4--Data Center Facility--Data Center Cooling Solution

The Huawei Smart Cooling Solution addresses the high energy consumption of data centers, particularly from cooling, which constitutes a significant portion of operational costs. It offers a range of cooling systems designed for various scales of data centers, improving efficiency, simplifying maintenance, and reducing installation time. The solution emphasizes energy savings, reliability, and adaptability to different environmental conditions, aiming to enhance overall data center performance.

Uploaded by

Alex
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
66 views56 pages

4--Data Center Facility--Data Center Cooling Solution

The Huawei Smart Cooling Solution addresses the high energy consumption of data centers, particularly from cooling, which constitutes a significant portion of operational costs. It offers a range of cooling systems designed for various scales of data centers, improving efficiency, simplifying maintenance, and reducing installation time. The solution emphasizes energy savings, reliability, and adaptability to different environmental conditions, aiming to enhance overall data center performance.

Uploaded by

Alex
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 56

Huawei Smart Cooling Solution for Data Center

DC Consumes Enormous Energy, Mostly on Cooling

Global DC power consumption DC OPEX composition


Maintenance,
[值]
Rent, [值]
Manpower,
[值]

Capex;
22% Power, [值]
3%
15%

PUE
PUE 50%
1.6
1.6
1 DC = 4x Three Gorges Dam 32%

Annual power consumption


IT Cooling
400G kWh
Source: 2018 global power report,Forbes

2
Higher Power Density, Hotspot Issue Causes Huge Loss

DC power density trend Cases of hotspot issue



Unit: kW/R A commercial bank,
cooling system down due
2017.09 to power overload,
business interrupted.

A airline cancelled more


than 400 flights due to data
10 center cooling system 2018.06
failure. More than 75000
passenger affected.
A cloud service provider:
5 cooling system down due

1
2018.09 to lightning strike, multiple
services impacted.

Original Traditional Now Future

3
Difficult O&M is the Main Reason for Malfunction

Others 5%
Slow
Environment1 service
2% response
Hard to Hard to
monitor locate fault

Malfunction cause
O&M
Hard to
Complex
analyze
equipment
data

High
Complex
O&M 83% technical
operations
skills

Source: 365 Data Centers

4
Huawei Cooling Solution, Adapts to Diverse Scenarios
For Medium-small Scale DC For Large Scale DC

Smart cooling indoor units


& Cabinets
Chillers
Indoor units & Cabinets Out door units

NetCol5000-A NetCol8000-A NetCol5000-C NetCol8000-C FusionCol8000-C FusionCol8000-E

13~46kW 13~120kW 30~65kW 62~190kW 210kW 220~400kW


In-row air-cooled In-room air-cooled In-row In-room Fan wall Indirect evaporative
chilled water chilled water

5
FusionCol8000-E
Indirect Evaporative Cooling Solution

6
FusionCol8000-E Typical Application
1. Side installation of building: Equipment room length ≥8m, height 2. Roof installation: air supply duct is not provided. Floor load-
≥4.8m, the distance between AHU and wall ≥ 500mm bearing per unit ≥ 500kg/m2

3. Side installation of multi-storey buildings: equipped with air 4. FDC: Supports seamless stacking, and is connected to the
supply duct, Only a single-layer maintenance ladder (width ≥ 800 equipment room through duct
mm) is required at layer 2 or above.

7 Huawei Confidential
Solution: More Simple than Traditional Chiller Water System
Cooling System AHU

7 Major Systems 3 Major System

Chiller Tower CRAC AHU Water treatment Duct

Pump Tank Pipe

Valve Air return duct

Tower
Tower VS
IT Room
Pumps

CRAC AHU Air supply duct


Pipe
Chillers

8 Huawei Confidential
FusionCol Specifications and Parameters

Fan Condenser Heat exchange core


Model NetCol8000-E

Total Cooling Capacity/Sensible Cooling Capacity 220 /220 kW

Air Flow 55000 m3/h

Power Specifications 380V~415V AC, 3Ph, 50/60Hz

Ratio of Supplementary Refrigerant 10%-50%

Supply Air Temperature(℃)/Humidity (%) 25℃/50%

Return Air Temperature(℃)/ Humidity(%) 38℃/25%

Indoor/Outdoor Air Filter(EN779) G4/G2

Evaporator Compressor pump Sprinkler Drain Dimensions(


L x W x H) Installation 6058mm x 2438mm x 3600mm

Net Weight/Operating(without
Weight 5,750kg/6,300kg
duct)

