start-up and maintenance of heating,
ventilating and air-conditioning unit will be hazardous, and the operator shall have specific knowledge and training.
Improper installation, adjustment or change of the unit by an unqualified person will result in death or serious injury.
When operating the unit, pay attention to all precautions in the documents and the tags and labels attached to the
unit.
Nomenclature ………………………………………………………………………………………… 5
Dimensions …………………………………………………………………………………………… 6
Pre-Start-up ………………………………………………………………………………………… 22
Troubleshooting …………………………………………………………………………………… 50
Maintenance ……………………………………………………………………………………… 60
2
General Information
This manual is the customer property, which shall be used with the unit. Please put it back to the tecŠical information
bag after the completion of the work, and keep it properly.
Please read this manual carefully before installing the air conditioning unit, and install and maintain the unit according
to this manual to ensure the normal and reliable operation of the unit. Installation of the air conditioning unit must be
completed by the professional designated by Trane Company. If the installation or maintenance is done by unqualified
personnel or fails to comply with the requirements of this manual, the manufacturer shall not be held responsible.
This manual does not purport to cover the differences among various units or all problems that may be encountered
in the installation, and impossibly provides guidance for all possibilities in the installation. If you want to get more
information or face any special problem that is not explained in this manual, please contact your local Trane sales
office.
This manual contains a Checklist for Installer to Apply for Commissioning, and you may use the checklist to check
and confirm whether all necessary installation steps are completed. Reading the checklist does not mean reading the
contents of this manual, and you should read this manual carefully before the installation.
Dangers, Warnings and Cautions can be found in different parts throughout this manual. In order to ensure personal
safety and normal operation of the unit, please read these contents carefully and follow them.
Danger: Indicates a potentially hazardous situation which, if ignored, could result in death or serious
injury.
Warning: Indicates a potentially hazardous situation which, if ignored, could result in minor or moderate
Caution: Indicates a potential damage to the unit which, if ignored, could result in damage to the unit
Warning
Lock the power supply and cutoff switch of the air conditioning unit at the disconnected state before installation or
maintenance in order to avoid the personal death or injury caused by electrical shock or contact with moving parts.
All installation procedures of the air conditioning unit must comply with the national, provincial and local regulations.
Refrigerant Warning
Please do not use substandard refrigerants, refrigerant substitutes or refrigerant additives. Improper use method
or use of substandard refrigerants, refrigerant substitutes or refrigerant additives will cause damage to the air
conditioning unit and various safety risks. Please select acceptable refrigerants or call 8008208676 to purchase
acceptable refrigerants. All technical personnel using refrigerants must have the qualifications, be familiar with and
strictly follow the relevant technical requirements, laws and regulations for use, handling, recovery and recycling of
refrigerants.
3
Safety Precautions
In order to avoid electrical shock or fire, and other • Never sit on the direct air duct at any time. Sitting on
injuries that may be caused, the following rules should the direct air duct is not conducive to your health and
be kept in mind and strictly adhered to: safety.
• The unit power supply and the electric heating power • In order to prevent the relief valve failure due to
supply must be equipped with an electric leakage calcification, fouling and blockage, the user should
protection device, and must be connected to the check the valve at least once every month. If the local
grounding wire; otherwise, injury or even death and water quality is poor, the check interval should be
other accidents may occur if unprotected. shortened appropriately. Please promptly replace
the relief valve with a new valve with reliable quality
• The specification of the power wire shall meet the
if blockage, corrosion, manual operation failure or
requirements, otherwise there may be accidents
damage to manual pressure relief handle is found.
related to circuit safety.
• A heating device or other heat source shall not
• Please use a fuse appropriate for the current intensity.
be arranged under or near the air conditioner. The
• Do not use any temporary substitute, such as a piece
machine body may be deformed by heating.
of wire, which not only may damage the unit itself,
• Objects, such as sticks, sands or gravels, shall be
but also may cause fire.
avoided from entering the air inlet grid or air outlet
grid. Fans running at high speed are very dangerous,
and children should be kept away from them.
• Never block or cover the air inlet grid or air outlet
grid. If such case happens, it may reduce the
Using a piece of wire performance and affect the normal operation
may cause fire. capacity.
Ok!
• Whenever you operate the machine, make sure the
air filter net is installed correctly. Otherwise, dirt
may enter the internal running position and cause
• In order not to exceed the capacity of the power
damage.
meter and the protector, please do not simultaneously
• When cleaning the machine, do not sprinkle water
switch on the electric heating for the air conditioner
directly on the machine, which may lead to electric
and the electric heating for the water tank. The use of
shock.
all types of electrical appliances shall be coordinated.
• Before maintenance, make sure the unit is powered
• Please connect the wires in strict accordance with the
off to prevent electric shock.
wiring diagrams in this manual. Improper wiring or
• When the unit is not used for a long period, you
artificial change of wiring will result in unit failure and
should cut off the power supply and drain the water
damage, or endanger personal safety.
from the water tank. After the water is drained, do
• The condensate water from the indoor and outdoor
remember to close the drain valve. If the water tank
units must be drained according to the requirements.
is under frozen conditions for a long time, it may be
Improper drainage of the condensate water may lead
damaged.
to adverse consequences.
4
Nomenclature
Model: C X A J 0 6 5 5 B
1 2 3 4 5 6 7 8 9
Additional options: 1 H S D R A
10 11 12 13 14 15
Maintenance code: C X A J 0 6 5 5 B 1 H S D R A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Digit 1 C= Chiller
Digit 2 X=Heat pump G=cooling only
Digit 3 A=air cooled
Digit 4 J= modular type
Digit 5,6,7 Model (cooling capacity)
045 (45kW) 065 (65kW) 130 (130kW)
Digit 8 Voltage/Hertz/Phase
5=380V/50Hz/3PH
Digit 9 Design Sequence
B
Digit 10 Fan speed
1=single speed
Digit 11 Energy efficiency( unit type)
N=standard efficiency H=High efficiency
Digit 12 Controller
S=modular controller (units ≥2) U=unit controller (unit =1)
N=None
Digit 13 Service Sequence
D=4th time
Digit 14 Ambient temperature
R=Standard
Digit 15 Connector option
C=Without 2 pcs. of DN125 rubber connector
D= With 2 pcs. of DN125 rubber connectors
Digit 16 BMS interface
M=Modbus module N= NONE
Digit 17 Refrigerant charged
A=without 045 065 130 B=with
Digit 18 Option
A=None
B=Special option
T=leaving water control (digit 11 = N)
5
Dimensions
CXAJ045/065 (N/H type)
2155
WARNING ޅૐૐDŽඤDžఇऐፇ
HAZARDOUS VOLTAGE !
DISCONNECT ALL ELECTRIC POWER ऐ႙ ऐࡽ
INCLUDING REMOTE DISCONNECTS ఁᅭૐଉ KW ఁᅭඤଉ KW
BEFORE SERVICING.
ຕଉ ୁۉۨܮ ܂ገୁۉ ࠀ୲
Failure to disconnect power before
servicing can cause severe personal უऐA A A KW
injury or death.
უऐB A A KW
1987
ටᇵฅྨ. ༬ଳۙဣཥDŽዐࡔDžᆶ၌ࠅິ
DN125
ړ႐ۉة
613
1521 727
2038 927
2145 951
2020
2155
ޅૐૐDŽඤDžఇऐፇ
ऐ႙ ऐࡽ
ఁᅭૐଉ KW ఁᅭඤଉ KW
ຕଉ ୁۉۨܮ ܂ገୁۉ ࠀ୲
უऐA A A KW
უऐB A A KW
ۉᇸ: ۉუ V ೕ୲ 50 Hz ၎ຕ
ሎႹट၌უ૰: ֨ MPa ૐ֨ MPa
ૐඐୁଉ m3/h ૐ۳ୁଉ m3/h
ૐ؊࠺ଉ kg ሯำ dB(A) ऐፇዘଉ kg
1987
༬ଳۙဣཥDŽዐࡔDžᆶ၌ࠅິ
DN125
613
1521 1426
2038 1476
2145 1862
6
Performance Data
Performance data for Modular Air-cooled Chiller (Heat Pump) Unit (N Type)
Model CXAJ045 CXAJ065 CXAJ130 CGAJ045 CGAJ065 CGAJ130
Nominal cooling capacity kW 45 65 130 45 65 130
Cooling Input power kW 14.2 20.4 40.8 14.2 20.4 40.8
Operating current A 33.0 41.4 82.8 33.0 41.4 82.8
Nominal heating capacity kW 47 67 132 - - -
Heating Input power kW 15.0 20.2 40.4 - - -
Operating current A 33.4 41.4 82.8 - - -
Type Hermetically sealed scroll compressor
Quantity 只 2 2 4 2 2 4
1. The refrigeration capacity is measured in the conditions of water inlet at 12℃, water outlet at 7℃ and air inlet at the
ambient temperature of 35℃.
