TRUSS
TRUSS
of
Emergency staircase & canopy
of Main block
Lumbini Provincial Hospital
1
Contents
List of Figures..........................................................................................................................................3
List of Tables...........................................................................................................................................3
Introduction..............................................................................................................................................4
Material properties...................................................................................................................................4
Loads....................................................................................................5
Wind load parameters...........................................................................5
Seismic design parameters....................................................................9
Response spectrum method................................................................10
Load Combinations:...........................................................................10
Modal analyses:.....................................................................................................................................11
Storey Drift............................................................................................................................................12
Structural Design................................................................................13
Steel design.........................................................................................13
Design of welded connection.................................................................................................................13
Design of pedestals................................................................................................................................14
Design of anchor bolts:..........................................................................................................................15
2
Member design of ISMB 300 (upper crown- B867).........................20
Gusset Plate Design Check.................................................................24
ISMB 300 connection to Built-up Column.........................................34
Design of base plate and anchor bolts................................................36
Design of foundation..........................................................................37
Seismic Gap Check.............................................................................39
List of Figures
Figure 1: 3D view of the building....................................................................................................4
Figure 2 Storeywise drift check.....................................................................................................12
Figure 3: stress distribution in base plate.......................................................................................14
Figure 4: Arrangement of bolts......................................................................................................15
Figure 5: Prying forces on base plates, cleat angles......................................................................16
Figure 6 Soil Pressure for DL+LL <100 kN/m2..........................................................................38
Figure 7 Top Rebar (max 1277 mm2)...........................................................................................38
Figure 8 Strap Beam longitudinal rebars.......................................................................................39
List of Tables
Table 1: Shells loads........................................................................................................................5
3
Introduction
This report summarizes the procedure for analyzing and designing the steel truss structure below
Figure 1) of the canopy truss.
Material properties
The material specifications of the structural components of the buildings follow IS 875 (Part 1) [2]
and are as follows. `
Structural steel
Indian standard steel sections of grade Fe250 has been adopted herein.
4
Loads
The shell loads consists of live and dead loads. The live loads added to the structure are based on IS
875 (Part 2) [2]. Specifically, an inaccessible live load of 0.75 kN/m2 has been adopted in this study.
The dead loads applied to the structure are distinguished into two components, i.e. (a) self-weight, and
(b) superimposed dead loads. The superimposed dead loads in the form of finishing has been applied
to the shell.
finishing 1.5
inaccessible live 0.06
5
Estimation of internal and external pressure coefficients of the building taking C pi =± 0.7:
Note for all cases negative sign on the pressure indicates suction on the outer surface.
6
IS 875(Part 3) :
2015 Table 5,
Page(13)
POSITIVE COEFFICENT
CPI FOR WALLS
wind
0 0 90 90 180 180 270 270
angle
+Wy +Wy -Wx -Wx -Wy -Wy +Wx +Wx
ROOF
H L H L H L H L
ANGLE
Cpe 5 -1.00 -0.50 -1.00 -0.50 -0.50 -1.00 -1.00 -0.50
Cpe 10 -1.00 -0.50 -1.00 -0.50 -0.40 -1.00 -1.00 -0.50
Cpe 10 -1.00 -0.50 -1.00 -0.50 -0.40 -1.00 -1.00 -0.50
Cpi 0.70 0.70 0.70 0.70 0.70 0.70 0.70 0.70
kc kc 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
kd kd 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90
ka ka 0.88 0.88 0.88 0.88 0.88 0.88 0.88 0.88
pd 0.77 0.77 0.77 0.77 0.77 0.77 0.77 0.77
force/area -1.30 -0.92 -1.30 -0.92 -0.84 -1.30 -1.30 -0.92
H1 H2 L1 L2 He Le
-2 -1.5 -2 -1.5 -2 -2
-2 -1.5 -2 -1.5 -2 -2
-2.00 -1.50 -2.00 -1.50 -2.00 -2.00
0.70 0.70 0.70 0.70 0.70 0.70
1.00 1.00 1.00 1.00 1.00 1.00
0.90 0.90 0.90 0.90 0.90 0.90
0.88 0.88 0.88 0.88 0.88 0.88
0.77 0.77 0.77 0.77 0.77 0.77
-2.07 -1.69 -2.07 -1.69 -2.07 -2.07
7
kd kd 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90
ka ka 0.88 0.88 0.88 0.88 0.88 0.88 0.88 0.88
pd 0.77 0.77 0.77 0.77 0.77 0.77 0.77 0.77
force/
-0.23 0.15 -0.23 0.15 0.11 -0.23 0.40 0.40
area
The approximate fundamental time period is increased by amplification factor of 1.25 as per Cl. 5.1.3.
