0% found this document useful (0 votes)
39 views4 pages

Catalog SCR

The GS40 and NM8 Operation Manuals detail the features, parameters, and operational guidelines for Xi'an Noker Electric Co., Ltd.'s power regulators. Key features include high-performance microcontrollers, low power consumption, and various protection mechanisms. The documents also outline communication protocols, fault codes, and maintenance recommendations for optimal device performance.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
39 views4 pages

Catalog SCR

The GS40 and NM8 Operation Manuals detail the features, parameters, and operational guidelines for Xi'an Noker Electric Co., Ltd.'s power regulators. Key features include high-performance microcontrollers, low power consumption, and various protection mechanisms. The documents also outline communication protocols, fault codes, and maintenance recommendations for optimal device performance.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Xi'an Noker Electric Co.,Ltd. 6.

Basic parameters
Version2.16 Above chapter is the brief operation parameter, R: readable parameter,RW: readable and
GS40 Operation Manual writeable parameter.Please change parameter when regulator stops.
paramet
description range
defaul
Attributes regist-
er no. t er
1.Features
0-100.0 F-055=0 0
F-000 input value
[%] 0.1% - R
 Built-in high performance microcontroller.
0-3000.0 F-055=0 4
 Low power consumption design. F-004 output voltage
[V] 0.1V - R
 Wide main voltage input(AC110--440V). F-005 output current
0-3000.0
-
F-055=0 5
[A] 0.1A R
 Compact design, small dimension.
0-3000.0 F-055=0
F-006 output power
[KW]0.1KW - R 6
 Support 4-20mA,0-10v analogue input.
F-055=35
 Perfect protection: Phase lose, overheat, overcurrent, load lose. F-017 Current fault 0-100 - R 17
 Modbus communication(optional). 0-100.0 F-055=35
F-030 Set-point through communication
% .1% 0 RW 30
2.Dimension
Menu Authority
F-055
0:Read-only parameter is displayed
0 - 3000 0 F-055=0 55
35:Display simple parameter and read-only RW
parameter
Reference types
F-061 33 - 54 50 F-055=35
50 :Analog value set-point
RW 61
51 :Set-point through communication

Digital given type 0:Keypad set-point 1: F-055=35


F-065 communication
0-1 0 RW 65

F-066 Digital setting power saving F-055=35 66


0:saving 1:not saving 0-1 0 RW

F-055=35 68
F-068 Given value top limit 0-100.0 100.0 RW
3.Keyboard operation
Rated voltage :The same as nameplate . Data can
F-077 be changed according to actual load , for the
0-3000 380 F-055=35
[V] 1V RW 77
purpose of protecting device

Feedback signal type F-055=35


F-086 7:voltage 8:current 9:power 0-33 7 RW 86

Analogue signal type


0-4 0 F-055=35
F-097 0:0-20mA, 1:4-20mA, 2:0-10V, 3:0-5V,4:4-20mA/0-10V 1 RW 99

F-111
Feedback Type 0-1 1 F-055=35
0:Open loop 1:closed loop 1 RW 111

Trigger Mode 0-1 F-055=35


F-114 0:Phase shifter 1:Zero trigger 1 1 RW 114

F-055=0
F-125 Previous fault type - - RW 125

F-127
Power fault protection enables 0:Disable 1:alarm 0-1 2 F-055=35
2:alarm + relay 3:alarm + relay +s top 1 RW -

F-128
Load fault protection enables 0:Disable 1:alarm 0-1 0 F-055=35
2:alarm + relay 3:alarm + relay+stop 1 RW -

F-129 Load-off threshold


10-70 70 F-055=35 -
[%] 1% RW

F-133
device address 1-247 123 F-055=35 -
Setting address of Modbus and Profibus 1 RW
baud rate
4.Terminal description 0-4 F-055=35 -
F-134 0:2400 1:4800 2:9600
1 2 RW
3:19200 4:38400
Data format
0:8n2 Date bit 8 bits, no calibration, 2 stop bits
F-135 1:8e1 Date bit 8 bits, parity - checking, 1 stop bits
0-2 1 F-055=35 -
2:8o1 Date bit 8 bits, odd parity -checking, 1stop 1 RW
bits
R

