The EA448B Generator Automatic Voltage Regulator (AVR) is designed for use with Permanent Magnet Generators and offers features such as voltage regulation, under frequency protection, and over excitation current limitation. It supports various voltage inputs and has adjustable settings for optimal performance. The manual includes specifications, connection diagrams, and safety notices for installation and operation.

Uploaded by

martina9933660
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
19 views4 pages

ea448b-manual-en

The EA448B Generator Automatic Voltage Regulator (AVR) is designed for use with Permanent Magnet Generators and offers features such as voltage regulation, under frequency protection, and over excitation current limitation. It supports various voltage inputs and has adjustable settings for optimal performance. The manual includes specifications, connection diagrams, and safety notices for installation and operation.

Uploaded by

martina9933660
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

EA448B

Generator Automatic Voltage Regulator


Operation Manual

Permanent Magnet Generator or A.R.E.P or Auxiliary Winding Type


Compatible with Leroy Somer R448*

Use with KUTAI EPMG-1270 / EPMG-2470 add-on module can boost


generator motor starting capacity

* Use for reference purpose only and not a genuine Leroy Somer product.

KUTAI ELECTRONICS INDUSTRY CO., LTD.


TEL : +886-7-8121771 FAX : +886-7-8121775 Website : www.kutai.com.tw
Headquarters : No.3, Ln. 201, Qianfu St., Qianzhen Dist., Kaohsiung City 806037, Taiwan
SECTION 1: SPECIFICATION
Sensing Input (E1、E2) Average Reading Voltage Regulation
Voltage 95  520 Vac 1 phase 2 wire Less than +/- 0.5% ( with 4% engine governing )
DIP Switch Settings
Adjustment 95  140 Vac @ 110 Vac Typical System Response
170  260 Vac @ 220 Vac 0.3  1 seconds @ +/- 20% Voltage Vibration
340  520 Vac @ 380 Vac
Frequency 50/60 Hz Jumper selected Static Power Dissipation
Max. 4 watts
Power Input (X1、X2)
Voltage 40  150 Vac 1 phase 2 wire Under Frequency Protection
Frequency 40  500 Hz 50 Hz system knee point at 45Hz
60 Hz systems knee point at 55Hz
Auxiliary Input (Z1、Z2)
Voltage 40  150 Vac 1 phase 2 wire Over Excitation Current limitation
Frequency 40  500 Hz 3.5A to 10A (EXC.MAX. Adjustable)

Excitation Output (E+、E-) Voltage Thermal Drift


120V 1 phase Continuous 110 Vdc 7A Less than 3% from -40 to +70 °C
Max. 160 Vdc 10A 10Sec
Resistance Min. 15Ω, Max. 100Ω @120V Environment
Fuse Spec. Slow blow 5 x 20mm 10A Operation Temperature -40 to +70 ˚C
Storage Temperature -40 to +85 ˚C
External Voltage Adjustment (1KΩ) Relative Humidity Max. 95%
Max. +/- 10% @ 1 KΩ 1 watt potentiometer Vibration 5.5 Gs @ 60 Hz

Quadrature Droop Input (S1、S2) Dimensions


CT N:1A 203.0 (L) x 153.0 (W) x 60.5 (H) mm
Sensitivity +/- 7%@ PF +/- 0.7 (STAT. Adjustable) 7.99 (L) x 6.03 (W) x 2.38 (H) inch

Build Up Voltage Weight


5 Vac 25Hz residual volts at power input terminal 850 g +/- 2%
1.874 lb +/- 2%
Soft Start Ramp Time
3 seconds +/- 10%

SECTION 2: DEMISION NOTICE

1. AVR could be installed in any suitable


locations of the generator sets, the
appearance and fixing holes are as (Figure
60.0 1)
[2.36"]
M5 L30
18.0 2. To ensure safety and avoid the permanent
[0.71"] damage to the AVR caused by the high
pressure, make sure remove the connection
wiring on the AVR before using
megohmmeter and the voltage meter.
75.0
[2.95"] 3. Make sure tie up the connection wiring of the
AVR when installing in a high-vibration
200.0
140.0
115.0 [5.51"]
100.0 [7.87"] environment. The cooling fin could release
[3.94"]
[4.53"] the high temperature under the normal
operation, please do not touch.
Unit : mm
[inch]

Figure 1. Outline Drawing


___________________________________________________________________________________________
2 EA448B
SECTION 3: DIP SWITCH SETTING