9 Huawei Confidential
Different Modes Switched on Demand
According to fresh air temperature and IT load, runs in different modes
Ambient T℃ Mode Fans Pumps DX

Dry bulb≤16℃ Dry Mode ON OFF OFF

Dry bulb>16℃ and wet bulb≤19℃ Spray Mode ON ON OFF

wet bulb>19℃ Hybrid Mode ON ON ON

Dry Mode(Dry bulb≤16℃) Spray Mode(Dry bulb>16℃ and Hybrid Mode(wet bulb>19℃)
wet bulb≤19℃)

10 Huawei Confidential
FusionCol: Extreme Energy Saving, Faster Delivery

• PUE 1.2@ London, Saved 11% Power Consumption


Efficient • “iCooling” Reduce pPUE 8%
• High Space Usage , Improved SpUE 34%

Simple • Fast Installation, TTM Shortened 50%


可靠 • Maintenance is faster and easier

FusionCol

Reliable • One-click fault information collection


简单 • Partial failure not affect the whole system

11 Huawei Confidential
Efficient Simple Reliable

PUE 1.2@ London, Saved 11% Power Consumption


 Different modes at London, pPUE is 0.06  Anuual PUE reduce 0.15, annual electricity fee
of the data center reduce 1.3 M$ (including IT )
High Low Ave Web
London Ave T(℃)Ave Humi% PUE Power Charge (M$)
T(℃) T(℃) T(℃)
32.3 -5.9 11.6 75.2 9
Dry Spray Hybrid
pPue
1.35
1,34 11.9
PUE Reduce Save
Mode Mode Mode
0.15 1.3M$
7217h 1478h 65h 0.06 1.2
1,255
1.2 (11%)
 Temperature distribution
10.6
Hours
3000
2500
2000
1500
1000 Chiller+FC NetEco8000-E Chiller+FC FusionCol8000-E
Chiller+FC FusionCol8000-E
500
0
(Model: London xx Data Center, Tier3, Racks is 1500, load is 8kW/R, the load rate is 50%,
and the electricity fee is 0.168 $/kWh. )

12 Huawei Confidential
Efficient Simple Reliable

High Space Usage , Improved SpUE 34%


Model: 1500 racks, 8kW/R, total load 12MW@ London, chilled water system VS FusionCol
 Only equipment footprint, When a stack is installed outdoors, FusionCol reduce 38% outdoor footprint.
 No PAC is required indoors, all space is released to the cabinet. Spue increases by 34%

Chiller+InRoom FusionCol
 54 modules. Per module contains 30 cabinets,  43 modules, Per module contains 34 cabinets ,
108pcs CRAHS , (4+1) sets of 1100RT chillers (58+6) sets of AHU
Outdoor Area
Outdoor Area
1550㎡
2470㎡

Indoor space :6300㎡ Indoor space :4705㎡


VS

AHU stack

13 Huawei Confidential
Efficient Simple Reliable

Core Components Improve System Efficiency


Heat Exchanger Core Spray System EC Fan

 Air - air heat exchange core, material  The spray direction is consistent with the  EC fans, 30%-100% stepless adjustment,
aluminum foil / epoxy resin coating, inlet air flow direction, the water spray Reduce power consumption at least 20%
Efficiency is 10% higher than polymer surface is wider, and heat exchange
 Indirect Evaporation exchange heat, efficiency is 10% higher than others.
Indoor return air and outdoor air cross  The diameter of the nozzle only 5~6mm , Fan Power Curve
heat transfer, no directly contact. less water consumption

Spray System
Heat Exchange Core

The spray
direction is
consistent with
the inlet direction

14 Huawei Confidential
Efficient Simple Reliable

Fast Installation, TTM Shortened 50%


Fast Delivery Simple Onsite Installation

 All components are preinstalled and pre-tested in the  Support different installation site: Container body
factory and no need to be assembled onsite structure, Indoor/outdoor installation
 installation <1 month,Business delivery <4 months,  Support different installation modes: side-mounted,
shortening business online time more than 50% top, or stacked installation

240 days

Deepen design: Review: Commissioning/accept


chilled water 20 days 15days Construction: 135days ance: 60days

Assemble Debugging:
Produce: 60days : 30 days 30 days
FusionCol Save 50%

120days Side-mounted (stacking) Top-mounted (on roof)