2. The heating capacity is measured in the conditions of water inlet at 40℃, water outlet at 45℃ and air inlet at the
ambient dry bulb temperature of 7℃ and the wet bulb temperature of 6℃.
3. CXAJ/CGAJ045 unit shall conform to the standard GB/T 18430.2-2008; CXAJ/CGAJ065/130 unit shall conform to the
standard GB/T 18430.1-2007.
7
Performance Data
TecŠical Parameter Table for Modular Air-cooled Chiller (Heat Pump) Unit (H Type)
Model CXAJ045 CXAJ065 CXAJ130 CGAJ045 CGAJ065 CGAJ130
Nominal cooling capacity kW 45 65 130 45 65 130
Cooling Input power kW 14.2 19.2 38.8 14.2 19.2 38.8
Operating current A 33.0 37.2 75.2 33.0 37.2 75.2
Nominal heating capacity kW 47 67 132 - - -
Heating Input power kW 15.0 19.4 39.2 - - -
Operating current A 33.4 41.4 82.8 - - -
Type Hermetically sealed scroll compressor
Quantity 只 2 2 4 2 2 4
1. The refrigeration capacity is measured in the conditions of water inlet at 12℃, water outlet at 7℃ and air inlet at the
ambient temperature of 35℃.
2. The heating capacity is measured in the conditions of water inlet at 40℃, water outlet at 45℃ and air inlet at the
ambient dry bulb temperature of 7℃ and the wet bulb temperature of 6℃.
3. CXAJ/CGAJ045 unit shall conform to the standard GB/T 18430.2-2008; CXAJ/CGAJ065/130 unit shall conform to the
standard GB/T 18430.1-2007.
8
Unit Installation
Hoisting
Please use a forklift or crane with proper tonnage to handle this unit to its installation location.
Hoisting method:
Installation location
• The unit must be installed on a flat and level plane;
• It is better to install the shockproof rubber cushion, which is arranged between the host unit
and its load to absorb vibration;
• In the installation, the drainage, ventilation and maintenance space as well as others shall
be considered. Refer to the installation space diagram for the recommended minimum
maintenance space;
• It is necessary to consider the bearing capacity of the building in the installation to arrange
the unit base
9
Unit Installation
≥1.2M
AIR IN AIR IN
WARNING WARNING
HAZARDOUS VOLTAGE ! HAZARDOUS VOLTAGE !
DISCONNECT ALL ELECTRIC POWER DISCONNECT ALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS INCLUDING REMOTE DISCONNECTS
BEFORE SERVICING. BEFORE SERVICING.
Failure to disconnect power before Failure to disconnect power before
servicing can cause severe personal servicing can cause severe personal
injury or death. injury or death.
য় ߢ য় ߢ
ᆶླۉ၃! ᆶླۉ၃!
ሞྼႪമൎᆶۉڦᇸ,Ԉઔᄫ੦ևݴ. ሞྼႪമൎᆶۉڦᇸ,Ԉઔᄫ੦ևݴ.
ሞྼႪമසࡕփൎۉᇸ,ࣷሰׯჹዘڦ ሞྼႪമසࡕփൎۉᇸ,ࣷሰׯჹዘڦ
ටᇵฅྨ. ටᇵฅྨ.
AIR IN
SERVICE
SPACE
610mm
≥1.2M
WATER OUTLET
Note: each CXAJ/CGAJ045/065 multi-module combination includes 8 units at most, and each CXAJ/CGAJ130 multi-
module combination includes 4 units at most. Direct return connection is not allowed.
10
Unit Installation
WATER
OUTLET
PUMP
WATER
INLET
Note: CXAJ/CGAJ045/065 single-module combination includes 8 reverse return connection units at most, and CXAJ/
CGAJ130 single-module combination includes 4 reverse return connection units at most.
WATER
OUTLET
PUMP
WATER
INLET
Note: CXAJ/CGAJ045/065 single-module combination includes 4 direct return connection units at most, and CXAJ/
CGAJ130 single-module combination includes 2 direct return connection units at most.
11
Unit Installation
Blind flange
The water pipe interface blind flange necessary for the installation of the end unit is show in the
diagram below:
18
8-
210
245
Name: blind flange
Material: No.20
Specification: 5", PN1.6
20
Water pipeline
• Clean all chilled water pipelines.
• connect the evaporator pipeline.
• Exhaust the air in the chilled water system at the highest point of this system.
• Install the pressure gauge, the thermometer and the valve in the water inlet and outlet pipes.
• Install the filter in the water inlet pipe of the evaporator.
• Install the balance valve and the flow switch at the water outlet.
Cautions
• If the washing the pipe with acid solvent, a temporary by-pass pipe shall be arranged beside
the unit for fear of damaging the evaporator.
• Never use the untreated or improperly treated system water for fear of damaging the
machine.
• Refer to Connection Diagram for Water System for the installation location of each typical
accessory on the water supply pipeline of the unit. The pipe components may vary with the
locations of connectors and water source.
• To avoid damaging the unit, do not reversely install the system water pipe. The water inlet
pipe must be connected to the water inlet connector marked with “water inlet”. The water
outlet pipe must be connected to the water outlet connector marked with “water outlet”.
• The exhaust valve shall be arranged at the highest point of the pipeline in order to exhaust
the air in the chilled water system.
• The water pressure of the evaporator shall not be more than 0.5 MPa (i.e. maximum working
pressure) for fear of damaging the parts and components on the chilled water side of the
unit.
• Before the final pipe connection of the unit, all external water supply piping systems shall
be thoroughly flushed. It is strictly prohibited to be mixed with sundry in the piping system,
otherwise our company will not be responsible for the consequences.
Connection of water pipeline
The circulating water pump must be installed on the water inlet pipe of the evaporator to ensure
that the internal pressure of the evaporator is positive pressure. Refer to Figure 1 for the installation
12
Unit Installation
6 (4) 6 (2)
6 (1) 1
9 3
6 (3)
5 2
Cautions
• All units must be equipped with the filters which can filter the particles with the diameter larger
than 1 mm to ensure that the impurities cannot enter the evaporator.
• Never use the untreated or improperly treated system water for fear of damaging the unit.
Otherwise, TRANE will not be responsible for the unit damage therefrom.
• After the installation of water pipeline is completed, please firstly close the shutoff valves 2 and 3,
open the shutoff valves 1 and 4, the open the water pump, and flush the debris in the water pipe
residual in the water pipe with water onto the filter; then close the shutoff valves 1 and 4, remove
the filter and cleanup the dirt on the filter, and reinstall the filter. Repeat the above operation till
there is no dirt on the filter. Therefore, the evaporator can be prevented from being blocked.
• The chiller water pipe must be insulted to prevent condensation. If the pipeline may be exposed
below 0 ℃, the pipeline must be equipped with the heating resistor.
• When the ambient temperature is below 16℃ in winter, do not cut off the power supply, and
preheat the unit 24 hours ahead of start-up, otherwise the compressor will be damaged.
13
Unit Installation
Feed-water Overflow
FCU FCU
Tree-way valve
Flow switch
Electric heater
Principle Description
1. In order to avoid pipe rupture caused by the excessive pressure inside the system pipeline
when the ambient temperature changes and prevent the pneumatic hammer from occurring
in the pipeline, a pressure water tank is added on the pipe system.
