Basic parameters
Version2.16 Above chapter is the brief operation parameter, R: readable parameter,RW: readable and
GS40 Operation Manual writeable parameter.Please change parameter when regulator stops.
paramet
description range
defaul
Attributes regist-
er no. t er
1.Features
0-100.0 F-055=0 0
F-000 input value
[%] 0.1% - R
Built-in high performance microcontroller.
0-3000.0 F-055=0 4
Low power consumption design. F-004 output voltage
[V] 0.1V - R
Wide main voltage input(AC110--440V). F-005 output current
0-3000.0
-
F-055=0 5
[A] 0.1A R
Compact design, small dimension.
0-3000.0 F-055=0
F-006 output power
[KW]0.1KW - R 6
Support 4-20mA,0-10v analogue input.
F-055=35
Perfect protection: Phase lose, overheat, overcurrent, load lose. F-017 Current fault 0-100 - R 17
Modbus communication(optional). 0-100.0 F-055=35
F-030 Set-point through communication
% .1% 0 RW 30
2.Dimension
Menu Authority
F-055
0:Read-only parameter is displayed
0 - 3000 0 F-055=0 55
35:Display simple parameter and read-only RW
parameter
Reference types
F-061 33 - 54 50 F-055=35
50 :Analog value set-point
RW 61
51 :Set-point through communication
F-055=35 68
F-068 Given value top limit 0-100.0 100.0 RW
3.Keyboard operation
Rated voltage :The same as nameplate . Data can
F-077 be changed according to actual load , for the
0-3000 380 F-055=35
[V] 1V RW 77
purpose of protecting device
F-111
Feedback Type 0-1 1 F-055=35
0:Open loop 1:closed loop 1 RW 111
F-055=0
F-125 Previous fault type - - RW 125
F-127
Power fault protection enables 0:Disable 1:alarm 0-1 2 F-055=35
2:alarm + relay 3:alarm + relay +s top 1 RW -
F-128
Load fault protection enables 0:Disable 1:alarm 0-1 0 F-055=35
2:alarm + relay 3:alarm + relay+stop 1 RW -
F-133
device address 1-247 123 F-055=35 -
Setting address of Modbus and Profibus 1 RW
baud rate
4.Terminal description 0-4 F-055=35 -
F-134 0:2400 1:4800 2:9600
1 2 RW
3:19200 4:38400
Data format
0:8n2 Date bit 8 bits, no calibration, 2 stop bits
F-135 1:8e1 Date bit 8 bits, parity - checking, 1 stop bits
0-2 1 F-055=35 -
2:8o1 Date bit 8 bits, odd parity -checking, 1stop 1 RW
bits
R
E009 Overload of regulator, load current is bigger than rated current of regulator.
Output
F-008
Start/stop signal Signal source of start/stop 0-2 0 R
percentage 0: switch off 1: switch on 2:fault 1 8
F-012
Current analog type 0:0-20mA1:4-20mA 0-2 1 RW 12
power 2:Integrated slope control 1
F-014
Ramp-down time Before the ramp signal processing 0-120 2 RW 14
dropped from 0.0% to 100% of the time required 1
description function
LED Status and parameter value display Output ceiling 0-100.0 15
F-015 [%] 0.1%
100.0 RW
POWER Maximum output limit
Power
RUN Equipment operation Output limit 0-100.0
F-016 0 RW 16
FAULT Equipment failure Output minimum value [%] 0.1%
Enter the parameters Proportion 0-200
F-017 1 80 RW 17
Data up PID control proportional factor
Data down
Integral 0-200 18
Switch and confirm the data F-018 1 5 RW
PID control integral time
Start the device
Stop the device and fault reset F-019
Differential 0-200 0 RW 19
PID control differential time 1
F-023
Control mode 0:Closed-loop phase shift 1: 0-2 23
1 0 RW
Open loop phase shift 2:Zero trigger
SW4
NM8
10
U V W +10V AI1 AI2 AI3 AI4 GND SW1 SW2 SW3 AI1 end correction
50-150.0
F-027 This parameter is set so that 20mA
[%] 0.1%
100.0 RW 27
4-20mA
corresponds to a given input 100%
AI2 end correction This parameter is set so
LOAD F-029 50-150.0 29
Analog Input Switch Input
that 5V /10Vcorresponds to a given input
[%] 0.1%
100.0 RW
100%
The default is stop start signal SW1, SW2 default switch between AI1 and AI2, closed AI2
F-033
AI1 Signal selection 0-1 33
1
0 RW
given signal is valid, disconnect AI1 given signal is valid. SW3 is a programmable port, refer to parameter F38 0:0-5V 1:0-10V
AI3, AI4 and SW4 are reserved pins Device Address 0-247
F-035 123 RW 35
5、Communication This parameter sets the Modbus address 1
M8 Series power regulator supports Modbus protocols.Modbus supports 3、4、6、16, Baud Rate 36
totally 4 functions, F-35: slave station address: 1-247,F-36 baud rate:2400 4800 9600 F-036 0-4 2
0:2400 1:4800 2:9600 1 RW
19200 38400.F-37: data format: 8n2 8e1 8o1 8n1, 4 types.Parameter value is 16bits no signal 3:19200 4:38400
register, decimal point is not supported.For example, before writing 56.7, it should be Data format 0:8n2 Date bit 8 bits, no calibration, 2
adjusted as 567 and then re-write. stop bits 1:8e1 Date bit 8 bits, parity - checking, 1 0-3 37
Notice: every frame cannot exceed 20 bytes, so every frame can maximum read 10 parameters F-037 stop bits 2:8o1 Date bit 8 bits, odd parity -checking, 1 1 RW
Read Holding Registers frame format 1stop bits 3:8n1 data bit, 8 bits, no check, 1 stop bit
www.noker-inverter.com
Xi'an Noker Electric Co.,Ltd.
