4--Data Center Facility--Data Center Cooling Solution
4--Data Center Facility--Data Center Cooling Solution
Capex;
22% Power, [值]
3%
15%
PUE
PUE 50%
1.6
1.6
1 DC = 4x Three Gorges Dam 32%
2
Higher Power Density, Hotspot Issue Causes Huge Loss
1
2018.09 to lightning strike, multiple
services impacted.
3
Difficult O&M is the Main Reason for Malfunction
Others 5%
Slow
Environment1 service
2% response
Hard to Hard to
monitor locate fault
Malfunction cause
O&M
Hard to
Complex
analyze
equipment
data
High
Complex
O&M 83% technical
operations
skills
4
Huawei Cooling Solution, Adapts to Diverse Scenarios
For Medium-small Scale DC For Large Scale DC
5
FusionCol8000-E
Indirect Evaporative Cooling Solution
6
FusionCol8000-E Typical Application
1. Side installation of building: Equipment room length ≥8m, height 2. Roof installation: air supply duct is not provided. Floor load-
≥4.8m, the distance between AHU and wall ≥ 500mm bearing per unit ≥ 500kg/m2
3. Side installation of multi-storey buildings: equipped with air 4. FDC: Supports seamless stacking, and is connected to the
supply duct, Only a single-layer maintenance ladder (width ≥ 800 equipment room through duct
mm) is required at layer 2 or above.
7 Huawei Confidential
Solution: More Simple than Traditional Chiller Water System
Cooling System AHU
Tower
Tower VS
IT Room
Pumps
8 Huawei Confidential
FusionCol Specifications and Parameters
Net Weight/Operating(without
Weight 5,750kg/6,300kg
duct)
9 Huawei Confidential
Different Modes Switched on Demand
According to fresh air temperature and IT load, runs in different modes
Ambient T℃ Mode Fans Pumps DX
Dry Mode(Dry bulb≤16℃) Spray Mode(Dry bulb>16℃ and Hybrid Mode(wet bulb>19℃)
wet bulb≤19℃)
10 Huawei Confidential
FusionCol: Extreme Energy Saving, Faster Delivery
FusionCol
11 Huawei Confidential
Efficient Simple Reliable
12 Huawei Confidential
Efficient Simple Reliable
Chiller+InRoom FusionCol
54 modules. Per module contains 30 cabinets, 43 modules, Per module contains 34 cabinets ,
108pcs CRAHS , (4+1) sets of 1100RT chillers (58+6) sets of AHU
Outdoor Area
Outdoor Area
1550㎡
2470㎡
AHU stack
13 Huawei Confidential
Efficient Simple Reliable
Air - air heat exchange core, material The spray direction is consistent with the EC fans, 30%-100% stepless adjustment,
aluminum foil / epoxy resin coating, inlet air flow direction, the water spray Reduce power consumption at least 20%
Efficiency is 10% higher than polymer surface is wider, and heat exchange
Indirect Evaporation exchange heat, efficiency is 10% higher than others.
Indoor return air and outdoor air cross The diameter of the nozzle only 5~6mm , Fan Power Curve
heat transfer, no directly contact. less water consumption
Spray System
Heat Exchange Core
The spray
direction is
consistent with
the inlet direction
14 Huawei Confidential
Efficient Simple Reliable
All components are preinstalled and pre-tested in the Support different installation site: Container body
factory and no need to be assembled onsite structure, Indoor/outdoor installation
installation <1 month,Business delivery <4 months, Support different installation modes: side-mounted,
shortening business online time more than 50% top, or stacked installation
240 days
Assemble Debugging:
Produce: 60days : 30 days 30 days
FusionCol Save 50%
15 Huawei Confidential
Efficient Simple Reliable
Power and signal cable separation, Compressor RotaLock connection Unique self-diagnosis algorithm,
the main control and auxiliary maintenance does not require eliminating the root cause of
modules support quick operation welding, saving time 80% irrelevant faults
and maintenance within 1 minute Independent control cable slot for Fault rectified within 15 minutes.
