extinguishing_control_panel

The iQ800 series extinguishing control panel by Fireguard is a UL listed, microprocessor-based system designed for multiple area extinguishing protection, compliant with UL-864 and NFPA-72 standards. It features a 16x2 dot matrix LCD display, various initiating and releasing circuits, and advanced programmability for ease of use and reliability. The panel operates on a wide voltage range with battery backup and includes comprehensive monitoring and logging capabilities.

Uploaded by

tarek3mamdouh-1
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
46 views

extinguishing_control_panel

The iQ800 series extinguishing control panel by Fireguard is a UL listed, microprocessor-based system designed for multiple area extinguishing protection, compliant with UL-864 and NFPA-72 standards. It features a 16x2 dot matrix LCD display, various initiating and releasing circuits, and advanced programmability for ease of use and reliability. The panel operates on a wide voltage range with battery backup and includes comprehensive monitoring and logging capabilities.

Uploaded by

tarek3mamdouh-1
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

!

iQ800 series Extinguishing control panel

Fireguard iQ series microprocessor based UL listed


extinguishing control panels provide a flexible approach to multiple
area extinguishing protection.
Fireguard iQ series panels
fully complies with UL-864
and NFPA-72.Approval by
Underwriters Lab to the most
rigorous of international
standards, provides peace of
mind for both designers and
end-users With gas panels
often protecting high cost,
high risk areas.

Fireguard iQ series panels are


packed with advanced features as standard to ensure ease of use
and high reliability. It comes with 16x2 dot matrix LCD display
with walk test facility & 200 event log

Model iQ800 series-W (White cabinet)


Model iQ800 series-R (Red cabinet)

Features:

• Fully complies with UL -864 9th Edition and NFPA-72.

• Rugged CRCA sheet with powder coated finish.

• 4 Class B initiating device circuit (IDC).

◦ All zones accept smoke detectors and any normally open contact device.

◦ Any Zone can be configured as Alarm or supervisory Zone.

• 2 Class B Releasing Agent Circuits (RAC).

• 2 Class B Notification Appliance Circuits (NAC).

!
!
!

• Operates on 120 - 220v 60 / 50 Hz, AC Mains power supply.

• Standby (battery) backup 24v DC power supply with built in charger

• 16x2 Dot Matrix LCD Display.

• Error free Fire / Fault status in unambiguous colored LED indication.

• System ON indication.

• Main, Standby status audible and visual indication.

• Battery Low visual warning with audible tone.

• 3 Form C relays one for fire and two programmable relays for Fire / fault /
supervisory / Cross Zone / Gas Released.

• Programmable two Input Circuits for Manual release and abort.

• Two modes of operations Auto / Manual.

• Programmable 24v D.C. Outputs.

• Programmable NAC2 as RAC1.

• RS 485 Communication facility (Optional).

• 200 Events Log facility with RTC.

• Walk Test facility.

• Zone Isolation facility.

• All field wiring circuits are Power limited except 120 / 220v AC and Battery.

• All field wiring circuits are supervised.

• AC Low voltage cutoff.

• Programmable RAC’s with count down timer.

• Programmable NAC’s.

• NAC it is saying releasing agent circuit

• Programmable IDC’s.

• Programmable Supervisory Mode.

• Programmable AC loss delay.

• Alarm verification facility.

• Programmable trouble reminder facility.

!
!
!

Technical Specification :

Primary Power – CN1 (RE-SMPS-4A-R1)


120 - 220VAC ± 10%, 50 Hz,
Standby Power
24v D.C (2 Nos of 12v, 12Ah Sealed Lead acid battery).
Operating Condition
Operating Temperature – 0 - 49° C/32-120° F.
Relative Humidity – 93±2% RH (non-condensing) at 25 ±2° C/77±3° F.
Charging Circuit
Charging Voltage – 28.4V, ±0.2V with Current – 800mA (Max.).
Initiating Device Circuits
All zones are Class B Style B/C operation (Programmable).
Normal Operating Voltage : 120 - 220VAC ± 10%, 50 Hz,
Alarm Current : 15- 30mA.
Short Circuit Current : 45mA Maximum
Loop resistance : 100 ohms Maximum
End-Of-Line Resistor : 3K9, 1/2watt
Standby Current : 7mA (2mA for Detectors)
Notification Appliance Circuits
Class B Style - Y wiring
Operating Nominal Voltage : 24VDC Special Application
Current for all NACs : 1.2Amps (0.6A per circuit)
Current Li mit: CN5 and CN6 via Thermal Fuse
Line Drop : 1.8V
End-Of-Line Resistor : 3K9, 1/2watt
Releasing Appliance Circuits – CN 13 & 14
Class – B Style - Y wiring
Operating Nominal Voltage: 24VDC – Special Application
Current for all RACs: 0.6A per circuit
Line Drop: 1.8V
End-Of-Line Resistor: 3K9, 1/2watt
D.C. Output Power
Supervised 24VDC regulated. 300mA Max. (for 4 wire smoke detector)
Common Three Form C Relays
Relay Contact Rating : 2Amps @ 30 VDC. 2Amps @ 3OVAC.
Power Factor : 0.6
Dimension of the panel
440 x 350 x120 mm (l x h x d)