REF615 Report Format1
REF615 Report Format1
254/5, 3rd Main Road, Mahalaksmi Layout, Bangalore -560086, Mob : 9448040046, 9964441111
Certificate No Page No
Test date Next test due date
Client Details M/s.Jindal Steel Power,
Chhendipada Road,Nisha
Sub P.O. Jindal Nagar, Pin Code -759111,
District Angul, (Odisha), India
Project 2X525 MW, ACPP-II,
Location
Switchgear
Name
Feeder Name
3.0. Details :
CT Ratio
Test by REPL Witnessed by JPL Engineer Certified by JPL Incharge
No.254/5, 3rd Main Road, Mahalaksmi Layout, Bangalore -560086, Mob : 9448040046, 9964441111
PT Ratio
Phase Over Current Protection 51/50 :
(DPHLPDOC1:1) Ip> Ip> Set Characteristics set TMS
PHIPTOC1-1 I> I> Set Characteristics set Time
Earth Fault Protection 51N/50N : -
(DEFLPDEF1:1) Ie> Ie> Set Characteristics set TMS
EFHPTOC1-1 : Ie>> Ie>> Set Characteristics set Time
Sensitive Earth Fault 51NS:
DEFLPDEF2:1 Is> Is> Set Characteristics set TMS
Under Voltage 27
Stage -1 Voltage set Time set
4.0.Measurements Check :
a) Current Measurements : CT Ratio : , NCT Ratio :
Phase Injected Current Expected Value Measured Current In Relay (A.AC)
In (A.AC) In (A.AC) IA IB IC IN
R-N
Y-N
B-N
RYB
NCT
Note : Current Tolerance : ± 1.5 %,
b) Voltage Measurements : PT Ratio :
Phase Injected Voltage Expected Value Measured Voltage In Relay (Kv.AC)
In (V.AC) In (Kv.AC) RY YB BR RYB-N
R-Y
Y-B
B-R
R-N
Y-N
B-N
Voltage Tolerance : ± 1.5 %,
5.0. Phase Over Current Protection 51/50 : -
(DPHLPDOC1:1)
Setting :
Ip> Set IEC Character Set TMS/Time Delay Set
Test Results :
Phase Pickup Operating Time In (Secs) at Multiplies of Set current
In (A.AC) 2Times 5Times 10Times
Expected Actual Expected Actual Expected Actual Expected Actual
R
Y
B
RYB
Pass Criteria- ±1.% of the set value or ± 20ms
PHIPTOC1-1
Setting :
I> Set IEC Character Set TMS/Time Delay Set
Test Results :
Phase Pick up Expected trip time Actual trip time
In (A.AC In (Secs) In (Secs)
R
Y
B
RYB
Pass Criteria- ±1.% of the set value or ± 20ms
Setting :
Ie> Set IEC Character Set TMS/Time Delay Set
Test Results :
Phase Pickup Operating Time In (Secs) at Multiplies of Set current
In (A.AC) 2Times 5Times 10Times
Expected Actual Expected Actual Expected Actual Expected Actual
N
Pass Criteria- ±1.% of the set value or ± 20ms
EFHPTOC1-1 :
Setting :
Ie>> Set IEC Character Set TMS/Time Delay Set
Test Results :
Phase Pick up Expected trip time Actual trip time
In (A.AC In (Secs) In (Secs)
N
Pass Criteria- ±1.% of the set value or ± 20ms
Setting :
Is> Set IEC Character Set TMS/Time Delay Set
Test Results :
Phase Pickup Operating Time In (Secs) at Multiplies of Set current
In (A.AC) 2Times 5Times 10Times
Expected Actual Expected Actual Expected Actual Expected Actual
N
Pass Criteria- ±1.% of the set value or ± 20ms
Test Results :
Test by REPL Witnessed by JPL Engineer Certified by JPL Incharge
No.254/5, 3rd Main Road, Mahalaksmi Layout, Bangalore -560086, Mob : 9448040046, 9964441111
X100-PO3
X100-PO4
X110-SO1
X110-SO2
X110-SO3
X110-SO4
12.0, Remarks :
Status Remarks ( OK/Not OK)
Above Test Results Found
Tested Good
Relay Fit for Commissioning/Operational