50Hz、60Hz:Frequency Selection

X1、X2:Power Input
Connect working voltage, Max. 150Vac
50Hz 60Hz
Z1、Z2:Auxiliary Power Input
Connect Auxiliary voltage, Max. 150Vac
EXC.MAX. X2
J1
LED Z1
123
J2 X1
E+、E-:Excitation Output
V/Hz
Z2 Connect to generator excitation field
ST2 E+
STAB.
E-
E1、E2:Sensing Input
Connect sensing input voltage Max. 600Vac
E1
E2
ST6
VOLT
Sensing Input Voltage Selection
ST1 ST7 1 OFF 2 OFF :110Vac (95~140V)
EA448B STAT.
1 ON 2 OFF :220Vac (170~260V)
1 ON 2 ON :380Vac (340~520V)

3Ph.:Three Phase Sensing Input


Connect to Three Phase Sensing
J1 J1 Disconnected:Without LAM protection
Module

1KΩ:External Voltage Adjustment


J1 J1 Connected:With LAM protection
Connect to external 1KΩ potentiometer
Terminals must be shorted when not in used
LAM:When Generator is loading the Engine speed will be
reduced. When engine speed is lower than pre-set frequency
S1、S2:Quadrature Droop Input
threshold (V/Hz knee point), AVR will reduce voltage in 13%
Connect to generator CT
or 25% (set by J2). This will make the active power of loading
reduce 25% to 45%, until engine speed reach pre-set value
once again then voltage will resume to normal value.
STAT.:Quadrature Droop Adjustment 123
Adjust the ratio of the idle power to the J2 When J2 1–2 is shorted:Drop ratio 13% in LAM voltage
voltage drop, when used in parallel.
Adjustment range is 0% to 7% 123
J2 When J2 2–3 is shorted:Drop ratio 25% in LAM voltage
VOLT:Voltage Adjustment
Adjust Generator output voltage ST1:Single Phase / Three Phase Sensing Selection
Adjustment range can be set by DIP SW Shorted:Single phase sensing
Open:Three phase sensing (must use with Three Phase Sensing Module)
STAB.:Stability Adjustment
S F
Under no-load operation, slowly adjust the
ST2:Response Time Selection
STAB VR counterclockwise until the
Shorted:Slow
voltage is unstable, and then adjust it
Open:Fast
clockwise for about 1/5 circle
Select response time according to Stability adjustment

V/Hz:Under Frequency Adjustment


50 40
Adjustment for Under frequency and LAM ST6:Instantaneous Compensation for Voltage
(60) (50)
knee point Shorted:For Generator less than 600 KVA
Open:For Generator greater than 600 KVA
LED:LED will illuminate when AVR in normal operation

ST7: Keep shorted


EXC.MAX.:Over Excitation Current Limiting
Excitation output will be turn off when excitation
current is over the setting value
Min. 3.5A, Max. 10A

___________________________________________________________________________________________
EA448B 3
SECTION 4ː CONNECTION DIAGRAMS

FIELD STATOR : 12 wires (marked T1 to T12) FIELD STATOR : 12 wires (marked T1 to T12) AUX WINDINGS

T1 T7 T2 T8 T3 T9 T1 T7 T2 T8 T3 T9

T4 T10 T5 T11 T6 T12 T4 T10 T5 T11 T6 T12

X2 Z1 X1 Z2 E+ E- E1 E2

S2
S1 X2 Z1 X1 Z2 E+ E- E1 E2
T1
60Hz
50Hz
EA448B 1K

3Ph.
S2
S1
T1
External
potentiometer
1k /1W
60Hz
50Hz
EA448B 1K

3Ph.

External
potentiometer
1k /1W

Figure 2. Self-Excited (SHUNT) Figure 3. Auxiliary and Harmonic Power Winding

FIELD STATOR : 12 wires (marked T1 to T12)

T1 T7 T2 T8 T3 T9

PMG

T4 T10 T5 T11 T6 T12

X2 Z1 X1 Z2 E+ E- E1 E2

S2
S1
T1
60Hz
50Hz
EA448B 1K

3Ph.

External
potentiometer
1k /1W

Figure 4. PMG Winding

ATTENTION!!
1. Improper setting of under-frequency protection could cause the output voltage of the unit to drop or become
unstable under with changes in load. Avoid making any changes to the U/F setting unless necessary.
2. Terminal Specification:6.35mm (1/4 inch) Flagged Terminals
3. Use only replacement fuses specified in this user manual.
4. Appearance and specifications of products are subject to change for improvement without prior notice.