15 Huawei Confidential
Efficient Simple Reliable

Simple O&M, the Maintenance is Faster and Easier


Fast Maintenance Convenient Maintenance Self-Diagnosis

 Power and signal cable separation,  Compressor RotaLock connection  Unique self-diagnosis algorithm,
the main control and auxiliary maintenance does not require eliminating the root cause of
modules support quick operation welding, saving time 80% irrelevant faults
and maintenance within 1 minute  Independent control cable slot for  Fault rectified within 15 minutes.
the fans, online maintenance within Reduced 7 hours than tradition
5 minutes system

Control module

Auxiliary module

Power module 1

Power module 2

16 Huawei Confidential
Efficient Simple Reliable

One-Click Fault Information Collection

Excellent Platform Intelligent Networking Expert Big Data Storage

 7-inch full-touch color screen,  Supports up to 32 units network  Precise positioning fault, 500 records;
simplifying operations  Support backup, round robin, Access log traceability, 200 records
 One-click fault information collection cascading, anti-competitive  Can display 30 days temperature and
operation and other functions humidity curve

17 Huawei Confidential
Efficient Simple Reliable

Component Failure Will Not Affect the Whole System


Component Modular Design Redundancy Design

Component redundancy Backup power redundancy


 Multi-fan design, the failure of a single fan does not  The power of fan and DX system are
affect the output of the cooling capacity of the unit. independently, and the main circuit is automatically
 Pumps are configured in redundancy mode, and the switched to the standby to ensure reliable circuit
spray system is safe and reliable
A
Input-1 380Vac
Input-2
UPS
Spray Power 24V
FAN Controller
Pump Module

Fans 4+1 pcs


380Vac
Input-3
B

Driver Compressor

Backup Power Redundancy

Fans 4+1 pcs Pumps 1+1pcs

18 Huawei Confidential
Efficient Simple Reliable

Water Treatment Requirements Ensure Reliability of Sprinkler


Water Quality Requirements Water Treatment Design
Item Requirements
 Design : Municipal water source →treatment device →
at least 89 μm
Filtering level water tank → water pressure pump group → AHU
PH value 6.5~8  Water supply pressure: 300kPa~700kPa
Conductivity < 400μS /cm  Minimum water refill at the end of the unit: Layered
TDS < 260 mg / l @ 180°C loop water supply

Hardness < 100 mg/l Water system flowchart


Municipal water supply
Unit 1#
Total alkalinity < 50mg /l CaCO3 Suply A
Suply B
Chloride < 20 mg/l Unit N#

SiO2 < 5 mg/l


RO device Softening Softening
Organic matter < 3 mg/l Pool 1 Pool 2

19 Huawei Confidential
Efficient Simple Reliable

Maintenance Requirements for Core Components


Maintenance Requirements Water Requirements

 Spray time ≤3000h, HX core cleaning once per 2 years  Cleaning water pressure: 3-5 bar

 Spray time≤5000h, HX core cleaning once per 1 year  Cleaning water: the same as that of spray water. Zinc

 Spray time is >5000h, HX core cleaning once per 6 months sulfate and polyacrylic acid corrosion inhibitors can be
added to water.

Process of cleaning the heat exchanger core

Step 1: Enter the unit from the Step 2: From the maintenance door of the Step 3: Wash the core with a high-
maintenance door (1280*670). spacer to the upper layer of the unit pressure water gun

20 Huawei Confidential
Quiz

Q1: What type of climate and environment is suitable to use


indirect evaporative cooling solution?
Key: Indirect evaporative cooling is suitable for cool/cold
and dry environment with abundant water resource.
Q2: What type of data center is suitable to use indirect
evaporative cooling solution?
Key: Large/hyper scale data center.

21 Huawei Confidential
NetCol5000-A/8000-A
Air-cooled Smart Cooling Solution

22
Variable Frequency In-room DX Solution
Top features:

1、Efficient: Variable
frequency, wet-film
humidifier, iCooling

2、Reliable: Low load


dehumidification,
refrigerant detection

3、Simple: Welding-free
connection, fault self-
NetCol8000-A045/060D NetCol8000-A045/060U NetCol8000-A090/120D diagnosis

23 Huawei Confidential
Fully Variable Frequency Architecture: High Efficiency

Architecture AEER Comparison 省电费23万/年、ROI<2年


Effect
9 160%
Energy Saving
140%
8 30%+
120% annual saving
7 31 500 USD
DC Compressor 100%
6
80%
5 60%

4 40%
Indoor fan EEV
20%
3
25% 50% 75% 100% 0%
Fixed-frequency AEER AEER Energy Cost
Outdoor fan Variable-frequency AEER Fixed-frequency Variable-frequency