the fans, online maintenance within Reduced 7 hours than tradition
5 minutes system
Control module
Auxiliary module
Power module 1
Power module 2
16 Huawei Confidential
Efficient Simple Reliable
7-inch full-touch color screen, Supports up to 32 units network Precise positioning fault, 500 records;
simplifying operations Support backup, round robin, Access log traceability, 200 records
One-click fault information collection cascading, anti-competitive Can display 30 days temperature and
operation and other functions humidity curve
17 Huawei Confidential
Efficient Simple Reliable
Driver Compressor
18 Huawei Confidential
Efficient Simple Reliable
19 Huawei Confidential
Efficient Simple Reliable
Spray time ≤3000h, HX core cleaning once per 2 years Cleaning water pressure: 3-5 bar
Spray time≤5000h, HX core cleaning once per 1 year Cleaning water: the same as that of spray water. Zinc
Spray time is >5000h, HX core cleaning once per 6 months sulfate and polyacrylic acid corrosion inhibitors can be
added to water.
Step 1: Enter the unit from the Step 2: From the maintenance door of the Step 3: Wash the core with a high-
maintenance door (1280*670). spacer to the upper layer of the unit pressure water gun
20 Huawei Confidential
Quiz
21 Huawei Confidential
NetCol5000-A/8000-A
Air-cooled Smart Cooling Solution
22
Variable Frequency In-room DX Solution
Top features:
1、Efficient: Variable
frequency, wet-film
humidifier, iCooling
3、Simple: Welding-free
connection, fault self-
NetCol8000-A045/060D NetCol8000-A045/060U NetCol8000-A090/120D diagnosis
23 Huawei Confidential
Fully Variable Frequency Architecture: High Efficiency
4 40%
Indoor fan EEV
20%
3
25% 50% 75% 100% 0%
Fixed-frequency AEER AEER Energy Cost
Outdoor fan Variable-frequency AEER Fixed-frequency Variable-frequency
24 Huawei Confidential
Wet-film Humidifier: Save 95%+ Energy
140%
120%
• Save 95% energy,TCO is
better than Electrode type
100%
Dry air Wet air
80% • Replacement frequency:
60% Electrode: 1~2 times/year
Wet-film: 1 time/2 years
40%
25
Unique No condensation Design at Low Load
Cooling Capacity
at low load
100% 100% 100%
30%
10%
26
Automatic Refrigerant Detection to Improve Running Reliability
27
High Quality Components Make a Reliable System
DC inverter compressor
Screen
• Start current less than rated, no grid
• Anti - electromagnetic interference
shock
• Multi-level management permission
• Accurate driven and self-adaption
28
Indoor Fans And PSU Redundancy Design, Maintain On-line
PSU 1
PSU 2
Power cable slot
29
Key Components No Welding Connection, Easy for Maintain
Compressor and dry filter use Rotalock connection, save 80%+ troubleshooting time
30
Fault Self-diagnosis: Fast Fault Detection and O&M Guidance
Fault Self-diagnosis:
• Eliminates irrelevant
malfunction causes
31
7-inch Screen: Displays Key Parameters for Easy O&M
32
NetCol5000-A Indoor Unit Technical Specifications
Heating capacity kW 4 6
Note:
1. Standard condition: return air temperature 37ºC, RH 24%, outdoor temperature 35ºC.
33
NetCol8000-A Indoor Unit Technical Specifications
Heating capacity kW 6 6 12 12
Note:
1. The data in brackets are applicable to the indoor unit with electric heater & humidifier.
2. Standard condition: return air temp. 35ºC, RH 26%, outdoor temp. 35ºC.
34
NetCol8000-A013U
Air-cooled Smart Cooling Solution
Typically for Power Room/Small Computer Room
35
Typical Application Scenarios
1. NetCol8000-A013U
36
Efficient Reliable Simple
Variable-frequency Design, Saving 30% Energy at Partial
Load
Indoor Unit Outdoor Unit EER Comparison at 50% Load Rate
6
0
-5 0 5 10 15 20 25 30 35
Huawei Other
EC fan Inverter compressor
The actual load rate in data center is less than 50%, NetCol8000-A013U uses variable-frequency
frame, saving 30% energy versus fixed-frequency solution, leading 4,000 kWh electric saving per
37 year.