F-140 Hardware edition - - F-055=0 -

F-141 Software edition - - F-055=0 -


R

7.Fault and maintenance


fault code description
Main power fault, possible fault reason:
E002 1、No voltage of mail loop or not the same of nameplate .
2、Synchronous cable of terminal 12 is not connected, please refer to the wiring
drawing.
Overcurrent, measured current exceeds 1.25 time of rated current, possible
reason:
E003 1、Load changes rapidly or short-circuit.
2、Thyristor breaks .
Load-off, load off current = set-point percentage * rated current * load threshold,
alarms when difference between set-pint and measured current is bigger than
load off current. Possible reason:
E004 1、Load off
2、Load current is small
3、Setting of(F-129)is small
Overheat of regulator, heat-sink temperature is bigger than 85, possible reason:
1、Ambient temperature is higher than 45.
E005 2、Fan breaks.
3、Dust on the ventilation path.

E009 Overload of regulator, load current is bigger than rated current of regulator.

5.Communication E010 Thyristor breaks,Thyristor damage detected alarm is activated.


GS40 Series power regulator supports Modbus protocols.Modbus supports 3、4、6、16,
totally 4 functions, F-35: slave station address: 1-247,F-36 baud rate:2400 4800 9600 7.2.Daily maintenance
19200 38400.F-37: data format: 8n2 8e1 8o1, 3 types.Parameter value is 16bits no signal
register, decimal point is not supported.For example, before writing 56.7, it should be Fault might happen because of using temperature, humidity, dust and some other
adjusted as 567 and then re-write. reason, daily maintenance is needed, user can do the check and maintain within
Notice: every frame cannot exceed 20 bytes, so every frame can maximum read 10 parameters,
The register of the host computer starts from 1 and the register number is incremented by 1. 3~6 months, checking lists are as below:
If the register number is F004, it should be filled with 5. 1:Mainl loop connector.
2 : Clean PCB board, ventilation, fans.
Read Holding Registers frame format 3 :Regulator should be electricity every 3 months if not use.
4 : Prevent from high temp. humidity and metal powder location.
0 1 2 3 4 5 6 7
Function Starting Starting No. of No. of
CRC CRC
7.3.Spare part/maintain
Addr Address Address Points Points
03H Hi Lo Hi Lo H L 1:Please contact service centre +86 029-83754508 for maintenance.
Preset Single Register frame format :
2Please contact NOKER for buying spare parts.
0 1 2 3 4 5 6 7 8.Order no.
Function Starting Starting Preset Preset
CRC CRC
Addr
06H
Address Address Data
Hi Lo Hi
Data
Lo H L GS40
Single-phase Rated current ()A
power regulator www.noker-inverter.com
Xi'an Noker Electric Co.,Ltd.
NM8 Operation Manual 7、basic parameter
Version1.17 Above chapter is the brief operation parameter, R: readable parameter,RW: readable and
1、Product Description
writeable parameter.Please change parameter when regulator stops.
●Built-in High-performance, Low-power ●Efficient cooling solution ●One relay output
Microcontroller such small size, light weight - 3A AC250V paramet defaul
description range Attributes
●Peripheral Features - 3A DC30V er no. t
●Practical alarm function
- Support 4-20mA and 0-5/10V (pote- - Phase failure ●To facilitate centralized
ntiometer) two given F-000 0-100.0
- Overheat control RS485 communication Valid output - R 0
- Three switch inputs [%] 0.1%
- Overcurrent
- Wide Range Of Primary Loop - Load break
Voltages(AC260-440V) F-001 0-100.0 - R
Valid input
[%] 0.1% 1
2、Size
F-002 Output voltage 0-3000.0 - R 2
DIM. Installation Install [V] 0.1V
Current(A) G.W. cool down
L W H L W bolts
25-125 Fan F-004 0-3000.0 - R
270 145 214 250 75/75 6 M8 A phase Output current
[A] 0.1A 4
150-175 335 165 214 315 95/75 11 M8 Fan
200-250 425 245 238 399 160/178 16 M10 Fan 0-3000.0
F-005 B phase Output current - R 5
300-400 435 265 255 413 158/176 22 M10 Fan [A] 0.1A

3、 Keyboard operation F-006 C phase Output current 0-3000.0 - R 6


[A] 0.1A
Initial menu Parameter Data
Input percentage
F-007 0-3000.0 7
Output power
[KW]0.1KW - R

Output
F-008
Start/stop signal Signal source of start/stop 0-2 0 R
percentage 0: switch off 1: switch on 2:fault 1 8