Scenarios:Beijing,50% load rate, 0.12 USD per kWh

24 Huawei Confidential
Wet-film Humidifier: Save 95%+ Energy

Structure Energy consumption Effect

140%

120%
• Save 95% energy,TCO is
better than Electrode type
100%
Dry air Wet air
80% • Replacement frequency:
60% Electrode: 1~2 times/year
Wet-film: 1 time/2 years
40%

20% • Lower requirements for


0% water quality
Electrode Infared Wet-film

25
Unique No condensation Design at Low Load

No frequently On/Off Unique No condensation Design at Low Load

• IT load at10%~20% at the prime business


DC Load
• IT load will frequently change from 10%~100%
Condensation

Cooling Capacity
at low load
100% 100% 100%

Fixed- Others HUAWEI • Recovery heating


frequency Variable Variable
frequency frequency • Wider load range
No condensation
• No frequently On/Off
50% at low load

30%

10%

Industry Level Huawei


Time
Operation range Non-operation range (Frequently On/Off)

26
Automatic Refrigerant Detection to Improve Running Reliability

AI modeling intelligently calculates the refrigerant


content, and an early warning is generated to avoid the
unit breakdown due to insufficient refrigerant. The third party test report

27
High Quality Components Make a Reliable System

DC inverter compressor
Screen
• Start current less than rated, no grid
• Anti - electromagnetic interference
shock
• Multi-level management permission
• Accurate driven and self-adaption

Electronic expansion valve


Indoor unit fan
• Accurate PID control
• Using direct drive, less components
• Unique power module for sudden
• Less weight, easy for maintain on-line
close while unit down

Outdoor unit fan Huawei R&D drive


• Auto lower the current on locked-rotor • Better optimization, higher efficiency
• Reduce consumption on partial load to • Indoor installation avoids fault due to
extend the motor life severe weather

28
Indoor Fans And PSU Redundancy Design, Maintain On-line

Indoor unit fan N+1 design Swapping design for light-


Independent air switch and slot current module

Air switch Control module

Auxiliary power module

PSU 1

PSU 2
Power cable slot

29
Key Components No Welding Connection, Easy for Maintain

Compressor and dry filter maintenance diagram

Compressor and dry filter use Rotalock connection, save 80%+ troubleshooting time

30
Fault Self-diagnosis: Fast Fault Detection and O&M Guidance

Fault Self-diagnosis:
• Eliminates irrelevant
malfunction causes

• Locates faults fast and quickly


guides O&M personnel

• Shortens troubleshooting time


to 15 minutes, saving 7+
hours

31
7-inch Screen: Displays Key Parameters for Easy O&M

Brilliant Interactive Platform Intelligent Group Control Big Data Storage

• Support 32 units as a group


• 7-inch color touch screen • Review alarms in 1500 records
• Support backup, rotation, stack
• Key parameters displayed in • 30-day temperature/RH curve
and anti-competition functions
real time • Maximum of 1000 access logs
• Optimizing the distribution of
• Support Modbus and SNMP are traceable
heat load

32
NetCol5000-A Indoor Unit Technical Specifications

Model Unit NetCol5000-A035H(300mm) NetCol5000-A050H (600mm)

Air supply direction - Horizontal Horizontal

Total cooling capacity1 kW 35 46

Sensible cooling capacity kW 35 46

Air volume m3/h 6000 9000

Power supply voltage V/Ph/Hz 380-415/3/50(60) 380-415/3/50(60)

Heating capacity kW 4 6

Humidification capacity kg/h 1.5 3

Dimension (W×D×H) mm 300×1200×2000 600×1200×2000

Note:
1. Standard condition: return air temperature 37ºC, RH 24%, outdoor temperature 35ºC.

33
NetCol8000-A Indoor Unit Technical Specifications

Unit Model Unit NetCol8000-A045D/U NetCol8000-A060D/U NetCol8000-A090D NetCol8000-A120D

Air supply direction - D: Downflow U: Upflow

Total cooling capacity1 kW 45 60 90 120

Sensible cooling capacity kW 45 60 90 120

Air Volume m3/h 11250 14500 22500 29000

Power supply voltage V/Ph/Hz 380~415/3/50(60)

Heating capacity kW 6 6 12 12

Humidifier capacity kg/h 6 6 10 10

Full Load Current2 A 36(40) 41(45) 72(80) 82(90)

