instument, auto, three phase transformer
instument, auto, three phase transformer
1
Let I2 = Current drawn by the load
I1 = Current in primary side
Then the current through the section B-C is equal to (I1-I2)
Here, |I1| < |I2|, Therefore | I1-I2| will be negative.
| I1-I2| is going to be used to calculate weight of copper
winding used in the section B-C. Weight could not be
negative. Hence, the direction of (I1-I2) is made reverse in
Fig.2.39 to get positive value of (I2-I1).
Let us try to compare the weight of copper used in the auto-
transformer winding with the two winding transformer for
performing the same operation. Fig.2.39 Auto transformer
2
W auto (N1 - N 2 )I1 N 2 ( I 2 - I1 ) N1I1 - N 2 I1 N 2 I 2 - N 2 I1
Wtw ( N1I12 N 2 I 2 ) ( N1I12 N 2 I 2 )
2N 2
Its 𝐼1 don’t W auto N1I1 N 2 I 2 - 2.N 2 I1 2.N 2 I1 W auto N1
Or 1- Or 1-
confuse Wtw ( N1I12 N 2 I 2 ) ( N1I12 N 2 I 2 ) Wtw N .I
1 2 2
N1.I1
N2 I 1 W auto 2.K
( But K and 2 ) 1- (1 K )
N1 I1 K Wtw 2
Or Wauto = (1 – K) × Wtw (A)
V2 200
Case-I : If V1 = 220 V and V2 = 200V i.e. K 0.909 1
V1 220
Then, Wauto = (1 – 0.909) × Wtw = 0.091 × Wtw
That means, weight of copper used in auto transformer is only 9.1 % of weight of copper used in the two
winding transformer. There is significant save in weight of copper.
V2 6
Case-II : If V1 = 220 V and V2 = 6 V ( i.e. K 0.0272 not 1 )
V1 220
That means, weight of copper used in auto transformer is only 97.27% of weight of copper used in the two
winding transformer. (No significant saving)
Hence, the saving in weight of copper used in the auto-transformer is only significant when the
transformation ratio is nearly equal to unity.
3
Instrument Transformers
Instrument transformers are special purpose transformer designed with highly accurate transformation ratio
so it can be used in instrumentation and protection relay scheme. There are two types of instrument
transformers:
i) Current transformer (CT)
ii) Potential transformer (PT)
4
Let I1 = High current through the primary winding of CT
I2 = Secondary current through the ammeter
N1 = Numbers of turns in the primary winding of CT
N2 = Numbers of turns in the secondary winding of CT
Then, transformation ratio is given by:
N2 I
K 1 Or I1 = K. I2 (2.34)
N1 I2
Hence, by measuring I2 by low range ammeter, I1 can be estimated by using eqn (2.34). The primary
winding of normal two winding transformer is exited by a constant voltage source V1 and the no-load
current I0 remains constant and accordingly the magnetic flux in the core remains constant from no-load
to full load. Whereas incase of CT, the primary winding is excited by load current, which varies with the
system load. When the system load current I1 increases, the magnetic flux produced by the primary
winding of CT increases and at the same time, secondary current I2 also increases. Therefore, magnetic
flux produced by secondary winding also increases, which cancels the magnetic flux due to increase in
I1. Hence, the net magnetic flux in the core remains constant.
However, if the ammeter is removed with primary winding of CT excited, I2 will be zero and secondary
winding of CT can not produced opposing magnetic flux to cancel increased magnetic flux due to I1. In
such a case, the net magnetic flux will be very high thus by resulting high iron loss and high induced emf
in the primary and secondary windings of CT. The high emf induced in the windings will damage the
insulation of the winding and high iron loss will over heat the windings. Hence, the secondary winding
of CT never shall keep open with primary winding excited. If the ammeter is to be removed for repair
and maintenance purpose, the secondary winding shall be short circuited by a thick wire.
5
Potential Transformer (PT)
N V
Transformation ratio K 2 2
N V Fig.2.43 Connection diagram of PT
1 1
It will be known value for a potential transformer
Here, V1 is the system voltage of high voltage circuit whose value is to be measured.
If V2 is the reading of low range voltmeter connected across the secondary winding of PT,
then the value of V1 can be estimated as:
V
V 2 (2.35)
1 K
6
Three Phase Transformer
Large scale generation of electric power is usually three phase for the sake of better
efficiency and economy.
If the generated power is to be transmitted to a load center through a long route, the
transmission is done at higher voltage in order to reduce the power loss and voltage drop in
the line. Therefore, three-phase step up transformer is necessary at sending end of the line. At
the receiving end of the line, the voltage is again step down to a lower value suitable for
consumers. Therefore, three-phase step down transformer is required at the receiving end of
the line.