2. To avoid the internal pressure is too high or low inside the pipeline, a water compensation
valve and a drain valve are added. When the pressure is lower than 0.6 bar, the water
compensation valve will be automatically opened for water compensation; when the pressure
is higher than 5 bars, the drain valve will automatically open the drain pipe for drainage.
3. The water compensation pressure can be adjusted according to actual conditions.
14
Electrical Installation
Electrical Wiring
• Connect the power wire to the main terminal board (TB) of the distribution box for the unit.
• Connect the control panel with the main control board of the unit through the control panel
(indoor mounted) connecting cable. See pages 18-24.
• If the unit is not provided with the water pump, connect the control wire of the chilled water
pump to the corresponding terminal of the chilled water pump.
• Ground the unit, the chilled water pump motor (for the unit with water pump) and all devices
to be grounded.
• If the electric heater is provided, connect the power wire and the control wire to the terminal
TB2 of the electric heater.
• If the two-way valve of the fan coil is used for interlocking control, it is necessary to set SW2-
7(N Type) or SW1-7(H Type) to “ON” on the control board and connect the interlocking point
(dry contact) between the control box terminals 12(N Type) or 19(H Type) and U.
• Connect the flow switch between the control box connecting terminals U and 15 of the unit.
Warning
• To prevent injury or death, disconnect electrical power supply before completing wiring
connections to the unit.
Caution
• The terminals can be connected only through the copper conductors so as to avoid corrosion
or overheating. Refer to the electrical parameter table for the minimum current, the fuse
specifications and the electrical specifications of the motor.
Power Supply
Please refer to the wiring diagram on the cover plate of the control box for the unit. The installer
shall provide a power supply with correct voltage and a suitable breaker for the unit. The
variation of input power should be limited at ±10%.
Cautions
For the 380V~ unit adopts the scroll compressor, the phase reversing and loss protection
controller is installed which should be checked with electricity connection before start-up.
If the green light of the phase reversing and loss protection controller in the control box is on, it
means the phase sequence is right; red light being on means the phases of power wiring should
be exchanged; and the yellow light means lacking phase which need check with electricity
disconnection.
In any case that the phases are reversed or lacked, the unit will shut down its operation and
start-up automatically.
15
Electrical Installation
Electrical Data
Minimum
Full- Rated Rated Rated Rated
Rated Rated Rated Rated Minimum specification
load current current current current Recommended Maximum
Power current current current current circuit of copper
current of No.1 of No.2 of No.3 of No.4 fuse specification
Model Supply of No.1 of No.2 of No.3 of No.4 current of core wire
of water compressor compressor compressor compressor specification of fuse
(V/Hz/ph) fan fan fan fan unit diameter for
pump RLA RLA RLA RLA REC MFS
FLA FLA FLA FLA MCA power wire
FLA
mm2
CX(G)AJ1305 380/50/3 20.8 20.8 20.8 20.8 2.1 2.1 2.1 2.1 92.60 97.80 113.40 35
16
The following wiring diagrams are for reference only. The accompanied wiring diagrams shall prevail.
Wiring Diagram
Wiring Diagram CGAJ1305 (N Type)
N U V W 380Vac 3N~50Hz
(connected network and module mode)
3
TB1 220Vac RUN AL
1
U
MC1-1
OVC1-1 N
BK BK(L3)
M
WH WH(L2)
COMP 1-1
3~
RD RD(L1) MC2-1 MF1
MC1-2
MC1-2
OVC1-2 MC2-2 MF2
BK BK(L3) (14)
M MC1-1
MP
WH WH(L2)
COMP 1-2
3~ RFS
RD RD(L1) (11)
1
MF1 1 2 3 7 8 N 10 N 11
BK BK(L1)
M FAN
WH WH(L2)
COMP1
COMP2
RUN_OUT
AL_OUT
RUN_IN
MOTOR 1-1
PUMP
3~
M/FAN2
AL_IN
4WV1
HE/EV1
A-HAT
4WV2
H/FAN1
RD RD(L3)
N
N-COM
BK(L1) EN-SAVE
MC2-1 M FAN
OVC2-1 WH(L2) 3~ MOTOR 1-2 L
C H
BK BK(L3) BK HP2 BK
M RD(L3) SW1
HP2
WH W (L2) COMP 2-1 N YL LP2 YL
3~
RD R (L1) LP2
RD Microprocessor Control Board 15 FS
MC2-2 CON1 FLOW
OVC2-2 (Two Compressors) 16
BK BK(L3) CON2
OV-PUMP
M ADC_OD_C01
WH W (L2) COMP 2-2 WH
3~ Transformer SW2 OV-FAN OVC1-1 OVC1-2
RD R (L1)
OV-COMP1
OVC2-1 OVC2-2
MF2 OV-COMP2
BK BK(L1) BK HP1 BK
(L2) M FAN HP1
WH WH MOTOR 2-1 CN6 TH1 TH2 TH3 TH4 TH5 TH6
YL LP1 YL
3~ CN4 LP1
RD RD(L3) A BG
BK(L1)
M FAN
BK W(L2) MOTOR 2-2 connect with other units(correspond)
C 3~
WH B RFS R (L3)
RD A
TO CONTROL WIRING
power
MC Compressor Start Contactor EN-SAVE Run Output/Input RFS Phase Sequence Controller
Energy Saving/ 1-1 2-1
MF Fan Motor Contactor RUN-OUT/IN 2- Way Valve Interlock 4WV 4 Way Valve
Note:
CCH Crankcase Heater C/H Outer Cool/Heat Pump Setting
ControlBox
COMP Compressor OVC Compressor Overload/Overheat
1 Reserved control signal for controlling water pump and heating
Compressor Location
HT/EV1 Water Circuit Based FS Flow Switch
2 Pump Overload Switch(close) Connect 16 and U
Electrical Heating Control
A-HAT Plate Heat Exchanger Heater OVP Water Pump Overload 3 Water flow switch need connect between 15 and U
PUMP Water Pump OVF Fan Motor Overheat 4 DIP setting (sw1,sw2) according to IOM
H/FAN Fan Motor HP High Pressure Switch Factory Wiring 690134120001
17
N UV W 380Vac 3N̚50Hz
Wiring Diagram
CX(G)AJ 045/065 (N Type)
TB
220V
MC1OVC1 U
BK BK(L3)
WH WH(L2) M N
3~ COMP A-1
RD RD(L1)
5
MC1 4MV MP
MC2 OVC2
BK BK (L3) HT/EV MC2 MF AL
WH WH(L2) M (14)
3~ COMP A-2
RD RD (L1) RFS
(11) 1 2 3 4 5 6 13 14
1
AL_OUT
COMP
COMP
PUMP
BK MF
AL_IN
HEAT
4WV
BK (L1)
FAN
WH WH(L2) M FAN
3~ MOTOR A-1 L
RD RD(L3) N
N-COM
7 EG-SAVE
L EN-SAVE
BK (L1) CN6 SW2 8 C/H
N OV-HEAT
WH(L2) M FAN 9 OVCA-1
3~ MOTOR A-2 RD CN1 OV-COMP
BK C RD(L3) SW2˖ 5ǃ6˖ 00 Heatpumpˈ11 Refrigeration 10 FLOW
WH FLOW 3
RD B RFS 7˖ 0 Normalˈ1 2-Way Valve Interlock 11 OVP
A 8˖ 0 Singleˈ1 Modul OV-PUMP 2
WH 12 OVCA-2
Transformer CN2
OV-FAN
BK HP
SW1 HP1
Control Board YL LP
LP1
TH1 TH2 TH3 TH4
CN4
A BG
Defrost Sensor1
Defrost Sensor2
Water Outlet Sensor
R
Control panel
B A GND +12V
TO CONTROL WIRING
(Option)
Power
5
3
220Vac RUN AL
TB1 1
MC1-1 N
BK OVC1-1 BK (L3)
WH WH(L2) M
3~ COMP 1-1
RD RD(L1) MC1-2
MC2-1 MF1
MC1-2 MC2-2
4WV2
MF2
BK OVC1-2 BK (L3) (14) 4WV1
M
MC1-1
MP
WH WH(L2) RFS
3~ COMP 1-2
RD RD(L1) (11)
1
1 2 3 4 5 7 8 N 10 N 11
BK MF1 BK (L1)
COMP1
M FAN
COMP2
RUN_OUT
AL_OUT
RUN_IN
WH WH(L2)
PUMP
M/FAN2
AL_IN
4WV1
HE/EV1
A-HAT
4WV2
H/FAN1
3~ MOTOR 1-1
RD RD(L3) N
N-COM
EN-SAVE
BK (L1)
MC2-1 M FAN C H
OVC2-1 BK (L3) WH(L2) L
BK HP2 BK
BK 3~ MOTOR 1-2 SW1
RD(L3) HP2
WH WH(L2) M N YL LP2 YL
3~ COMP 2-1 LP2
RD RD(L1) RD Microprocessor Control Board 15 FS
CON1 FLOW
MC2-2 (Two Compressors) 16
OVC2-2 BK (L3) OV-PUMP
BK CON2
WH(L2) M WH ADC_OD_C01
