CapBank BR6000 ControllerManual
CapBank BR6000 ControllerManual
BR 6000
Manual EPCOS AG
Power Capacitors
Version 2.0 E P.O. Box 80 17 09
D-81617 Munich
St.-Martin-Str. 53
PFC-Hotline
Tel. ++49 89 636 - 23817
Telefax ++49 89 636 - 22748
e-mail: [email protected]
internet: http://www.epcos.com
Power Factor Controller BR6000
CONTENTS
Section 1 General 3
Section 9 Troubleshooting 17
Section 10 Interface 18
Section1 General
The BR 6000 power factor controller is the first of a new generation of controllers
incorporating innovative ideas and a broad diversity of functions.
It is distinguished by user-friendly operation based on menu-guided displays in plain
text. Its new features permit an intuitive mode of operation. Easy-to-understand symbols
and texts in the local language combine simplest operability with self-evident displays.
BR6000.../ F
BR6000.../S
Operating mode
- Automatic
- Programming
- Manual operation
- Service
COS j =0 , 98 I ND - Expert mode
Enter / OK
Confirm and
1 2 3 4 5 6 7 8 9 10 11 12
store values
Power Factor Controller BR 6000
Blindleistungsregler
Reguladores Automaticos
de Energia Reactiva Auto
Program Increase
Manual
Service selected
parameter
Enter
OK
cos j
Reduce
selected
parameter
T 2A
only BR6000- 12
L N L N k l RS 232 *
Ub Um Im P1 P2
K1
power factor * option
controller
BR6000
a b 1 2 3 4 5 6 7 8 9 10 11 12
L N L N k l a b P1 K1 K2 K3 K4 K5 K6
The coil voltage for the capacitor contactors and the measuring voltage must be drawn
from the same phase conductor, as only the measuring voltage is monitored. (Protection
against direct reconnection of the capacitor contactors in the event of momentary single-
phase power failure)
T 2A
L N L N k l RS 232 *
Ub Um Im P1 P2
K1
power factor * only option
controller
BR6000
a b 1 2 3 4 5 6 7 8 9 10 11 12
When installing the current converter, care should be taken to ensure that the load
current flows through it. The outputs of the compensation network must be installed
behind the current converter (in the direction of current flow). If the BR 6000 is
connected up via sum-current converters, the overall conversion ratio is entered.
Current converter clamps should be grounded on one side!
K k k K
L l l L
K L K L
k l
k l
Current
measurement
BR6000
The switching outputs may take the form of relay outputs (see Fig. 3) or of transistor
outputs. The relevant version is indicated on the controller type-plate.
Transistor outputs require an additional auxiliary voltage (10-24 VDC) for the direct
control of thyristor switches for dynamic power-factor correction (e.g. TSM-C...).
X2:1
to thyristor module
( e.g. TSM-C...)
X2:2
Further stages
X2:6 (12)
J X2:P 200mA
+ -
24VDC
The alarm contact is closed in normal operation and opens in the event of a fault. The
relevant fault is simultaneously shown on the display in plain text (alternating with the
standard display in automatic operation). The following fault messages are displayed:
When the operating voltage is switched on, the BR 6000 briefly displays its designation
and software version, then changes to its normal operating status (automatic operation).
The active cos-phi value is always displayed in the upper line and the currently connected
capacitors are shown as symbols in the lower line (operating display).
Active capacitor Control direction Supply display (for A double arrow symbolizes fast
branches (here connected-in) 4-quadrant operation) switching of several branches
The power values of the individual capacitors are monitored constantly. If a capacitor is
defective or if the deviation from the rated power is excessive, the corresponding
capacitor is displayed inversely.
Repeated pressing of the "Operating Mode” key takes the user to the various menus in
sequence: Automatic operation - Programming - Manual (manual operation)-
Service - Expert mode and back.
The BR 6000 is set to automatic operation as standard. Capacitor stages are then
automatically connected in or out in order to reach the target power factor. This happens
when the required reactive power exceeds the value of the smallest capacitor stage.
In automatic operation, various network parameters can be displayed by repeatedly
pressing the "ENTER” key:
Action Display
The power value specifies the total power (3-phase) assuming symmetrical load. If no
key is pressed for 60 seconds, the display automatically returns to the operating status!
3.2 Programming:
,
Pressing the "Operating mode” key once takes the user from automatic operation to
Programming mode. Parameter 1 ( I-CONVERTER) is reached by pressing "ENTER”.