Other factors considered for seismic load calculations are as follows
Zone factor, Z = 0.35 for Kathmandu [Table 4.5, Cl. 4.1.4, IS 105:2020]
Importance factor, I = 1.25 [Table 4.6, Cl. 4.1.5, NBC 105:2020]
Ductility Factor, R [Table 5.2, Cl. 5.3, NBC 105:2020]
For Ultimate Limit State, Rμ =3.5 for RC special moment frame system
For Serviceability Limit State, Rs = 1 for special moment frame system
Over strength Factor, W [Table 5.2, Cl. 5.4, NBC 105:2020]
For Ultimate Limit State, Wu = 1.3 for special moment frame system
For Serviceability Limit State, Ws = 1.15 for special moment frame system
The seismic weight is determined based on the following mass source. (Table -5.1, Cl.5.2, NBC
105:2020)
Clause 10.3 NBC
Height of structure H , m 49.8
8
Horizontal base shear
Ch(T)=z(1+hp/H)ap/μp 0.2524
Load Combinations:
Load combinations at limit state as per NBC 105:2020 and IS 800 are as follows:
1.2 DL+1.5≪¿
DL+ 0.3≪± E L x
DL+ 0.3≪± E L y
DL+ 0.3≪± R x
DL+ 0.3≪± R y
DL+ 0.3≪± R z
1.2 DL+1.2≪±1.2 Wx ¿
1.2 DL+1.2≪±1.2 Wx ¿
1.2 DL+1.2≪±1.2 Wy ¿
1.2 DL+1.2≪±1.2 Wy ¿
1.2 DL+1.2≪± 0.6Wx ¿
1.2 DL+1.2≪± 0.6Wx ¿
1.2 DL+1.2≪± 0.6Wy ¿
1.2 DL+1.2≪± 0.6Wy ¿
0.9 DL ± 1.5 Wx ¿
0.9 DL ± 1.5 Wx ¿
0.9 DL ± 1.5 Wy¿
0.9 DL ± 1.5 Wy¿
1.5 DL ± 1.5Wx ¿
9
1.5 DL ± 1.5Wx ¿
1.5 DL ± 1.5Wy ¿
1.5 DL ± 1.5Wy ¿
where,
DL: dead load (self-weight+superimposed),
LL: live load,
EL: earthquake load (equivalent static),
RL: earthquake load (response spectrum)
W: wind load
Note that the subscripts x , y, and z denote the direction of applied forces. The earthquake loads are
applied at ultimate limit state condition.
Storey Drift
As per Cl. 5.6.3 of NBC 105:2020, the story drift to the corresponding story shall not exceed:
0.025 at ultimate limit state
0.006 at serviceability limit state
In this building the story displacement is limited to 75 mm at ultimate limit state and 25.2mm at
serviceability. From the analysis the displacements of the mass center of various floors are obtained
and are shown in along with story drift below.
10
Structural Design Figure 2 Storeywise drift check
The design of reinforced concrete structural elements follows IS 800, IS 456:2000 [4] and
NBC105:2020 [1] codes.
Steel design
The design assumes the structural framing type of special concentric braced frame. The adopted
sections ISMB, ISNB and ISMC are of section class 1. The ISMC built up column is semi compact,
buckling class is a. The ISNB sections are of column buckling class “a” along all axes and section
class is class 1, whereas the ISMB are of buckling class “a” along all axes. Connections between any
two truss element is welded. The partial safety factors assumed are as follows:
definition symbol value
resistance governed by yielding γ m0 1.10
11
field welds γ mw 1.50
fu
f e =√ f a +3 q ≤
2 2
√3 γ mw
P
Where, f a or q=
tt lw
The weld capacity is should be greater than the design yield capacity R y of the section by an
overstrength γ ov , i.e.,
Rdw ≥1.1 γ ov R y
Herein, γ ov =1.25.