In the earlier days, three units of single phase transformers were used to step up or step down
the three-phase voltage. Later on, three-phase transformer was introduced to overcome the
disadvantages of using single phase transformer for three phase system.
7
Polarity of the each transformer has to be
taken care while connecting three units of
single phase transformers to step up or step
down the three-phase voltage.
8
Disadvantages of this system are:
• This system is more expensive than a single unit of three phase transformer
of equivalent capacity.
• This system is less efficient than a single unit of three phase transformer of
equivalent capacity.
• This system is occupies more space than a single unit of three phase transformer
of equivalent capacity.
•If it is required to have a stand by unit for better reliability of supply continuity
during the maintenance period, only one unit of single phase transformer can be
installed as a spare unit. Whereas in case of three phase transformer, the whole three
phase unit has to be installed as spare unit. Hence, the investment on spare will be
less in this system.
9
Evolution of Three Phase Transformers :
Let us consider three units of single phase transformers used for three phase system as shown in
Fig.2.45. Here, the iron core of three units are kept close together and only primary windings are shown
for simplicity.
R = m Sint
Y = m Sin(t-1200)
B = m Sin(t-2400) = m Sin(t+1200)
Therefore, no magnetic flux will pass through the common central part core. Hence, the core for three
phase transformer can be made by removing the common central part core as shown in Fig.2.46. The
volume of iron core in this type of core is only about 67 % of the volume of iron core used in three units of
single phase transformer and accordingly the iron loss of the transformer will be less.
10
Fig.2.46 Cross-sectional view of three phase transformer core and windings
R = m Sint
Y = m Sin(t-1200)
B = m Sin(t-2400) = m Sin(t+1200)
Therefore, magnetic flux in the central core will be ϕR = ϕm up-ward and magnetic flux in the other
two side core will be ϕY =0 .5ϕm and ϕB =0 .5ϕm downward. In this way total flux through the
central core gets return paths through other two side core.
11
Three Phase Transformer Connections :
A three phase transformer has three sets of winding in primary side and another three sets of windings in
secondary side. These six sets of winding can be connected to give various configurations of three phase
transformer connections.
12
The cross-sectional area of the winding depends upon the phase current. Hence, a Star /
Star connection is most economical for low capacity high voltage transformer.
If the primary R-phase phasor and secondary R-phase phasor are compared with the
longer arm and shorter arm of a clock, the above phasor diagram crossponds to zero hour
in the clock. Hence, this connection is named as Y-y0 phasor group.
13
ii) Delta / Delta (∆ / ∆ ) connection:
14
iii) Star / Delta (Y / ∆ ) connection:
15
iv) Delta / Star (∆ / Y ) connection:
16
Illustrative example :
A 3-phase, 50 Hz, 11kV/400V Delta/Star transformer has balanced star-connected load of 90 kW at 0.8
lagging power factor. Calculate: secondary line current, primary phase current and primary line current
in the following two cases:
Case-I : Transformer is ideal without any power loss
Case-II : Efficiency = 96%
Solution:
Given: VL1 = VP1 =11 kV, VL2 = 400V,
Load = 90 kW, Load pf = 0.8 lagging
V 400
V L2 230.9 V
P2 3 3
Case-I : Transformer is ideal without any power loss:
90,000
Output power 3.VL2 . I L2 .Cos2 Or I L2 162.38 Amp Secondary line current I P2
3 400 0.8
Since, there is no power loss, Input power = output power
17
Alternative method:
VP1×IP1 = VP2×IP2 (per phase power balance )
VP2 I P2 230.9 162.38
OR I P1 3.406 Amp
V P1 11000
93,750
I L1 6.15 Amp
3 1100 0.8
I L1
Then, I P1 3.55 Amp
3
18
Numerical:
A 230V/ 2300V single-phase transformer is excited by 230V ac voltage. The equivalent resistance and reactance referred to primary side are 0.1 ohm
and 0.4 ohm respectively. Given that R0 = 500 ohms and X0 = 200 ohms. The load impedance is (400 + j600) ohm. Calculate: a) Primary current b)
Secondary terminal voltage c) Input power factor.
The following test results were obtained on a 20 kVA, 2200/220 V, 50 Hz single phase transformer:
Open-circuit Test (LV Side): 220 V, 1.1 A, 125 W
Short Circuit Test (HV Side): 52.7 V, 8.4 A, 287 W
Calculate the equivalent circuit parameters referred to L.V side and draw the equivalent circuit.
With the secondary short circuited, if 200 V is applied to a 200 KVA, 1-phase, 3300/400 V transformer, the current through primary was
the full load value and the input power was 1650 W. Calculate the secondary p. d. and percentage regulation when the secondary load is
passing 300 A at 0.707 p.f. lagging with normal primary voltage.