F-009 Digital setting signal input 0-100.0 0 RW 9


flash [%] 0.1%
voltage
F-010
Start-stop control mode selection 0-1 0 RW 10
0:External switch 1:panel 2:communication 1
constant
current Given signal type selection 0-1 11
F-011 1 0 RW
0:Analog 1:Digital

F-012
Current analog type 0:0-20mA1:4-20mA 0-2 1 RW 12
power 2:Integrated slope control 1

Ramp-up time Signal processing before the 0-120 13


F-013 1 2 RW
ramp from 0.0% to 100% of the time required

F-014
Ramp-down time Before the ramp signal processing 0-120 2 RW 14
dropped from 0.0% to 100% of the time required 1
description function
LED Status and parameter value display Output ceiling 0-100.0 15
F-015 [%] 0.1%
100.0 RW
POWER Maximum output limit
Power
RUN Equipment operation Output limit 0-100.0
F-016 0 RW 16
FAULT Equipment failure Output minimum value [%] 0.1%
Enter the parameters Proportion 0-200
F-017 1 80 RW 17
Data up PID control proportional factor
Data down
Integral 0-200 18
Switch and confirm the data F-018 1 5 RW
PID control integral time
Start the device
Stop the device and fault reset F-019
Differential 0-200 0 RW 19
PID control differential time 1

Feedback signal source 0-2 20


4、Terminal description F-020 1
0 RW
0:Voltage 1:current 2:power
Input Power Output relay 485
AC260-440V AC160-240V 3A/AC250V RS485 Limiter signal source 0-1 21
F-021 1 0 RW
0:Current 1:Voltage
R S T L N 1N 1C A B Limit percent 0-100.0
F-022 100 RW 22
Set as a percentage of the limit signal [%] 0.1%
19 20 16 17 12 13
GND
11

F-023
Control mode 0:Closed-loop phase shift 1: 0-2 23
1 0 RW
Open loop phase shift 2:Zero trigger
SW4

NM8
10

Zero crossing mode: 0-1


F-026 0 RW 26
1 2 3 4 5 6 7 8 9 0:Fixed period 1:Variable period 0

U V W +10V AI1 AI2 AI3 AI4 GND SW1 SW2 SW3 AI1 end correction
50-150.0
F-027 This parameter is set so that 20mA
[%] 0.1%
100.0 RW 27
4-20mA
corresponds to a given input 100%
AI2 end correction This parameter is set so
LOAD F-029 50-150.0 29
Analog Input Switch Input
that 5V /10Vcorresponds to a given input
[%] 0.1%
100.0 RW
100%
The default is stop start signal SW1, SW2 default switch between AI1 and AI2, closed AI2
F-033
AI1 Signal selection 0-1 33
1
0 RW
given signal is valid, disconnect AI1 given signal is valid. SW3 is a programmable port, refer to parameter F38 0:0-5V 1:0-10V
AI3, AI4 and SW4 are reserved pins Device Address 0-247
F-035 123 RW 35
5、Communication This parameter sets the Modbus address 1
M8 Series power regulator supports Modbus protocols.Modbus supports 3、4、6、16, Baud Rate 36
totally 4 functions, F-35: slave station address: 1-247,F-36 baud rate:2400 4800 9600 F-036 0-4 2
0:2400 1:4800 2:9600 1 RW
19200 38400.F-37: data format: 8n2 8e1 8o1 8n1, 4 types.Parameter value is 16bits no signal 3:19200 4:38400
register, decimal point is not supported.For example, before writing 56.7, it should be Data format 0:8n2 Date bit 8 bits, no calibration, 2
adjusted as 567 and then re-write. stop bits 1:8e1 Date bit 8 bits, parity - checking, 1 0-3 37
Notice: every frame cannot exceed 20 bytes, so every frame can maximum read 10 parameters F-037 stop bits 2:8o1 Date bit 8 bits, odd parity -checking, 1 1 RW
Read Holding Registers frame format 1stop bits 3:8n1 data bit, 8 bits, no check, 1 stop bit