WH COMP 2-2 Transformer SW2 OV-FAN OVC1-1 OVC1-2
3~
RD RD(L1) OV-COMP1
OVC2-1 OVC2-2
OV-COMP2
MF2 BK HP1 BK
BK BK(L1) HP1
M FAN CN6 TH1 TH2 TH3 TH4 TH5 TH6 LP1
WH WH(L2) 3~ MOTOR 2-1 CN4 LP1 YL YL
RD RD(L3) A BG
BK(L1)
(L2) M FAN connect with other units(correspond)
BK WH MOTOR 2-2
C 3~
WH B RFS RD(L3)
RD A
Defrost SensorA-1
Defrost SensorA-2
Defrost SensorB-1
Defrost SensorB-2
Water Inlet Sensor
U
MC1-1
N 31
CCH1-1 32 MC1-2
Mian Controller
CCH1-2
U
Control panel CN1
B A GND +12V
N 33
MC2-1
(Option)
CCH2-1 MC2-2
34
CCH2-2
power
TO CONTROL WIRING
MP Chiller's Water Pump Contactor N-COM Common Neutral Line TB Terminal Board 1-2 2-2
Wiring Diagram
MC Compressor Start Contactor EN-SAVE Run Output/Input RFS Phase Sequence Controller
Energy Saving/
MF Fan Motor Contactor RUN-OUT/IN 2- Way Valve Interlock 4WV 4 Way Valve
Note: 1-1 2-1
A-HAT Plate Heat Exchanger Heater OVP Water Pump Overload 3 Water flow switch need connect between 15 and U
PUMP Water Pump OVF Fan Motor Overheat 4 DIP setting (sw1,sw2) according to IOM
H/FAN Fan Motor HP High Pressure Switch Factory Wiring 690134120003
19
Wiring Diagram
21
Pre-Start-up
Voltage Range
The power supply of the unit must comply with the operating power supply marked on the
nameplate of this unit, and the supply voltage and the voltage imbalance between phases must
be within the following scope. The voltage between phases shall be measured, and the voltage
reading must be within the allowable voltage tolerance (±10%) shown on the nameplate of
this unit. If the voltage between any two phases is not within this tolerance, the electric power
company shall be notified to improve before operate this unit. Improper voltage will result in
the disorder of control function and shorten the service life of various electrical components and
compressor motors.
Voltage Imbalance
If the voltage imbalance between any two phases in the three-phase power system is too high, it
will cause motor overheating and motor failure. The maximum permissible imbalanced voltage
is 2%, and the voltage imbalance is defined as follows:
100x|Va-Vd|
Voltage imbalance % = Va
Wherein
Va=(V1+V2+V3)/3(average voltage)
V1,V2,V3=line-to-line voltage
Vd=maximum line-to-line voltage deviated from Va
Water Flow
The chilled water flow through the unit must be between the upper and lower limits listed in
Table 1. If the chilled water flow entering the evaporator is lower than the lower limit, it will
cause discontinuous flow, reduce the heat transfer effect and cause the expansion valve out of
control or abnormal low pressure shutdown. On the contrary, if the water flow is higher than the
upper limit, the parts and components inside the evaporator will be eroded.
22
Pre-Start-up
Caution
When the water pump operates, adjust the water flow to 50% of the Rated flow, and adjust the
contact of the flow switch to open circuit. Please use the ohmmeter to verify the on and off of
the switch contact.
Warning
When the ambient temperature is below 16℃ in winter, do not cut off the power supply, and
preheat the unit 24 hours ahead of start-up, otherwise the compressor will be damaged.
23
Pre-Start-up
N Type H Type
CX(G)AJ045 CX(G)AJ045
CX(G)AJ065 CX(G)AJ065
Internal Pressure Drop of Unit
Water Pressure DropDŽmH2ODž
CX(G)AJ130 CX(G)AJ130
Internal Pressure Drop of Unit Internal Pressure Drop of Unit
Water Pressure DropDŽmH2ODž
14 16
12 14
10 12
10
8
8
6
6
4 4
2 2
0 0
13.44 15.68 17.92 20.16 22.4 24.64 26.88 29.12 31.36 13.44 15.68 17.92 20.16 22.4 24.64 26.88 29.12 31.36
Water FlowDŽm3/hDž Water FlowDŽm3/hDž
24
Pre-Start-up
Make sure the water flow in the reasonable range ( 60%--130% rated water flow)
Before unit start-up or commissioning, set the functions and operating parameters according to
the following methods. The unit function setting is mainly defined through the jumper, the dial
switch and the system bit. The incorrect setting will cause the faulty operation of the unit and
even shutdown!
Jumper Setting
The jumper JP1 is used for software version control. If JP1 is unplugged, the software can be
downloaded; if JP1 is short-circuited, the system will normally operate.
Mode:
00 Normal operating mode 01 Computer monitoring mode
10 System self-inspection and configuration mode 11 On-site commissioning mode
C/H:
0 "External cooling/heating switch" disabled 1 "External cooling/heating switch" enabled
Fan:
0 Single fan 1 Double fans
Type:
00 Heat pump+electrical heater 01 Cooling+electrical heater
10 Cooling+electrical heating 11 Cooling
EnSave:
0 Conventional 1 Two-way valve interlocking
Control:
0 Single-unit control 1 Module control
25
Pre-Start-up
Auto: (135)
0 Need manual start-up (by default) when powering on
1 Allow automatic start-up (in case of power-down in running state) when powering on
Flow : (133)
0 “Water flow switch mode” disabled (by default)
1 “Water flow switch mode” enabled (if the switch is still closed within 30 seconds after the
water pump is stopped, the alarm will be issued)
Temp: (134)
0 “Suction temperature” enabled
1 “Suction temperature” disabled
26
Pre-Start-up
Type
0 Heat pump
1 Cooling only
En-Save
0 Conventional
1 Two-way valve interlocking
Note: this function is invalid when “module control” is selected.
Control
0 Single-unit control
1 Module control
Bit Function Switch (H Type Unit, Set through Single Unit Controller, Centralized
Controller, etc.)
Bit8 Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1
Detection Manual
Reserved of full-water Reserved Reserved Reserved defrosting Reserved Reserved
flow switch
27
Pre-Start-up
28
Unit Operation
Start Steps
• Power on the unit, press MODE button on the Single Unit Controller to select cooling or
heating after 120 seconds, and then press ON/OFF button on the Single Unit Controller to
start the unit.
• When the unit operates for over 30 minutes and the system steadily operates, inspect the
following items to ensure the normal operation of the unit:
1. Inspect whether the water flow and water pressure readings of the unit are stable and
within the normal range.
2. Test the high and low pressures of the unit. During the normal operation, the low pressure
shall be 85-145 psig (0.586-1.0 MPa), and the high pressure shall be 290-500 psig (2.0-3.45
MPa).
3. Inspect the current reading of the compressor.
4. Inspect the power supply.
5. Measure the system superheat degree.
In ARI conditions (water inlet temperature of 12.2 ℃, water outlet temperature of 6.7 ℃,
ambient temperature of 35 ℃), the normal system superheat of each circuit is 5-8 ℃. The
superheat measured on any circuit is beyond this range, the superheat setting on the
expansion valve shall be regulated to obtain a proper reading. Wait for 15 to 30 minutes to
make the new set value stable after each adjustment of expansion valve.