Dimension: W×D×H mm 900*900*2000 1100*1000*2000 1800*1000*2000 2200*1000*2000

Net weight kg 380 430 700 800

Note:
1. The data in brackets are applicable to the indoor unit with electric heater & humidifier.
2. Standard condition: return air temp. 35ºC, RH 26%, outdoor temp. 35ºC.
34
NetCol8000-A013U
Air-cooled Smart Cooling Solution
Typically for Power Room/Small Computer Room

35
Typical Application Scenarios

1. NetCol8000-A013U

Power Distribution Smart Small Data


Room Scenario Centers Scenario

36
Efficient Reliable Simple
Variable-frequency Design, Saving 30% Energy at Partial
Load
Indoor Unit Outdoor Unit EER Comparison at 50% Load Rate
6

0
-5 0 5 10 15 20 25 30 35

Huawei Other
EC fan Inverter compressor

The actual load rate in data center is less than 50%, NetCol8000-A013U uses variable-frequency
frame, saving 30% energy versus fixed-frequency solution, leading 4,000 kWh electric saving per
37 year.
NetCol8000-A013U Indoor Unit Technical Specifications

Model Unit NetCol8000-A013U

Air Supply Direction - Upflow


Total Cooling Capacity1 kW 13.0

Sensible Cooling Capacity kW 11.7


Air Volume m3/h 3600
Power Supply Voltage V/Ph/Hz 380-415/3/50, 380~415/3/60

Refrigerant - R410A
Heating Capacity kW 4
Humidification Capacity kg/h 3
Dimension: W×D×H mm 800×664×1886
Net Weight kg 141/153 (With heater and humidifier)

Note:
1. Conditions: 24ºC air return temperature, 50% relative humidity, 35ºC ambient temperature.
38
Quiz

Q1: What type of compressor is used in Huawei air-cooled


products, and what is the advantages?
Key: DC inverter variable frequency compressor. Significant
energy saving at partial load.
Q2: What type of humidifier is used in Huawei air-cooled
products, and what is the advantages?
Key: Wet-film humidifier. ‘0’ energy consumption.

39 Huawei Confidential
NetCol5000-C/8000-C
Chilled Water Type Smart Cooling Product

40
High Efficiency Components
Power
EC fan
module

• Save 30% • Efficiency up to


energy, reduce 93%, reducing
running cost power
• Online consumption
maintenance

Coil
Valve

• Precision • Apply Field


temperature synergy theory to
control by fast optimize air flow
response to heat rate and capacity
load

41
Dual Power Supply and 6kV Surge Protection

 Automatic power switch


Dual power supply
 Real-time monitoring on voltage and phase

Input Cooling unit

UPS
Surge protection
Dual power switch Power inspection Power components
module

Grid

 Highest 6kV surge protection in industry


6kV surge protection
 Reduce surge lost to minimum

42
Fast Installation for Fan Saving 70%+ Installation Time

Rotation and sinking installation for fan:


The installation can be completed within 10 minutes without using auxiliary tools,
saving 70% time compared with traditional hoisting sinking.

43
Fault Self-diagnosis: Fast Fault Detection and O&M Guidance

Malfunction Self-diagnosis:
• Eliminates irrelevant malfunction
causes

• Locates faults fast and quickly


guides O&M personnel

• Shortens troubleshooting time to


15 minutes, saving 7+ hours
compared to industry average.

44
NetCol5000-C Technical Specifications

Model Unit NetCol5000-C030H NetCol5000-C032H NetCol5000-C065H

Air Supply Direction - Horizontal

Total Cooling Capacity kW 30 32 65

Sensible Cooling Capacity kW 30 32 65

Air Volume m3/h 5000 5000 10,000

Power Supply Voltage V/Ph/Hz 220~240/1/50(60)

Water Pressure Drop kPa 80 80 80

Humidification (Optional) kg/h 1.5 1.5 3

Full Load Current A 9.5 9.5 15

Dimension: W×D×H mm 300×1,200×2,000 300×1,200×2,200 600×1,200×2,000

Net Weight kg 165 175 202

Note:
Standard condition: inlet/outlet water temperature 10/15℃; return air temperature/RH 37℃/24%
45
NetCol8000-C Technical Specifications
NetCol8000- NetCol8000- NetCol8000- NetCol8000- NetCol8000- NetCol8000-
Model Unit
C070D C130D C190D C070U C130U C190U
Total Cooling Capacity kW 63.2 126.4 189.6 61.9 123.8 185.7
Sensible Cooling
kW 51.4 102.8 154.2 50.3 100.6 150.9
Capacity
Air Flow Rate m3/h 13500 27000 40500 13200 26400 39600