0 1 2 3 4 5 6 7 Programmable port SW3


0-5
F-038 0. No 2. Fault reset 3. External fault input
1 1 RW 38
Function Starting Starting No. of No. of
CRC CRC 5. Cm switch
Addr Address Address Points Points
03H Hi Lo Hi Lo H L Output relay 0-1
F-040 1 0 RW 40
Preset Single Register frame format 0:Fault 1:Start status
0-100
0 1 2 3 4 5 6 7 F-041 Previous fault
1 - RW 41
Function Starting Starting Preset Preset
CRC CRC Allow overcurrent protection 0-1
Addr Address Address Data Data F-042 1 RW -
06H H L 0:Disable 1:Enable 1
Hi Lo Hi Lo
6、Fault and maintenance Phase protection permit
1、Fault list F-043 0:Disable 1:Enable 2:Automatic fault reset 0-1 -
1 1 RW
3:Delay alarm 4:Delayed automatic recovery
fault description
code F-044
Load fault protection enables 0-1 1 RW -
0:Disable 1:Enable 1
Main power fault, possible fault reason: 10-70
E002 F-045 Load-off threshold
[%] 1% 70 RW -
1、No voltage of mail loop or not the same of nameplate.
F-046
Thyristor thermal protection allows 0-1 1 RW -
0:Disable 1:Enable 1
Overcurrent, measured current exceeds 1.25 time of rated current,possible reason:
E003 1、Load changes rapidly or short-circuit. Rated voltage :The same as nameplate. Data can
2、Thyristor breaks. be changed according to actual load, for the 48
F-048 purpose of protecting device
0-3000 380 RW
Load-off, load off current = set-point percentage * rated current * load threshold, Notice: cannot exceed nominated value on the [V] 0.1V
alarms when difference between set-pint and measured current is bigger than load nameplate
off current. Possible reason:
E004 1、Load off Rated current:The same as nameplate. Data can be
2、Load current is small changed according to actual load, for the purpose of 49
F-049 protecting device
0-3000 - RW
3、Setting of(F-45)is small [A] 0.1A
Notice: cannot exceed nominated value on the
Overheat of regulator, heat-sink temperature is bigger than 85, possible reason: nameplate
1、Ambient temperature is higher than 45.
E005 2、Fan breaks. Frequency 0-2
F-050 1 0 RW 50
3、Dust on the ventilation path. 0:50HZ 1:60HZ 2:Automatic tracking

www.noker-inverter.com
Xi'an Noker Electric Co.,Ltd.
6 basic parameter
Version 1. 13
NK10T Operation Manual Above chapter is the brief operation parameter, R: readable parameter,RW: readable and
writeable parameter.Please change parameter when regulator stops.
1 Product Description paramet defaul
description range Attributes Register
er no. t
●Built-in High-performance, Low-power ●Efficient cooling solution ●One relay output
Microcontroller such small size, light weight - 3A AC250V 0-100.0 F-055=0
F-000 input value
[%] 0.1% - R 0
●Peripheral Features ●Practical alarm function - 3A DC30V
- Support 4-20mA and 0-5V/10Vtwo - Phase failure ●Max Current 150A 0-3000.0 F-055=0
given - Overheat F-004 output voltage
[V] 0.1V - R 4
- Two switch inputs - Overcurrent ●To facilitate centralized
- Wide Range Of Primary Loop - Load break control RS485 communication 0-3000.0 F-055=0
F-005 output current
[A] 0.1A - R 5
Voltages(AC110-440V)
F-006 0-3000.0 - F-055=0
2 Size output power
[KW]0.1KW R 6
2.1 0-40A Current fault F-055=35
F-017 0-100 - R 17
128 80 73
0-100.0 F-055=35
F-030 Set-point through communication
[%] 0.1% 0 RW 30

R3 Menu Authority
0:Read-only parameter is displayed F-055=0
F-055 35:Display simple parameter and read-only 0-3000 0 RW 55
1
2
P+
parameter
3 4-20mA

4 GND NET

5 SW 1
Reference types
6 SW 2
F-055=35
F-061 33-54 50
160

7
50 :Analog value set-point 61

120
GND

8
9
+

-
RS 485

51 :Set-point through communication RW


10 DP
OUTPUT
11

Digital given type 0:Keypad set-point 1: F-055=35


12 SYNC

13
14
160-240VAC

F-065 communication
0-1 0 RW 65
Digital setting power saving F-055=35
F-066 0:s aving 1:n ot saving 0-1 0 RW 66