6. Measure the system sub-cooling degree.
In ARI conditions, the normal system sub-cooling degree of each circuit is 5-10 ℃. If the
sub-cooling degree measured on any circuit is beyond this range, necessary adjustment
shall be made after the inspection of circuit superheat. If the superheat is normal but the
sub-cooling degree is abnormal, please contact the professional maintenance personnel.
7. If the system leakage is found, the leakage point shall be found out to repair, and then
the gaseous refrigerant shall be charged into the circuit. When the unit operates, the
refrigerant is charged from the low pressure pipe till the operating pressure is normal. If
the operating pressure is low, and the sub-cooling degree is low, it will indicate that the
refrigerant is insufficient.
8. If the operating pressure shows that the refrigerant is excessive, the refrigerant shall be
recycled slowly at the liquid pipe (to minimize the loss of refrigerant oil as far as possible).
9. The start and stop unit below 4 times in an hour.
• Make sure all temperature sensors are installed at the correct position, and the capillary
tubes of the temperature sensors must be firmly fixed in order to avoid vibration and
abrasion.
• Inspect the unit and remove the wastes, the tools and the parts. Fix all shell plate metal parts
including the control panel and the compressor access plate, and install all screws to the
original places.
Long-term Shutdown
• If this system is not used for a long time, the followings shall be done before shutdown:
1. Inspect whether the refrigerant pipe leaks or not. If any, be sure to repair it.
2. Maintain the water pump and the air conditioning equipment as recommended by the
manufacturer.
3. Empty the circulating water in the system, unscrew the water drainage opening in the
water supply and return circuit, disassemble the side panel of the unit, unscrew the water
29
Unit Operation
drainage opening at the bottom of the water pump and the shell and tube heat exchanger
to ensure that the circulating water is drained off.
4. Turn off the power switches of the unit and water pump.
Cautions
• In winter, it is necessary to close the water supply valves of all evaporators, open the drain
valve and the exhaust valve on the unit pipeline to drain the water in the evaporator, and then
install the drain plug. For the ultra-thin ceiling unit, first drain off the water in the pipeline,
and then open the drain valve at the bottom to drain off the residual water in the evaporator.
If the water in the chilled water pipe cannot be fully drained off, the proper antifreeze liquid
can be injected to prevent the residual water from being frozen and thus damaging the unit.
Caution
When the water pump operates, adjust the water flow to the half of the maximum flow, and
disconnect the contact of the flow switch. Please use the ohmmeter to verify on and off of the
switch contact.
System Protection
Low-pressure protection (LP1, LP2) (N Type Unit Only)
The unit is under the protection of the low pressure switch. When the operating pressure is lower
than 21±7 psig (0.1145±0.048 MPa), the operation of compressor will be stopped; when the
operating pressure is up to 36±7 psig (0.248±0.048 MPa), the compressor will be automatically
reset. There will be 2-minute short circuit when starting to avoid unnecessary shutdown.
30
Unit Operation
31
Unit Operation
Flow protection
To avoid the evaporator freezing caused by the reduction of water flow, a flow switch (or other
flow sensing devices) shall be installed on the evaporator water pipe. Its set value must ensure
that the operation of compressor will be stopped immediately if the water volume is lower than
70% of the system design full flow.
Cooling mode:
Dual system
When the system is started, the water pump operates immediately. Two minutes later, the water
pump continues to operate. When the water return temperature is over 13 ℃, No.1 compressor
will be started. One minute later, if the water return temperature is over 15 ℃, No.2 compressor
will be started. If the cooling requirement is reached, the water return temperature will be
reduced to 11 ℃, and No.1 compressor will be stopped. If the water return temperature is
continuously reduced to 10 ℃, No.2 compressor will be stopped. Then, the load is increased, the
water return temperature rises to 13 ℃, and No.1 compressor is restarted. If the water return
temperature continuously rises to 15 ℃, No.2 compressor will run. Unless the unit is shut down,
the water pump will keep running.
32
Unit Operation
Single system
When the system is started, the water pump operates immediately. Two minutes later, the water
pump continues to operate. When the water return temperature is over 15 ℃, the compressor
will be started. If the cooling requirement is reached, the water return temperature will be
reduced to 10 ℃, and the compressor will be stopped. Then, the load is increased. If the water
return temperature rises to 15 ℃, the compressor will be restarted. Unless the unit is shut down,
the water pump will keep running.
Heating mode:
Dual system
When the system is started, the water pump operates immediately. Two minutes later, the water
pump continues to operate. If the water return temperature is lower than 39 ℃, No.1 compressor
will be started. One minute later, if the water return temperature is lower than 37 ℃, No.2
compressor will be started. If the heating requirement is reached, the water return temperature
will be increased to 41 ℃, and No.1 compressor will be stopped. If the water return temperature
is continuously increased to 42 ℃, No.2 compressor will be stopped. Then, the load is changed,
the water return temperature is reduced to 39 ℃, and No.2 compressor runs. If the water return
temperature is reduced to 37 ℃, No.1 compressor will be started. Unless the unit is shut down,
the water pump will keep running.
Single system
The operation of water pump, fan and compressor for the single-unit system is the same as the
above dual-unit system. The only difference is that the compressor will be started if the water
return temperature of the single-unit system is lower than 37 ℃ and will be stopped if the water
return temperature is higher than 42 ℃.
Cooling mode:
Dual system
When the system is started, the water pump operates immediately. Two minutes later, the water
pump continues to operate. If the water outlet temperature is higher than or equal to 8 ℃,
one compressor will be allowed to be started; if the water outlet temperature is higher than or
equal to 9 ℃, two compressors will be allowed to be started; if the water outlet temperature is
higher than or equal to 10 ℃, three compressors will be allowed to be started; if the water outlet
temperature is higher than or equal to 11 ℃, four compressors will be allowed to be started.
Unless the unit is shut down, the water pump will keep running.
33
Unit Operation
When the system is unloaded, if the water outlet temperature is lower than or equal to 6 ℃, one
compressor will be shut down; if the water outlet temperature is lower than or equal to 5.5 ℃,
two compressors will be shut down; if the water outlet temperature is lower than or equal to 5 ℃,
three compressors will be shut down; if the water outlet temperature is lower than or equal to 4.5
℃, four compressors will be shut down.
Single system
When the system is started, the water pump operates immediately. Two minutes later, the water
pump continues to operate. If the water outlet temperature is higher than or equal to 8 ℃, one
compressor will be allowed to be started; if the water outlet temperature is higher than or equal
to 10 ℃, two compressors will be allowed to be started.
When the system is unloaded in the Heating mode, if the water outlet temperature is lower than
or equal to 6 ℃, one compressor will be shut down; if the water outlet temperature is lower than
or equal to 5.5 ℃, two compressors will be shut down.
Heating mode:
Dual system
When the system is started, the water pump operates immediately. Two minutes later, the water
pump continues to operate. If the water outlet temperature is lower than or equal to 44 ℃,
one compressor will be allowed to be started; if the water outlet temperature is lower than or
equal to 43 ℃, two compressors will be allowed to be started; if the water outlet temperature is
lower than or equal to 42 ℃, three compressors will be allowed to be started; if the water outlet
temperature is lower than or equal to 41 ℃, four compressors will be allowed to be started.
Unless the unit is shut down, the water pump will keep running.
When the system is unloaded, if the water outlet temperature is higher than or equal to 46 ℃,
one compressor will be shut down; if the water outlet temperature is higher than or equal to 46.5
℃, two compressors will be shut down; if the water outlet temperature is higher than or equal
to 47 ℃, three compressors will be shut down; if the water outlet temperature is higher than or
equal to 47.5 ℃, four compressors will be shut down.
Single system
When the system is started, the water pump operates immediately. Two minutes later, the water
pump continues to operate. If the water outlet temperature is lower than or equal to 44 ℃, one
compressor will be allowed to be started; if the water outlet temperature is lower than or equal
to 42 ℃, two compressors will be allowed to be started.
When the system is unloaded in the Heating mode, if the water outlet temperature is higher than
or equal to 46 ℃, one compressor will be shut down; if the water outlet temperature is higher
than or equal to 46.5 ℃, two compressors will be shut down.