12
Design of pedestals
Design of moment resisting base plates:
The combined stress due to axial load and bending moment as shown in Figure 3 is
P 6e
f= (1 ± )
LB L
The length L of the base plate is selected such that, eccentricity e ≤ L/6
√
t s= 2.5 w ( a −0.3 b ) γ m 0 /f y >t f
2 2
13
Design of anchor bolts:
Axial force + moment
For the following arrangement of the bolts (as an example, Figure 4)
N u=k √ f ck l
1.5
}
Rnb=0.9 f ub A nv
f A γ > F b /n
0.9 f ub Anv < yb sb mb
γm 0
d fy
l= ×
4 τ bd γ m 0
Prying force
Prying force in base plates and structural members flanges (Clause 10.4.7, IS 800, Figure 5) :
4
lv βη f o b c t
Q= [T e − 2
]
2 le 27 l e l v
14
Figure 5: Prying forces on base plates, cleat angles
Shear force
The design shear capacity of the bolts is given by (Clause 10.3.3, IS 800):
V nsb
V dsb =
γ mb
fu
Where, V nsb = (nn A nb+ ns A sb )
√3
( )( )
2 2
V sb Tb
+ ≤ 1.0
V db T db
15
Buckling (Clause 7.1):
The design compressive strength of member is P< Pd , where Pd = Ae f cd . Here, Ae effective
sectional area (usually the gross cross-sectional area of the member), while f cd is the design
compressive strength estimated as follows:
f y /γ m 0
f cd =
2 0.5
ϕ+ [ ϕ −λ ]
2
ϕ=0.5 [ 1+ α ( λ−0.2 ) + λ 2 ]
λ=√ f y /f cc
2
π E
f cc =
( )
2
KL
r
α equals 0.21, 0.34, or 0.49 for buckling class a, b or c respectively.
βb Z p f y
M d=
γ m0
Under serviceability conditions,
M d <1.2 Z e f y /γ m 0 for simply supported condition
if
A nf f y γ m 1 1
< × ×
A gf f u γ m 0 0.9
Reduced effective flange area is used in estimating design bending moment as per Clause 8.2.1.4.
Shear lag effect: shear lag effects are disregarded as per clause 8.2.1.5.
16
Where,
f bd= χ ¿ f y / γ m 0
1
χ ¿= 0.5
≤1
ϕ ¿ + [ ϕ − λ¿ ]
2 2
¿
Where, f cr , b is obtained from Table 14 in case of simply supported conditions. More general
conditions are evaluated as per Annex E of IS800
Shear:
The factored design shear force V in a beam due to external actions satisfy V ≤V n /γ m 0
The nominal plastic shear resistance under pure shear is given by:
A v f yw
V n=
√3
Where A v is the shear area of the member.
ϵ = √ 250 / f y
The shear buckling strength is estimated from the following (Clause 8.4.2.2):
V n ≤V cr
V cr = A v τ b
17
{
f yw
when λ w ≤0.8
√3
f
τ b= [ 1−0.8 ( λ w −0.8 ) ] yw when0.8 ≤ λ w < 1.2
√3
f yw
when λ w ≥ 1.2
λw √ 3
2
λ w =√ f yw /( √ 3 τ cr ,e )
2
Kv π E
τ cr , e =
( )
2
d
12 ( 1−μ )
2
tw
Combined forces
Combined shear and bending (Clause 9.2)
For Plastic section:
M dv =M d −β ( M d −M fd ) ≤1.2 Z e f y /γ m 0
( )
2
2V
Where β= −1
Vd
[
M eff = M −
ψT Z eq
A ]
≤ Md
P C my M y K ¿ M z
+K y + ≤ 1.0
P dy M dy M dz
P Cmy M y C mz M z
+0.6 K y +K z ≤ 1.0
P dz M dy M dz
18
19
Beam design check
deflection = 15.74 mm
permissible 17.2666
deflection(L/240) = 7 mm
Hence,o
k
20
21
References
[1] NBC 105:2020: Nepal national building code
[2] IS:875 (Part 1) – 1987 Code of practice for design loads (other than earthquake) for
buildings and structures, part 1, dead loads – unit weight of building materials and stored
materials (second revision)
[3] IS:875 (Part 2) - 1987 Code of practice for design loads (other than earthquake) for
buildings and structures, part 2 imposed load (second revision)
[4] IS 456:2000 Code of practice for plain and reinforced concrete (fourth revision)
[5] FEMA 273 – 1997 NEHRP guidelines for the seismic rehabilitation of buildings
[6] Bowles JE, Foundation analysis and design (1988).
[7] Murthy VNA, Geotechnical engineering: principles and practices of soil mechanics and
foundation engineering
[8] IS 1893 (Part 1) - 2016 Criteria for earthquake resistant design, part 1, general provisions
and buildings
[9] IS 1893 (Part 2) - 2014 Criteria for earthquake resistant design, part 2, liquid retaining
tanks
[10] IS 1893 (Part 3) - 2014 Criteria for earthquake resistant design, part 2, bridges and
retaining walls
[11] SP 7 – 2005 National building code of India
[12] IS 1786 – 2008 High strength deformed steel bars and wires for concrete reinforcement
22