Rated voltage :The same as nameplate. Data can


0-3000 F-055=35
F-077 be changed according to actual load, for the
[V] 1V 380 RW 77
purpose of protecting device
2.2 75- 150A (Unit:mm)
128 80 73 Feedback signal type 0-33 F-055=35
F-086 7:voltage 8:current 9:power 1 7 RW 86

R3 AI2 Signal types 0-1 0 F-055=35


F-099 0:0-5V 1:0-10V 1 RW 99

F-111
Feedback Type 0-1 1
F-055=35
111
1 P+

2
3 4-20mA
0:Open loop 1:closed loop 1 RW
4 GND NET

5
100

SW 1

6 SW 2
Trigger Mode 0-1 F-055=35
160

7 GND
F-114 0:Phase shifter 1:Zero trigger 1 114
8
9
+

-
RS 485 1 RW
10 DP
OUTPUT

F-055=0
11

F-125 - -
12 SYNC

Previous fault type 125


RW
13
160-240VAC
14

F-127
Power fault protection enables 0:Disable 1:alarm 0-3 2
F-055=35
2:alarm+relay 3:alarm+relay +s top 1 RW 127

F-128
Load fault protection enables 0:Disable 1:alarm 0-3 0
F-055=35
2:alarm+relay 3:alarm+relay+stop 1 RW 128

F-129 10-70 F-055=35


Load-off threshold
[%] 1% 70 RW 129
3 Keyboard operation
device address 1-247 F-055=35
F-133 Setting address of Modbus and Profibus 1
123 RW -
Initial menu Parameter Data
Input percentage baud rate
F-134 0:2400 1:4800 2:9600
0-4 2 F-055=35
1 RW -
3:19200 4:38400
Radiator Data format
Temperature 0:8n2 Date bit 8 bits, no calibration, 2 stop bits
F-135
1:8e1 Date bit 8 bits, parity - checking, 1 stop bits 0-3 1 F-055=35 -
2:8o1 Date bit 8 bits, odd parity -checking, 1stop 1 RW
bits
blink save 3:8n1 Date bit 8 bits, no calibration, 1 stop bits
voltage
F-055=0
F-140 Hardware edition - - R -
Constant
current F-055=0
F-141 Software edition - - R -
communication
7 Fault and maintenance
power RUN FAULT COM
7.1 Fault list

fault code description


Main power fault, possible fault reason:
E002 1、No voltage of mail loop or not the same of nameplate.
2、Synchronous cable of terminal 12 is not connected, please refer to the wiring
drawing.
4 Terminal description Overcurrent, measured current exceeds 1.25 time of rated current, possible
reason:
E003 1、Load changes rapidly or short-circuit.
Input Power Output relay 1:5V DC Potentiometer power
2、Thyristor breaks.
AC110-440V AC90-260V OUTPUT RS485 2:0-20/4-20mA
Load-off, current <set-point percentage * rated current * load threshold,
SYN N L ON2 ON1 B A 3:0-5V/10DC Resistance≥10K
Possible reason:
5:Run/Stop E004 1、Load off
L1 12 14 13 11 10 9 8 6:change0-5V/4-20mA 2、Load current is small
open:4-20mA close:0-5V 3、Setting of(F-129)is large
NK10T 4、7:Common Overheat of regulator, heat-sink temperature is bigger than 85, possible reason:
8、9:RS485communication 1、Ambient temperature is higher than 45.
E005 2、Fan breaks.
L2 1 2 3 4 5 6 7
10、11:output relay 3、Dust on the ventilation path.
P+ AI1 AI2 GND SW1 SW2 GND 3A 250VAC/3A 35VDC
E009 Overload of regulator, load current is bigger than rated current of regulator.
12:Synchronization signal
load 4-20mA E010 Thyristor breaks,Thyristor damage detected alarm is activated.
13、14:powerAC100-240V
7.2 daily maintenance
5 Communication
Fault might happen because of using temperature, humidity, dust and some other
10T Series power regulator supports Modbus-RTU protocol. reason, daily maintenance is needed, user can do the check and maintain within
function:supports 3、4、6、16 baud rate:2400 4800 9600 19200 38400 3~6 months, checking lists are as below:
data format:8n2、8e、8o1 station address:1-247 register:16 bit unsigned integer 1:Mainl loop connector.
Notice: every frame cannot exceed 20 bytes, so every frame can maximum read 10 parameters. 2:Clean PCB board, ventilation, fans.
decimal point is not supported.For example, before writing 56.7, it should be adjusted as 567 3:Regulator should be electricity every 3 months if not use.
and then re-write.The register of the host computer starts from 1 and the register number is
4:Prevent from high temp. humidity and metal powder location.
incremented by 1. If the register number is F004, it should be filled with 5. 9.3 spare part/maintain
Read Holding Registers frame format
1:Please contact service centre + 86 029-83754508 for maintenance.
0 1 2 3 4 5 6 7 2:Please contac NOKE R for buying spare parts.
Function Starting Starting No. of No. of
CRC CRC 8 Order no. code
Addr Address Address Points Points
03H Hi Lo Hi Lo H L
Optional: P Profibus DP
Preset Single Register frame format NK10T C MODBUS TCP/IP
0 1 2 3 4 5 6 7 T Temperature function
Single-phase Rated current(A): Optional R TRMS vaue
Function Starting Starting Preset Preset power regulator
Addr Address Address Data Data CRC CRC
06H Hi Lo Hi Lo H L