34
Module Control System
System Introduction
The module control system is a highly intelligent centralized control system. It can manage the
loading and unloading controls of multiple outdoor unit modules, the centralized control of
multiple outdoor units is mainly performed by the Centralized Controller, and one Centralized
Controller can control 25 units at most.
Centralized
controller
Up to 25pcs
Centralized Controller
The centralized controller is the core of the whole system. It can be used for single-unit and
group operations (including startup & shutdown, temperature setting, mode change, etc.),
comfort timing control, network monitoring alarm, etc. The configuration of 50*100mm large
LCD screen and 15 keys provides a clear operation interface bringing convenience to the users.
The casing of the centralized controller is provided with a flip cover, the common keys such as
‘OK’, ‘ ∧’ and ‘∨’ are exposed on the surface for normal operation. The more detailed
operation can be finished through the keys under the flip cover. The simple and easy operation
instructions are printed under the flip cover.
The centralized controller needs a 220VAC/12VDC, 500mA DC power supply.
The dimensions are 122*162*19.2mm (W*H*T), and the centralized controller can be installed
through the standard 86 type junction box.
S44 1 2 3 4 1 2 S37
NO. Group
S43
S42
S41
A
ON OFF
S20
S21
S22
S40
S39
֠ F 21
2))
:((. S23
S24
SET RH C CO2
S25
Outdoor
α ZZZ S26
S38 S27
35
Module Control System
Description:
S1 ……… Keyboard lock; if this icon is displayed, the keyboard will be locked;
S2-S5 …… icon for compressors 1-4 Running;
S6-S9 …… icon for compressors 1-4 Defrosting ;
S10-S11 … icon for electrical heaters 1-2 Running;
S12 ……… Antifreezing icon;
S13 ……… Water pump Running icon;
S14 ……… Meters icon;
S15 ……… Boiler icon;
S16 ……… Expressing the telephone interface board or communication problem;
S17 ……… Expressing the relevant operations of the light interface board;
S18 ……… Unit number icon flashing when binding. If this icon is displayed, the number displayed at S37 is unit
number;
S19 ……… Group operation indication;
S20 ……… Expressing system running. In general, it indicates the running of unit with minimum unit number;
S21 ……… Expressing system stopped. In general, it indicates stopped of unit with minimum unit number;
S22 ……… Filter screen. In the comfort control mode, it indicates enabled or disabled of comfort control;
S23 ……… Fresh air;
S24 ……… Much air dust;
S25 ……… Swing;
S26 ……… High carbon dioxide content;
S27 ……… Sleep;
S28 ……… Day of Week;
S29 ……… Timing On icon;
S30 ……… Time displaying the time of clock and timing;
S31 ……… Timing Off icon;
S32 ……… Timing setting icon. If timing is set and this icon is displayed, timing will be valid; in general, if this icon is
displayed, timing has been set.
S33 ……… Fahrenheit degree;
S34 ……… Centigrade degree;
S35 ……… Percent for expressing the humidity or the loading rate of the compressor, etc.;
S36 ……… Displaying temperature, humidity, fault code and other values;
S37 ……… Expressing the total quantity of units, the unit number, etc.;
S38 ……… Displaying the outdoor unit or external ambient temperature, etc.;
S39 ……… Displaying the setting temperature;
S40 ……… Displaying the humidity;
S41 ……… Alarm;
S42 ……… Expressing the room temperature (water temperature);
S43 ……… Fan icon. The peripheral circle expresses automatic fan speed, one leaf expresses low fan speed, two
leaves express middle fan speed, and three leaves express high fan speed;
36
Module Control System
S44-S48 … Respectively expressing cooling, dehumidification, heating, ventilating and automatic modes;
Keys
Description:
∧ ……… After the centralized controller selects the single-unit operation mode, press this
key to set the temperature. The temperature will rise by 1 degree. See the following
description for other functions.
∨ ……… After the centralized controller selects the single-unit operation mode, press this key
to set the temperature. The temperature will drop by 1 degree. See the following
description for other functions.
OK ……… Confirmation of operation. Press this key to perform the group startup & shutdown
operation.
SetTime Time setting key.
① ……… Browse key. Rapidly inquire the network unit condition. This key can be also used as
a number key.
② ……… Mode key. After the centralized controller selects the single-unit operation mode,
press this key to change the mode. When setting the time, press this key to change
the month setting. This key can be also used as a number key.
③ ……… Week key. After the centralized controller selects the single-unit operation mode,
press this key to set the sleep mode. When adjusting the time (or setting the week
timing), press this key to change the week setting. This key can be also used as a
number key.
④ ……… Single Unit key. This key is used for the centralized controller to select the single-unit
operation mode. This key can be also used as a number key.
⑤ ……… Fan key. After the centralized controller selects the single-unit operation mode, press
this key to change the fan speed. When setting the time, press this key to change the
date. This key can be also used as a number key.
⑥ ……… Hour key. When adjusting the time (or setting the week timing), press this key to
adjust the hour. This key can be also used as a number key.
⑦ ……… Connect key. This key is used for the network binding of units. This key can be also
used as a number key.
⑧ ……… Backlight key. This key is used for backlighting the centralized controller. This key can
be also used as a number key.
⑨ ……… Minute key. After the centralized controller selects the single-unit operation mode,
37
Module Control System
this key is used for fault resetting; When adjusting the time (or setting the week
timing), press this key to adjust the minute. This key can be also used as a number
key.
0 ……… Timing key. This key is used for the timing setting of comfort function. It can be also
○
used as a number key.
……… Group key. This key is used for group operation control.
……… Exit key. This key is used for the last key function exiting. Long press this key to lock
the keyboard.
See the common key operation instructions under the flip cover of the casing for the centralized
controller.
Key Description
• Unit network binding: key ⑦
• Rapid inquiry of connected units: key ①.
• Time adjustment: month: key ②; day of week: key ③; date: key ⑤;
hour: key ⑥; minute: key ⑨.
• Single-unit operation: temperature setting: keys ④ and ; mode:
key ②; sleep: key ③; fan speed: key ⑤; alarm reset: key ⑨.
• Group operation: mode: keys and ②; startup & shutdown: key ;
temperature setting: key .
Hotline:8008208676/4008201363
Connecting
terminal
38
Module Control System
R26
SW2
ON
RUN-OUT
RUN-OUT
RUN-OUT
AL-OUT
AL-OUT
M/FAN2
M/FAN2
H/FAN1
RUN-IN
H/FAN1
RUN-IN
AL-OUT
COMP1
COMP2
COMP1
COMP2
M/FAN2
HT/EV1
HT/EV1
H/FAN1
RUN-IN
COMP1
COMP2
HT/EV1
PUMP
PUMP
LINE
AL-IN
AL-IN
4WV2
LINE
4WV2
4WV1
4WV1
PUMP
LINE
AL-IN
4WV2
A-HAT
A-HAT
4WV1
A-HAT
N-COM N-COM N-COM
CN2
NEGETIVE ADC_OD_CO1 NEGETIVE ADC_OD_CO1 NEGETIVE ADC_OD_CO1
EN-SAVE EN-SAVE EN-SAVE
CN6 TH1 TH2 TH3 TH4 TH5 TH6 CN6 TH1 TH2 TH3 TH4 TH5 TH6 CN6 TH1 TH2 TH3 TH4 TH5 TH6
B A B G A B G A B G A B G
A G A B G
C15
GND
POWER
+V A A A
+9~12V B B B
SHIELD LAYER SHIELD LAYER SHIELD LAYER Grounding
39
Module Control System
40
Module Control System
NO.
Flash display
:((.
C
In case the controller is connected with the network but there is any key operation:
After the control panel is connected to the network, firstly search for the control panel. In the
searching process, the square brackets will be still displayed at the number position of the air
conditioning unit and will be displayed in a mobile way. After searching is ended, the quantity
of control panels will be displayed at the number position of the air conditioning unit. The mode
of No.0 unit will be displayed at the mode position. If more than one connected units are started
up, there will be a startup indication “ON”; if all connected units are shut down, there will be a
shutdown indication “OFF”, as shown in the figure below:
Quantity of
connected units
If the key ⑦ (Connect) is pressed for more than 1 second, the centralized controller will search
for the unit again, the results in the above figure will be displayed.
