Tableau Tolerance
Tableau Tolerance
– 44 – 60076-1 © IEC:2011
Table 1 – Tolerances
Item Tolerance
1. a) Total losses See Note 1 +10 % of the total losses
b) Measured component losses See Note 1 +15 % of each component loss, provided that the
tolerance for total losses is not exceeded
2. Measured voltage ratio at no load on principal The lower of the following values:
tapping for a specified first pair of windings or the
extreme tappings, if specified a) ±0,5 % of the specified ratio
NOTE 1 The loss tolerances of multi-winding transformers apply to every pair of windings unless the guarantee
states that they apply to a given load condition.
NOTE 2 For certain auto-transformers and series transformers the low value of their impedance may justify a
more liberal tolerance. Transformers having large tapping ranges, particularly if the range is asymmetrical, may
also require special consideration. On the other hand, for example, when a transformer is to be combined with
previously existing units, it may be justified to specify and agree on narrower impedance tolerances. Any special
tolerances should be indicated in the enquiry, and any revised tolerances agreed upon between manufacturer and
purchaser.
11 Tests
11.1.1 General
Tests other than temperature rise tests shall be made at an external cooling medium
temperature between 10 °C and 40 °C. See IEC 60076-2 for temperature rise tests.