www.noker-inverter.com
Xi'an Noker Electric Co.,Ltd.
7、basic parameter
Version 1.15 Above chapter is the brief operation parameter, R: readable parameter,RW: readable and
NK30T Operation Manual writeable parameter.Please change parameter when regulator stops.

1、Product Description paramet defaul


description range Attributes
er no. t
●Built-in High-performance, Low-power ●Efficient cooling solution ●One relay output
Microcontroller such small size, light weight - 3A AC250V 0-100.0
- 3A DC30V F-000 Valid output
[%] 0.1% - R 0
●Peripheral Features
●Practical alarm function
- Support 4-20mA and 0-5/10V (pote- - Phase failure ●To facilitate centralized
ntio meter) two given F-001 0-100.0 -
- Overheat control RS485 communication Valid input
[%] 0.1% R 1
- Two switch inputs - Overcurrent
- Wide Range Of Primary Loop - Load break
Voltages(AC110-440V) F-002 Output voltage 0-3000.0 - R 2
[V] 0.1V
2、Size (Unit:mm)
1、10-50A 3、150A 0-3000.0
209 164 100 F-004 A phase Output current
[A] 0.1A - R 4
125 80 73 Φ9
17

B phase Output current 0-3000.0


F-005 [A] 0.1A - R 5

316
120

335
186

C phase Output current 0-3000.0 6


F-006 [A] 0.1A - R
6
F-007 Output power 0-3000.0 - R 7
2、75-120A 4、200-300A [KW]0.1KW
25

169 136 122 228 194 120 9


F-008
Start/stop signal Signal source of start/stop 0-1
0: switch off 1: switch on 1 0 R 8
160

F-009 Digital setting signal input 0-100.0 0 RW 9

340
360
251

[%] 0.1%

Start-stop control mode selection 0-1 10


F-010 1 0 RW
7 0:External switch 1:panel

F-011
Given signal type selection 0-1 11
3、 Keyboard operation 1 0 RW
0:Analog 1:Digital
Initial menu Parameter Data
Current analog type 0:0 -20mA 1:4 -20mA 0-2
Input percentage F-012 1 RW 12
2:Integrated slope control 1

Ramp-up time Signal processing before the 0-120 13


Output F-013 1
2 RW
percentage ramp from 0.0% to 100% of the time required

F-014
Ramp-down time Before the ramp signal processing 0-120 2 RW 14
dropped from 0.0% to 100% of the time required 1
flash
save
voltage Output ceiling 0-100.0
F-015 100.0 RW 15
Maximum output limit [%] 0.1%
constant Output limit 0-100.0
current F-016 0 RW 16
Output minimum value [%] 0.1%

POWER Parameter Return Proportion 0-200


F-017 1 80 RW 17
PID control proportional factor
power RUN

FAULT Integral 0-200 18


F-018 1 5 RW
COM
PID control integral time
NC
F-019
Differential 0-200 19
1 0 RW
PID control differential time
4、Terminal description
Feedback signal source 0-2 20
F-020 1 0 RW
Input Power Output relay 0:Voltage 1:current 2:power
AC260-440V AC160-240V 3A/AC250V RS485-RTU
F-021
Limiter signal source 0-1 0 21
1 RW
0:Current 1:Voltage
R S T L N ON1 ON2 A B
F-022
Limit percent 0-100.0 100 22
14 15 11 12 8 9 [%] 0.1% RW
Set as a percentage of the limit signal