The upper display always shows the parameter and the lower one the set value. The
values are changed by pressing the é / ê keys. Subsequent pressing of the "ENTER” key
stores the value and takes the user to the next parameter.
To quit programming mode in any step, press the "Operating mode” key.
1 I-CONVERTER PRIM: This selects the primary current of the current converter.
Adjustment is via the é / ê keys. (5...7500A) Save and continue
with ENTER
2 I-CONVERTER SEC: This sets the secondary current of the current converter
(5A or 1A possible). Selection via é / ê. Save and continue with
ENTER
3 END STOPP: By setting the end stopp, the number of active capacitor branches is
matched to the respective capacitor bank. This is done via the é / ê
keys. The visible symbols of the capacitors correspond to the connected
outputs. The maximum possible number of capacitor branches is pre-
set at the works (BR 6000-R12:12 branches). The setting is confirmed
and saved with the ENTER key.
4 CONTROL SERIES: The ratio of the capacitor branch powers determines the control
series, the power of the first capacitor always being assigned the value
1. The control series required for the compensation network is again
selected via the é/ê keys. If the required control series should
exceptionally not be present (Annex 1), the user may define a special
one (control series "E”).More on this point in the control-series editor in
Annex 1. The selected series is entered with the ENTER key, which also
takes the user to the next step.
! SEQUENTIAL connection
! LOOP connection
! INTELLIGENT loop connection (default setting)
! COMBINED CHOKE
See Section 8 for an explanation of the various control modes.
Selection with é / ê keys and confirmation with ENTER leads to the
next point:
7 TARGET COS PHI: By setting the target cos phi, the power factor to be attained via
the PF correction is defined. It is also set via the é / ê keys. The
range may be selected from 0.8 inductive to 0.8 capacitive. Confirming
and saving the value with ENTER leads to the next point.
T 2A
BR6000
L N L N k l
Vb Vm Im
10 CONNECTING TIME: This refers to the time between connecting the capacitors to
increase the momentary network capacitance. It should be noted that in practical
operation the real connection time is affected by the discharge time (locking time).
Setting range: 1 sec. ... 20 min. (long time for HV- networks)
Default setting: 10 sec.
Selection is performed via the é /ê keys. Continue with ENTER
12 DISCHARGE TIME: This is the time for which an individual output is blocked
between connecting and disconnecting. This blocking time has priority over
connecting and disconnecting times. It depends on the capacitor discharge rating
and thus is specified by the compensation network. The discharge time of a
conventional network without additional fast-discharge resistors or chokes should be
set to no less than 40 seconds.
For setting of a second discharge time see 'Expert Mode' point 10
Setting range: 1 sec ...20 min. Default setting: 60 sec.
Selection is performed via the é /ê keys. Continue with ENTER
13 ALARM TEMP:
The temperature inside the BR 6000 is measured and converted to the internal
temperature of the switching cabinet. This value can be shown on the display.
The alarm temperature programmed here is the temperature at which the
capacitor stages are disconnected in steps. The controller’s alarm relay
responds after ten minutes. At the same time the display shows the cause of the
alarm (over-temperature). If the temperature drops again, the required
branches are automatically re-connected in steps.
The selection is performed with the é /ê keys. Save and continue with ENTER.
The following parameters are available only for controllers with the/F or /S
options
14 MESSAGE RELAY:
The message relay can be programmed for one of the following options as required:
"External”: The relay switches if an external input signal (230 VAC) is sent to
the "cos-phi2 /external” input. This function may be used to directly
compensate a larger load, for example - the required 40-second
reconnection delay is already integrated.
Display: Capacitor symbol at the top right of the first line.
When this function is selected, the input cannot be used for the
signal 'target cos phi2' and the output cannot be used for the fan.
"Harmonics”: This message appears when the limit of the total harmonic distortion
THD-V is exceeded. This value can be set under "17 Harmonics” in%
"Remote control R1”: Coupling of two controllers via remote control input,
R1= Controller is configured as controller 1 (master)
"Remote control R2”: Coupling of two controllers via remote control input,
R2= Controller is configured as controller 2 (slave).
A description for the coupling of two controllers can be found in the
annex. When this function is selected, the input cannot be used for
the signal 'target cos phi2' and the output cannot be used for the
fan.
Depending on the programming of the message relay, the following parameters may be
selected here:
! Fan option: Input of the switching threshold for the fan (30-70°C) Only active
when option 'Fan' is selected (temperature input as described under point 13)
! Target cos phi2: Input of the second target cos phi as described under point 7,
e.g. tariff conversion.