Fast Query
When the key ① (Browse) for more than 1 second, the display screen will display the operating
state of the unit with the minimum number. Then automatically increase the unit number (the
automatically increased speed can be adjusted) to continue to browse downward. When the key
“∨” is pressed, the increase of unit number will be stopped; when the key “∨” is pressed,
the unit number will be increased; when the unit number stops increasing, and the key “∧” is
pressed, the unit number will be reduced by 1 to reversely display other units. If the key Exit is
pressed, quit browsing. See the following figure:
NO.
:((.
OFF
SET C
ZZZ
41
Module Control System
Single-unit operation
If the key ④ (Single Unit) is pressed, 00 will be displayed at the number position of the air
conditioning unit and flash. At this time, press the number key to input the number of unit to be
controlled, and then press OK. If this air conditioning unit exists on the network, the number of
air conditioning unit stops flashing, which indicates that this indoor unit is selected for control.
The display screen will display all information of this unit, including mode, air speed, set
temperature, etc.
Then press the keys “OK”, “∨”, “∧”, “2”, “5”, “8”, “3” and “9” corresponding
to “startup & shutdown”, “temperature drop”, “temperature rise”, “mode”, “air
speed”, “electrical heating”, “sleep”, “fault resetting”, etc.
If the key “∧” is pressed when the number of air conditioning unit flashes, A0 will be
displayed at the number position of the air conditioning unit. Then “∨” and “∧” can be
pressed, and the unit number will vary from A0 to BF. At this time, the key OK is pressed, and it
indicates that the selected unit number is the number of outdoor unit. And then the outdoor unit
can be operated. (Notes: if the address switch of the outdoor unit is 0, A0 will be displayed on
the centralized controller; if the address switch of the outdoor unit is 1, A1 ill be displayed on the
centralized controller. The display mode is hexadecimal. 32 outdoor units can be connected from
A0 to BF.) For the outdoor units, startup & shutdown and mode change can be performed.
At this time, if the key Exit is pressed, the single-unit operation will be quit. The key ④ (Single
Unit) can be also pressed to select other unit to operate.
Time Adjustment
When the key SetTime is pressed for more than 1 second, the time display part will flash.
Then press ③ (Week), ⑥ (Hour) and ⑨ (Minute) to respectively adjust week, hour and minute.
If ③ (Week), ⑥ (Hour) and ⑨ (Minute) are long pressed, week, hour and minute will rapidly
change.
Press ② (Month) to adjust the month, and press ⑤ (Date) to adjust the date.
After adjustment, press SetTime to change the clock and quit the time adjustment. If SetTime is
not pressed but Exit is pressed, the clock will not change.
Month
ON
Hour :((. Week
Date
Minute
SET
ZZZ
Note: after the centralized controller is initially installed or the battery is replaced, it is
necessary to adjust the clock, otherwise the clock will not work.
Fault Display
Offline display
Under normal circumstances, the quantity of units is displayed at the unit number position, and
“NO.” is not displayed. If there is an offline unit, “NO.” will be displayed, and the number
of offline unit will be displayed at the unit number position and flash, and the phone icon will
42
Module Control System
be simultaneously displayed. If there are many offline units, the unit numbers will be display in
turn.
Flash
Modify the parameters of the outdoor unit through the centralized controller
Firstly select an outdoor unit (to enter the single-unit operation mode);
Then press (Group) for 3 seconds, and then the lock symbol will be displayed at the top left
corner and flash; at this time, the unit number part will also flash;
Then enter the password 66 through the number key; then press OK to enter the parameter
adjustment mode.
At this point, the parameter code will be displayed at the time display part, and the parameter
value will be displayed at the temperature display part. Then press “∨” and “∧” to
respectively modify the parameters. After modification, press OK to confirm modification and
modify the next parameter. If the parameter is not expected to be modified, press “0” to
modify the next parameter.
Note 1: if there is no parameter to be modified for the outdoor unit, press OK to quit the
parameter modification mode.
43
Module Control System
Note 2: if the parameters is temperature parameter, the unit “C” or “F” will be displayed; if
the parameters are time or other parameters, the units will not be displayed;
Note 3: the decimal part of the parameter will not be displayed.
“66” Password Setting
Code Set value
016 Set cooling temperature
017 Set heating temperature
022 Antifreezing temperature in winter
001 Defrosting time interval
002 Minimum defrosting time
The method for modifying the factory set value and the bit function switch is similar with this
method. The difference is that the password and the parameter code are different.
Set the centralized controller to display the set temperature or the room temperature (water
temperature)
Press “∨” for 3 seconds to enter the password mode. The lock symbol will be displayed at the
upper left corner, and the unit number part will flash. Enter two-bit password (00 by default),
and press OK. The lock symbol and the unit number will flash at the same time to enter the
adjustment interface.
At this time, press “∨” to switch to display the set temperature or room temperature. If
the unit on the network does not support the room temperature, the set temperature will be
displayed.
When the room temperature is displayed, the icon will occur; when the set temperature is
displayed, the icon will occur.
NOTE: If has indoor units, the centralized controller will display room temperature, if no indoor
units, only has outdoor units, the centralized controller will display water temperature (return or
leaving water temperature which by different control).
Lock the keyboard
If Exit is pressed for more than 6 seconds, the lock icon will be displayed at the upper left corner
of the display screen;
At this time, the keyboard is locked. If Exit is pressed for more than 6 seconds again, the
keyboard will be unlocked.
During the keyboard locking period, the operation of any key will not be performed.
44
Module Control System
Module Control
The single-unit cascade system is a system which can realize the centralized control function
by connecting multiple single units through the network cable. The centralized controller can
operate any cascaded single unit and can operate all cascaded single units by group. The
functions of any cascaded single unit are the same and independent of each other.
The module control system is a system which can realize the centralized control function by
connecting one host unit and multiple slave units through the network cable. The module control
system shares a water system, the host unit undertakes the operation of the system pump, all
slave units share this water system, and the system automatically adjusts the energy balance,
controls the time-sharing startup of the units, automatically loads and unloads the energy and
realizes the average wear among the units.
Control Requirements
No.0 unit is the host unit, and other units are slave units.
All units share a waterway system.
For N Type unit, all slave units on the network are subject to the water inlet temperature of No.0
unit;
45
Module Control System
For H Type unit, all slave units on the network are subject to the water outlet temperature of No.0
unit.
The host unit is provided with the system pump and the basic input and output.
The host unit is connected with the water pump and detects the water flow switch; the slave
units are not connected with the water pump but still connected with the water flow switch for
detecting the water flow switch. If the water flow switch of a slave unit issues an alarm, this slave
unit will be automatically turned off.
The slave units are not provided with the pump and the interlocking two-way valve, is only
provided with the basic input and output.
If the water pump of the host unit issues an alarm, all units will be shut down. The slave units
have no water pump alarm function.
The slave units are subject to the water outlet temperature of the host unit.
After receiving the all-unit start command, the units will be started up by delaying for 60s+unit
number*16s.
After receiving the all-unit shutdown command, the units on the network will be shut down
according to unit number*8s, but the host unit will not execute this shutdown command and
only accept the single-unit shutdown command.
Do not start up any host unit or slave unit or switch the mode by using the single unit controller;
it can view and set the parameters of the unit only.
System Operation
System startup: the centralized controller executes the group startup operation.
System shutdown: the centralized controller executes the group shutdown operation.
The mode operation can be switched only in the group operation.
Implementation Method
Grouping of outdoor units
1) The outdoor units are grouped by unit number.
Group 1 No.0 unit No5. unit No10. unit No.15 unit No.20 unit
Group 2 No.1 unit No.6 unit No.11 unit No.16 unit No.21 unit
Group 3 No.2 unit No.7 unit No.12 unit No.17 unit No.22 unit
Group 4 No.3 unit No.8 unit No.13 unit No.18 unit No.23 unit
Group 5 No.4 unit No.9 unit No.14 unit No.19 unit No.24 unit
Notes: installation instructions: if the quantity of outdoor units is 6, the numbers shall be 0, 1,
2, 5, 6 and 7, which are grouped into 3 groups; if the quantity of outdoor units is 4, the numbers
shall be 0, 1, 2 and 3, which are grouped into 4 groups, namely, the numbers shall be arranged
by matrix as soon as possible.