Power Supply Voltage V/Ph/Hz 380-415/3/50, 380-415/3/60

Water Flow Rate l/s 3.02 6.03 9.05 2.95 5.91 8.86

Water Pressure Drop kPa 62.4 85.4 96.0 60.5 82.6 92.7

Full Load Current A 4.7 (15.2) 8.9 (29.9) 13.1 (34.1) 4.7 (15.2) 8.9 (29.9) 13.1 (34.1)

Dimensions: W x D x H mm 900*1000*2000 1800*1000*2000 2700*1000*2000 900*1000*2000 1800*1000*2000 2700*1000*2000

Net Weight kg 340 635 930 330 615 900

Cooling Capacity Parameters: Inlet/outlet water temperature 7℃/12℃, return air temperature 24℃, 50% RH, static pressure 20 Pa

46
NetCol8000-C210H
Chilled Water (Fan Wall) Smart Cooling Product

47
FusionCol8000-C Typical Application Scenarios

Side View

Top View
1. PAC
2. IT equipment

48 Huawei Confidential
Energy Saving with Higher Chilled Water Temperature
Energy saving: support higher water temp(15→20℃)

Free cooling
time
10%→28%

Chiller
efficiency
15%↑
VS

Horizontal air flow Traditional downflow in-room unit


210kW@36℃ return air, 20~28℃ ≤140kW@36℃ return air, 15~21℃
2350*1200*2600(WDH) 2550*1000*(2000+600) (WDH)

49 Huawei Confidential
No Doors for Easier Maintenance
No doors and large maintenance space

Front Back
Conventional in-
Fan wall
room up/down flow
horizontal flow unit
chiller water unit
50 Huawei Confidential
No Raised Floor, Faster Deployment

Hot aisle Hot aisle

CRAH

CRAH
Fan wall

Fan wall: no raised floor, Traditional in-room CW:


diffusing air flow Under floor air flow

51 Huawei Confidential
FusionCol8000-C Technical Specifications
Unit Model Unit FusionCol8000-C210H

Air Flow Direction - Horizontal

Total Cooling Capacity① kW 210.0

Sensible Cooling Capacity kW 210.0

Air Flow Rate m3/h 57,000

Quantity of Fan PCS 4

Air Filter Class - G4

Power Supply V/Ph/Hz 380-415/3/50, 380-415/3/60

Humidification Capacity (Optional) kg/h 10.0

Dimension: W × D × H mm 2500×2350×1100

Net Weight kg 1200

① Cooling capacity condition: return air dry bulb temperature 36 ºC/24% RH, inlet/outlet water
temperature 20 ºC/28 ºC.

52 Huawei Confidential
Quiz

Q1: What type of compressor is used in Huawei air-cooled


products, and what is the advantages?
Key: DC inverter variable frequency compressor. Significant
energy saving at partial load.
Q2: What type of humidifier is used in Huawei air-cooled
products, and what is the advantages?
Key: Wet-film humidifier. ‘0’ energy consumption.

53 Huawei Confidential
History of Huawei Smart Cooling Solution

2008 2012 2015 2019


Established with First generation in- In-row cooling Shipped over 30k units.
Huawei network room cooling ranked No.2 in China Cooling solution
energy product line NetCol8000-A ranked No.2 in China.
launched In-row cooling No.1 in
China

2020+
Continuous
innovation and
development

2011 2013 2016


First patent awarded. NetCol5000-A and In-row cooling
First generation in-row NetCol8000-C ranked No.1 in China
cooling NetCol5000-C launched
launched

54 Huawei Confidential
Market Share of Huawei Smart Cooling Solution

In-row Cooling No.1 in China Total Cooling Solution No. 2 in China

9,90%
20,60%
8,60%

37,10% 39,70%
8,60%

13,90%

11,30%

9,20%
8,20%
24,50% 8,40%

HUAWEI VET ENV STU CAN Others VET HUAWEI ENV STU CAN Others

Source: CCID 2020


55 Huawei Confidential
Bring digital to every person, home, and

Thank you.
organization for a fully connected,
intelligent world.

Copyright©2018 Huawei Technologies Co., Ltd.


All Rights Reserved.

The information in this document may contain predictive


statements including, without limitation, statements regarding
the future financial and operating results, future product
portfolio, new technology, etc. There are a number of factors that