Input signal 230 VAC at input cos phi => target cos phi 2.
At the active input, the display shows: 2 cos j …
CONTRAST
The display contrast can be changed with this menu point. The contrast depends
to a certain degree on the viewpoint of the observer, i.e. on the insertion height
of the equipment in the switching cabinet. The é /ê keys can be used to set an
optimal contrast. The contrast changes after a slight delay.
Manual operation
ST OP P C 0, 98 CAP
1 2 3 4 5 6 7 8 9 10 11 12
Pressing ENTER takes the user to the menu point "Programming of fixed stages”. In the
normal case, all stages are programmed for automatic operation (default setting).
1 2 3 4 5 6 7 8 9 10 11 12
Currently selected stage blinks
In special cases, all controller outputs (C1 - C12) may be permanently defined in
succession (continued switching via ENTER) for the following statuses:
The active stage is marked by blinking. The required status is set via é /ê. By pressing
ENTER, the user saves this step and moves to the next stage.
The programmed statuses for the outputs also remain visible on the display in automatic
operation.
After the required settings have been made, pressing the "Operating Mode” key takes the
user to the next menu ("Service”) or further to "Automatic Operation”.
Action Display
Expert mode is used to set values which remain unchanged for normal operation. This
level has an access code to protect it from improper operation.
1. Sequential connection
In sequential connection, the required capacitor stages are successively connected
and disconnected in stages (last in - first out). The ranking of each step always
corresponds to the power of the smallest stage.
Advantage: Exact definition of the next capacitor to be connected in each case
Disadvantage: Long settling time, high switching frequency of the small stages
In order to shorten the settling time, the BR 6000 switches several stages
simultaneously for a large power-factor requirement. This applies to all
control types. The maximum dimensions of the simultaneously switching
branches can be changed in expert mode. If the value of the smallest stage
is pre-selected, the conventional sequential connection is obtained.
2. Loop connection
In this variant, the controller operates in loop mode (first in - first out) which
minimizes the wear on the capacitor bank, i.e. where stages are of equivalent
dimensions, the stage which was disconnected for the longest period of time is
always connected next.
Advantage: Balanced utilization of equivalent stages and thus an increased
operating life of the capacitor bank.
Disadvantage: This mode can only be used in control series with groups of the same
stage power and long settling time, as every switching step corresponds to the value
of the smallest stage.
Section 9 Troubleshooting
At target cos phi=1 and inductive load, Check terminals of the measuring voltage and
switch-off or connection of capacitor in current (l and k)!
the corrected line Check phase position
Supply / Drawing mismatched
In strongly asymmetrically loaded lines, Line measurements allow the most favorable
differences may occur between control phase for measuring the power factor to be
response and power-factor determined. The current converter is set
measurement, as the power factor is accordingly for the measuring current.
measured in single phase.
Section 10 Interface *
The BR 6000 should need no maintenance if the operating conditions are observed.
However, it is recommended that a functional check of the controller be performed in
conjunction with the regular checking of the capacitor bank. In the event of any
interventions in the controller during the warranty period, all warranty claims lapse.
Option / F Additional message relay, input for second target cos phi
Option / S As option F, with additional serial interface RS 232 or RS 485
The controllers with transistor outputs are designed for dynamic PFC.
Thyristor switches of type TSM-C... can be controlled directly.
13 Technical data
OPTIONS:
Option /F Input for second target cos phi
additional user programmable message relay
Controller coupling possible
Option /S 232 (485) As option /F with additional interface
RS232 or RS485
1 1:1:1:1:1:1:1:1:1:1:1:1 Possible
2 1:2:2:2:2:2:2:2:2:2:2:2 Possible
3 1:2:3:3:3:3:3:3:3:3:3:3 Possible
4 1:2:3:4:4:4:4:4:4:4:4:4 Possible
5 1:2:4:4:4:4:4:4:4:4:4:4 Possible
6 1:2:3:6:6:6:6:6:6:6:6:6 Possible
7 1:2:4:8:8:8:8:8:8:8:8:8 Possible
8 1:1:1:1:2:2:2:2:2:2:2:2 Possible
9 1:1:1:1:1:6:6:6:6:6:6:6 Possible
10 1:1:2:2:2:2:2:2:2:2:2:2 Possible
11 1:1:2:2:2:4:4:4:4:4:4:4 Possible
12 1:1:2:2:4:4:4:4:4:4:4:4 Possible
13 1:1:1:2:2:2:2:2:2:2:2:2 Possible
14 1:1:2:3:3:3:3:3:3:3:3:3 Possible
15 1:1:2:4:4:4:4:4:4:4:4:4 Possible
16 1:1:2:4:8:8:8:8:8:8:8:8 Possible
17 1:2:2:3:3:3:3:3:3:3:3:3 Possible
18 1:2:3:4:4:8:8:8:8:8:8:8 Possible
19 1:2:2:4:4:4:4:4:4:4:4:4 Possible
20 1:2:2:2:4:4:4:4:4:4:4:4 Possible
The control-series editor allows the user to simply define his/her own control series if the
required control series is not available for any reason.