2) The uploading and downloading conditions are classified into 5 conditions.
46
Module Control System
47
Building Control System
Mini-ICS system is a highly intelligent centralized control system developed by Trane for Unitary
(small and medium sized) units. Mini-ICS system can manage the linkage control of multiple
indoor units and outdoor units, the loading and unloading control of multiple indoor unit
modules, the centralized control of multiple outdoor units as well as the centralized control of
multiple indoor units; if Mini-ICS system is connected with Modbus communication module,
the monitoring of local computer and the remote control of Internet can be realized, i.e. remote
setting of room temperature, operation mode, startup and shutdown as well as fault alarm.
The system can be classified into a single-master controller system and a multi-master controller
system. Wherein, the single-master controller system is suitable for the air conditioning comfort
control of multiple rooms for a single family; the multi-master controller system is suitable for
the control of multiple units for the small commercial system. This centralized control system is
composed of a centralized controller, a Modbus communication module, a concentrator, units,
etc. It can perform the remote centralized control of whole air conditioning system, and provide
the necessary data for BA system to ensure that it is connected to the building automatic control
system.
48
Building Control System
Centralized
Modbus module Up to 25pcs controller
Host computer
Centralized
Modbus module Up to 25pcs
controller
RS458 communication
wire (Modbus)
RS458 communication wire
Centralized
Modbus module Up to 25pcs controller
Up to 15 Modbus modules
RS458 communication wire
See Operation Manual for CXAJ Series Modbus Module for the specific wiring and operation of
Modbus module.
49
Troubleshooting
50
Troubleshooting
17 fault input alarm switches, 1 fault output alarm switch and 1 operating status output switch are arranged for the
double-compressor system.
No. Input Port Fault Description Type Code Fault Handling
Short circuit / open circuit of water inlet
1 TH1 A SE Turn off all external devices
temperature sensor
Short circuit / open circuit of water
2 TH2 A SL Turn off all external devices
outlet temperature sensor
Short circuit / open circuit of suction
3 TH3 A Sd Turn off all external devices
temperature sensor 1
Short circuit / open circuit of defrosting
4 TH4 A S1 Turn off all external devices
temperature sensing sensor 1
Short circuit / open circuit of defrosting
5 TH5 A S2 Turn off all external devices
temperature sensing sensor 2
Short circuit / open circuit of suction
6 TH6 A S3 Turn off all external devices
temperature sensor 2
Only switch off the compressor
7 OVHT/HP2 High pressure alarm of compressor 2 E H2
2
8 FLOW Lack of water flow D FL Turn off all external devices
9 OV-PUMP Overload of water pump 1 B OP Turn off all external devices
10 OV-FAN Overload of fan B OF Turn off all external devices
Only switch off the compressor
11 OV-COMP1 Overload of compressor 1 C C1
1
Only switch off the compressor
12 OV-COMP2 Overload of compressor 2 E C2
2
Only switch off the compressor
13 HP1 High pressure voltage of compressor 1 C H1
1
Only switch off the compressor
14 LP1 Low pressure voltage of compressor 1 C L1
1
Only switch off the compressor
15 FREZ/LP2 Low pressure voltage of compressor 2 E L2
2
Switch off the compressor. The
Low refrigeration water outlet
16 / / / D E3 auxiliary heater for the water
temperature
pump operates.
Switch off the compressor. The
17 / / / Low suction temperature D E4 auxiliary heater for the water
pump operates.
51
Troubleshooting
52
Troubleshooting
53
Troubleshooting
54
Troubleshooting
55
Troubleshooting
56
Troubleshooting
(1) The parts inside the compressor are damaged or broken (the
Replace the compressor.
compressor makes a tap-tap).
Inspect and adjust the superheat.
(2) Liquid backflow.
Inspect whether the refrigerant is charged
(3) There is liquid refrigerant in the compressor when starting (the
excessively.
compressor housing is unusually cold).
(2) The drying filter is blocked (the temperature from the refrigerant
Replace the drying filter.
pipe to the dryer varies).
(3) The expansion valve is incorrectly adjusted. Readjust the expansion valve.
(4) The expansion valve is blocked (the superheat is too high and the
Repair or replace the expansion valve.
water temperature is too high).
(7) The valve of the compressor leaks and the suction pressure is high
Replace the compressor.
(the high pressure is high, and the low pressure is low).
(1) The refrigerant is charged insufficiently (the superheating capacity is Find out and repair the leakage point, and
high and the sub-cooling capacity is low). recharge the refrigerant.
(2) The temperature switch setting is too low (the low pressure is too
Readjust the temperature switch.
low, and the water outlet temperature is too low).
(5) The expansion valve is blocked (the superheating capacity is high). Clean or replace the expansion valve.
57
Troubleshooting
(1) The cooling load is too high (i.e. the water supply temperature is
See the section E.
high).
(2) The expansion valve excessively supplies liquid (i.e. the Adjust the superheat setting, and inspect
superheating capacity is too low, and the liquid overflows to the whether the temperature sensor is installed in
compressor). the gas pipe.
(3) The suction valve is broken (i.e. the compressor noise is high). Replace the compressor.
(2) The exhaust valve of the compressor is broken or leaks air. Replace the compressor.
(3) The low pressure switch is poor. Replace the poor control element.
(2) There is air or noncondensing gas in the system (i.e. the condenser Recharge the refrigerant after the system is
is unusually hot). vacuumized.
(5) The condensing fan or the fan pressure is poorly controlled (i.e.
Repair or replace the switch.
certain fan is faulty, and the condenser pressure is too high).
(1) The control circuit is wrong or poor. Inspect the control circuit.
58
Troubleshooting
(2) The air flow entering into the coil is too low or the Clean the coil, and inspect whether the fan motor function is
air is too cold. normal.
59
Maintenance
Shutdown
If the system is required to be shut down for a short time, just press the key “ON/OFF” on the
control panel. If the system is required to be shut down for a long time, the main power supply
shall be switched off. If there are no additional antifreezing protection measures (not this unit)
taken on the water pipeline. The water shall be drained off through the drain valve on the water
pipeline. Unscrew the water outlet in the water supply and return circuit, disassemble the unit
side panel, and unscrew the water outlets at the bottom of the water pump and the shell and
tube heat exchanger to ensure that the circulating water is drained off.
60
Maintenance
Notes:
• Prior to any contact, please be sure to switch off the main power supply, otherwise it may
cause casualties and unit damage.
• The maintenance and service work completed by the qualified professionals is very important
and shall be performed annually or every 2000 operating hours.
Cleaning of condenser
Please use a brush or water column to clean the condenser. Flush the condenser with the water
column from inside to outside. If the pipe bank is too dirty, please contact the professional
cleaning personnel.
Note:
• Do not clean the condenser with steam; otherwise, it will lead to the rise of internal pressure
to cause the refrigerant to leak through the relief valve.
Cleaning of shell and tube heat exchanger
Trane recommends to clean the shell and tube heat exchanger by the chemical cleaning method.
The cleaning agent shall be hot phosphoric acid solution, and its use conditions are as follows:
50-60 ℃, concentration of 15%, and cyclic cleaning for 3-6 hours.
Warning!
• Do not clean the shell and tube heat exchanger with the toxic or corrosive cleaning fluid.
Unit
Shutoff
valve (off)
Water
outlet Three-way
valve Unit
Three-way
Shutoff valve
valve (off)
Water
inlet
Circulating
water pump
61
Trane optimizes the performances of the global civil housings and buildings. As a brand subordinated by Ingersoll
Rand, the leader creating and maintaining the safe, comfortable and energy-saving environment in the world, Trane
provides a complete set of advanced control and thermal energy air conditioning system, comprehensive building
services and spare parts support. Please visit www.trane.com。
Trane constantly improves and innovates its products. The data in this document will be changed without prior notice.