Control mode 0:Closed-loop phase shift 1: 0-2 23


F-023 1 0 RW
NK30T Open loop phase shift 2:Zero trigger

AI1 end correction


1 2 3 4 5 6 7 50-150.0
F-027 This parameter is set so that 20mA
[%] 0.1%
100.0 RW 27
U V W P+ AI1 AI2 GND SW1 SW2 GND corresponds to a given input 100%
AI2 end correction This parameter is set so
F-029 that 5V /10Vcorresponds to a given input 50-150.0 100.0 RW 29
4-20mA [%] 0.1%
100%
load Analog Input Switch Input AI1 Signal selection 0-1 33
F-029 1
0 RW
The default is stop start signal SW1, SW2 default switch between AI1 and AI2, closed AI2 0:0-5V 1:0-10V
given signal is valid, disconnect AI1 given signal is valid.
5、Communication Device Address 0-247 35
F-035 123 RW
30T Series power regulator supports Modbus protocols.Modbus supports 3、4、6、16, This parameter sets the Modbus address 1
totally 4 functions, F-35: slave station address: 1-247,F-36 baud rate:2400 4800 9600 Baud Rate
19200 38400.F-37: data format: 8n2 8e1 8o1, 3 types.Parameter value is 16bits no signal 0-4 36
F-036 0:2400 1:4800 2:9600 2 RW
register, decimal point is not supported.For example, before writing 56.7, it should be 1
3:19200 4:38400
adjusted as 567 and then re-write.
Notice: every frame cannot exceed 20 bytes, so every frame can maximum read 10 parameters, Data format 0:8n2 Date bit 8 bits, no calibration, 2
The register of the host computer starts from 1 and the register number is incremented by 1. stop bits 1:8e1 Date bit 8 bits, parity - checking, 1 0-2 37
If the register number is F004, it should be filled with 5. F-037 stop bits 2:8o1 Date bit 8 bits, odd parity -checking, 1 1 RW
Read Holding Registers frame format 1stop bits

0 1 2 3 4 5 6 7 Output relay 0-1 40


F-040 1 0 RW
0:Fault 1:Start status
Function Starting Starting No. of No. of
CRC CRC
Addr Address Address Points Points 41
03H H L
F-041 0-100
Hi Lo Hi Lo Previous fault
1 - RW
Preset Single Register frame format
Allow overcurrent protection 0-1 -
0 1 2 3 4 5 6 7 F-042 1 1 RW
0:Disable 1:Enable
Function Starting Starting Preset Preset
CRC CRC
Addr Address Address Data Data Phase protection permit 0-1 -
06H Hi Lo Hi Lo H L F-043 1 1 RW
0:Disable 1:Enable
6、Fault and maintenance
Load fault protection enables 0-1 -
1、Fault list F-044 0:Disable 1:Enable 1 1 RW
fault description -
Load-off threshold 10-70
code F-045 [%] 1% 70 RW

Main power fault, possible fault reason:


Thyristor thermal protection allows 0-1 -
E002 1、No voltage of mail loop or not the same of nameplate. F-046 1 1 RW
0:Disable 1:Enable
2、Synchronous cable of terminal 12 is not connected, please refer to the wiring
drawing. Rated voltage :The same as nameplate. Data can
Overcurrent, measured current exceeds 1.25 time of rated current,possible reason: be changed according to actual load, for the 48
F-048 0-3000
E003 1、Load changes rapidly or short-circuit. purpose of protecting device
[V] 0.1V 380 RW
2、Thyristor breaks. Notice: cannot exceed nominated value on the
nameplate
Load-off, load off current = set-point percentage * rated current * load threshold,
alarms when difference between set-pint and measured current is bigger than load Rated current:The same as nameplate. Data can be
off current. Possible reason: changed according to actual load, for the purpose of 49
E004 F-049 protecting device
0-3000 - RW
1、Load off [A] 0.1A
2、Load current is small Notice: cannot exceed nominated value on the
3、Setting of(F-45)is small nameplate

Overheat of regulator, heat-sink temperature is bigger than 85, possible reason: Frequency 0-2 50
F-050 1 0 RW
1、Ambient temperature is higher than 45. 0:50HZ 1:60HZ 2:Automatic tracking
E005 2、Fan breaks.
3、Dust on the ventilation path.

www.noker-inverter.com