6 basic parameter
Version 1. 13
NK10T Operation Manual Above chapter is the brief operation parameter, R: readable parameter,RW: readable and
writeable parameter.Please change parameter when regulator stops.
1 Product Description paramet defaul
description range Attributes Register
er no. t
●Built-in High-performance, Low-power ●Efficient cooling solution ●One relay output
Microcontroller such small size, light weight - 3A AC250V 0-100.0 F-055=0
F-000 input value
[%] 0.1% - R 0
●Peripheral Features ●Practical alarm function - 3A DC30V
- Support 4-20mA and 0-5V/10Vtwo - Phase failure ●Max Current 150A 0-3000.0 F-055=0
given - Overheat F-004 output voltage
[V] 0.1V - R 4
- Two switch inputs - Overcurrent ●To facilitate centralized
- Wide Range Of Primary Loop - Load break control RS485 communication 0-3000.0 F-055=0
F-005 output current
[A] 0.1A - R 5
Voltages(AC110-440V)
F-006 0-3000.0 - F-055=0
2 Size output power
[KW]0.1KW R 6
2.1 0-40A Current fault F-055=35
F-017 0-100 - R 17
128 80 73
0-100.0 F-055=35
F-030 Set-point through communication
[%] 0.1% 0 RW 30
R3 Menu Authority
0:Read-only parameter is displayed F-055=0
F-055 35:Display simple parameter and read-only 0-3000 0 RW 55
1
2
P+
parameter
3 4-20mA
4 GND NET
5 SW 1
Reference types
6 SW 2
F-055=35
F-061 33-54 50
160
7
50 :Analog value set-point 61
120
GND
8
9
+
-
RS 485
13
14
160-240VAC
F-065 communication
0-1 0 RW 65
Digital setting power saving F-055=35
F-066 0:s aving 1:n ot saving 0-1 0 RW 66
F-111
Feedback Type 0-1 1
F-055=35
111
1 P+
2
3 4-20mA
0:Open loop 1:closed loop 1 RW
4 GND NET
5
100
SW 1
6 SW 2
Trigger Mode 0-1 F-055=35
160
7 GND
F-114 0:Phase shifter 1:Zero trigger 1 114
8
9
+
-
RS 485 1 RW
10 DP
OUTPUT
F-055=0
11
F-125 - -
12 SYNC
F-127
Power fault protection enables 0:Disable 1:alarm 0-3 2
F-055=35
2:alarm+relay 3:alarm+relay +s top 1 RW 127
F-128
Load fault protection enables 0:Disable 1:alarm 0-3 0
F-055=35
2:alarm+relay 3:alarm+relay+stop 1 RW 128
www.noker-inverter.com
Xi'an Noker Electric Co.,Ltd.
7、basic parameter
Version 1.15 Above chapter is the brief operation parameter, R: readable parameter,RW: readable and
NK30T Operation Manual writeable parameter.Please change parameter when regulator stops.
316
120
335
186
340
360
251
[%] 0.1%
F-011
Given signal type selection 0-1 11
3、 Keyboard operation 1 0 RW
0:Analog 1:Digital
Initial menu Parameter Data
Current analog type 0:0 -20mA 1:4 -20mA 0-2
Input percentage F-012 1 RW 12
2:Integrated slope control 1
F-014
Ramp-down time Before the ramp signal processing 0-120 2 RW 14
dropped from 0.0% to 100% of the time required 1
flash
save
voltage Output ceiling 0-100.0
F-015 100.0 RW 15
Maximum output limit [%] 0.1%
constant Output limit 0-100.0
current F-016 0 RW 16
Output minimum value [%] 0.1%
Overheat of regulator, heat-sink temperature is bigger than 85, possible reason: Frequency 0-2 50
F-050 1 0 RW
1、Ambient temperature is higher than 45. 0:50HZ 1:60HZ 2:Automatic tracking
E005 2、Fan breaks.
3、Dust on the ventilation path.