Product datasheet
Specifications
C60 - circuit breaker - C60H - 3P -
16A - C curve
25000
notification_critical_stroke Discontinued on: Jan 23, 2021
notification_critical_stroke Discontinued
Main
Range of product C60
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Range Multi9
product name C60
Product or component type Miniature circuit-breaker
Device short name C60H
Device application Distribution
Poles description 3P
Number of protected poles 3
[In] rated current 16 A at 30 °C
network type AC
Trip unit technology Thermal-magnetic
Curve code C
Breaking capacity 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 400...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
25 kA Icu at 125 V DC 2P conforming to EN/IEC 60947-2
30 kA Icu at 230...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
40 kA Icu at 125 V DC 3P conforming to EN/IEC 60947-2
Suitability for isolation Yes conforming to IEC 60947-2
Complementary
Network frequency 50/60 Hz
[Ue] rated operational voltage 440 V AC 50/60 Hz
230...240 V AC 50/60 Hz
400...415 V AC 50/60 Hz
Magnetic tripping limit 5...10 x In
[Ics] rated service breaking 15 kA conforming to EN/IEC 60947-2 - 12...440 V AC 50/60 Hz
capacity 7.5 kA conforming to EN/IEC 60947-2 - 60 V AC 50/60 Hz
5 kA conforming to EN/IEC 60947-2 AC 50/60 Hz
Limitation class 3 conforming to EN/IEC 60947-2
Contact position indicator Yes
control type Toggle
Local signalling ON/OFF indication
Mounting mode Clip-on
Mounting support 35 mm symmetrical DIN rail
Feb 4, 2025 1
Comb busbar and distribution YES
block compatibility
9 mm pitches 6
Height 81 mm
Width 54 mm
Depth 73 mm
Product weight 0.36 kg
Mechanical durability 20000 cycles
Connections - terminals Tunnel type terminals16 mm² flexible
Tunnel type terminals25 mm² rigid
Wire stripping length 14 mm
Earth-leakage protection Separate block
Environment
Tropicalisation 2 conforming to IEC 60068-1
Relative humidity 95 % at 55 °C
Operating altitude 2000 m
Ambient air temperature for -25…60 °C
operation
Ambient air temperature for -40…70 °C
storage
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 7.3 cm
Package 1 Width 5.3 cm
Package 1 Length 8.5 cm
Package 1 Weight 0.33 kg
Contractual warranty
Warranty 18 months
2 Feb 4, 2025
Environmental Data
Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity
via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.
Environmental Data explained
How we assess product sustainability
Use Better
Materials and Substances
EU RoHS Directive Compliant
Use Again
Repack and remanufacture
The product must be disposed on European Union
WEEE markets following specific waste collection and never end
up in rubbish bins
Feb 4, 2025 3