The last control series - Control Series E - is selected by pressing the "Programming” key
(point 4: Control series) and confirmed with ENTER. This leads to the insertion of an
additional menu point in the main menu -> the control-series editor. It may be reached
via the "Operating Mode” key.
In the control-series editor, all stages can be set in succession to the desired value with
the selection keys é / ê. The next stage in each case is reached by pressing ENTER. An
intelligent pre-selection of the stages is integrated, so that only "meaningful”
control series can be generated. The maximum number of stages can be limited by a
programmed END STOPP < 12.
NEW: In the control series editor, the various steps may be programmed up to a rating of
20 (!). The rating >9 is indicated in the display as follows:
10=A, 11=B, 12=C, 13=D, 14=E, 15=F, 16=G, 17=H, 18=I, 19=J, 20=K
The user may quit the editor with the "Operating Mode” key.
EPCOS FK PM PFC - 20 - Version 2.0E, June 2003
Power Factor Controller BR6000
Note: The following values for the default settings apply only if the controller is supplied
directly from the works. Otherwise, these values are replaced by the basic settings made
by the manufacturer of the compensation network (optimal values for the relevant
network).
0 LANGUAGE ENGLISH
1 I CONVERTER prim. 1000 A
2 I CONVERTER sec. 5 A
3 END STOPP 12 ( 6 )
4 CONTROL SERIES 1
5 CONTROL PRINCIPLE INTELLIGENT
6 POWER 1. STAGE 25.00 kvar
7 TARGET COS-PHI 0.98 IND
8 MEASURING VOLTAGE 230 V L-N
9 V- CONVERTER RATIO - NO -
10 SWITCH- IN TIME 10 sec.
11 SWITCH- OFF TIME 10 sec.
12 DISCHARGE TIME 60 sec.
13 ALARM TEMP. 55 °C
14 MESSAGE RELAY * FAN
15 TEMP. FAN ON 30 °C
16 TARGET COS-PHI 2 0,95 IND
17 HARMONICS THD-V 7,0 %
CONTRAST -7-
Operating lock - NO -
Switching operations 10,000
warning
Fast discharge - NO -
Phase shift U/I 0°
C - Test - YES -
C - Fail 50 %
Test Attempts 5
Baudrate 9600
Protocol MODBUS
Address 1
For example, coupling is useful when two separate installations are operating on two
transformer supplies and a coupling exists for both systems. When the coupling is closed
(because only one supply is working), it is still possible to access the total compensation
power of both installations via the coupling of the controllers. The network is then
operating in master-slave mode. When all stages of the first controller are connected, the
second controller is taking over and switches the remaining stages.
It is therefore also possible to extend networks easily.
When coupling is requested, it is necessary to program "controller1” (as master) or
"controller2” (as slave) in this menu point.
For coupling, the controllers of the two installations have to be connected as follows:
Controller 1 Controller 2
L N L N k l L N L N k l
Ub Um Im Ub Um Im
Br6000 Br6000
external 2.relay external 2.relay
a b P1 1 2 3 4 5 6 P2 7 8 9 10 11 12 1 2 3 4 a b P1 1 2 3 4 5 6 P2 7 8 9 10 11 12 1 2 3 4
alarm- alarm-
relay relay
capacitor- capacitor- capacitor- capacitor-
contactors 1-6 contactors 7-12 contactors 1-6 contactors 7-12
Coupling switch
- 24V+
When the coupling switch is open, both installations are operating independently. When
the coupling is closed, master-slave operation is initiated automatically.
It is an advantage of this simple solution that an additional serial interface is not required.
Part 3 example:
MODBUS – Function 1 (only read - register) MODBUS – Function 10 (only write - register)
BACK TO 1
MANUAL MODE SERVICE EXPERT MODE
15 TEST ATTEMPT
[5]
17 PROTOCOL
[ MODBUS ]
BACK TO 2