NetCol8000-A013U Indoor Unit Technical Specifications
Refrigerant - R410A
Heating Capacity kW 4
Humidification Capacity kg/h 3
Dimension: W×D×H mm 800×664×1886
Net Weight kg 141/153 (With heater and humidifier)
Note:
1. Conditions: 24ºC air return temperature, 50% relative humidity, 35ºC ambient temperature.
38
Quiz
39 Huawei Confidential
NetCol5000-C/8000-C
Chilled Water Type Smart Cooling Product
40
High Efficiency Components
Power
EC fan
module
Coil
Valve
41
Dual Power Supply and 6kV Surge Protection
UPS
Surge protection
Dual power switch Power inspection Power components
module
Grid
42
Fast Installation for Fan Saving 70%+ Installation Time
43
Fault Self-diagnosis: Fast Fault Detection and O&M Guidance
Malfunction Self-diagnosis:
• Eliminates irrelevant malfunction
causes
44
NetCol5000-C Technical Specifications
Note:
Standard condition: inlet/outlet water temperature 10/15℃; return air temperature/RH 37℃/24%
45
NetCol8000-C Technical Specifications
NetCol8000- NetCol8000- NetCol8000- NetCol8000- NetCol8000- NetCol8000-
Model Unit
C070D C130D C190D C070U C130U C190U
Total Cooling Capacity kW 63.2 126.4 189.6 61.9 123.8 185.7
Sensible Cooling
kW 51.4 102.8 154.2 50.3 100.6 150.9
Capacity
Air Flow Rate m3/h 13500 27000 40500 13200 26400 39600
Water Flow Rate l/s 3.02 6.03 9.05 2.95 5.91 8.86
Water Pressure Drop kPa 62.4 85.4 96.0 60.5 82.6 92.7
Full Load Current A 4.7 (15.2) 8.9 (29.9) 13.1 (34.1) 4.7 (15.2) 8.9 (29.9) 13.1 (34.1)
Cooling Capacity Parameters: Inlet/outlet water temperature 7℃/12℃, return air temperature 24℃, 50% RH, static pressure 20 Pa
46
NetCol8000-C210H
Chilled Water (Fan Wall) Smart Cooling Product
47
FusionCol8000-C Typical Application Scenarios
Side View
Top View
1. PAC
2. IT equipment
48 Huawei Confidential
Energy Saving with Higher Chilled Water Temperature
Energy saving: support higher water temp(15→20℃)
Free cooling
time
10%→28%
Chiller
efficiency
15%↑
VS
49 Huawei Confidential
No Doors for Easier Maintenance
No doors and large maintenance space
Front Back
Conventional in-
Fan wall
room up/down flow
horizontal flow unit
chiller water unit
50 Huawei Confidential
No Raised Floor, Faster Deployment
CRAH
CRAH
Fan wall
51 Huawei Confidential
FusionCol8000-C Technical Specifications
Unit Model Unit FusionCol8000-C210H
Dimension: W × D × H mm 2500×2350×1100
① Cooling capacity condition: return air dry bulb temperature 36 ºC/24% RH, inlet/outlet water
temperature 20 ºC/28 ºC.
52 Huawei Confidential
Quiz
53 Huawei Confidential
History of Huawei Smart Cooling Solution
2020+
Continuous
innovation and
development
54 Huawei Confidential
Market Share of Huawei Smart Cooling Solution
9,90%
20,60%
8,60%
37,10% 39,70%
8,60%
13,90%
11,30%
9,20%
8,20%
24,50% 8,40%
HUAWEI VET ENV STU CAN Others VET HUAWEI ENV STU CAN Others
Thank you.
organization for a fully connected,
intelligent world.